Siemens Drives Fault Codes & Troubleshooting

Technical troubleshooting reference for Siemens SINAMICS modular drives, Micromaster inverters, SIMOVERT power systems, and high-precision servo amplifiers. Select your drive model series below to access parameter checks, trip code descriptions, and physical test sequences.

15 AC Inverter Series 2 DC Power Converters 4 Servo & Motion Drives

Siemens AC Variable Frequency Drives

15 Models

Siemens Industrial DC Drives

2 Models

Siemens Servo & System Motion Drives

4 Models

Most Common Siemens Drive Fault Codes

Diagnostic Quick Reference
Fault Code Legacy MM4 Fault Description Root Cause & Diagnostic Check
F30001 F0001 Power Unit: Overcurrent Output phase short-circuit, rapid motor acceleration, mechanical load binding, or damaged IGBT power transistors.
F30002 F0002 Power Unit: DC Link Overvoltage Motor regenerative energy during rapid deceleration exceeding limit. Check braking chopper or extend ramp-down time (p1121).
F30003 F0003 Power Unit: DC Link Undervoltage Main line power failure, blown incoming fuse, or primary supply voltage dip below minimum threshold.
F07900 F0011 Drive: Motor Blocked / Stalled Motor operating at current limit for longer than stall detection time (p2177). Check mechanical jamming and motor brake release.
F30004 F0004 Inverter Heatsink Overtemperature Internal cooling fan failed or blocked, clogged heat exchanger, or ambient control cabinet temperature exceeding 50°C.
F07800 — Drive: No Enable Acknowledgment Missing safety circuit enable (Safe Torque Off – STO terminal missing 24V) or missing PLC control word enable signals.
F30027 — Precharging DC Link Time Out Defective line contactor, damaged precharging resistors, or short circuit across internal DC bus rails.

How to Clear & Acknowledge Siemens Drive Faults

  1. Operator Panel Reset: On the BOP-2 (Basic Operator Panel) or IOP-2 (Intelligent Operator Panel), press the orange/red Fn (Function / Acknowledge) key or select Acknowledge Fault on the menu screen.
  2. Digital Input Reset: Trigger the programmed digital input terminal assigned to fault acknowledgment (parameter p2103 or p2104 [BI: Faults acknowledge]).
  3. TIA Portal / STARTER Software: In the Startdrive or STARTER online commissioning dashboard, open the Diagnostics tab and click “Acknowledge All Faults”.
  4. PROFINET / PROFIBUS Control Word: Set Bit 7 of Control Word 1 (STW1.7) from `0` to `1` (positive edge trigger) from the master PLC (S7-1200 / S7-1500).
  5. Power Cycle: Disconnect line voltage (and auxiliary 24V DC control supply), wait until all LEDs on the Control Unit extinguish, and reapply power.
⚠️ High-Voltage Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC link capacitor voltage measures strictly below 50VDC across terminals (DCP / DCN) before opening Power Module covers or servicing motor output terminals (U, V, W) on any Siemens drive.