Delta ASDA-A Servo Drive Fault Codes & Diagnostic Guide
Comprehensive fault code reference directory, AL alarm definitions, and step-by-step troubleshooting procedures for the Delta ASDA-A advanced AC servo drive series. Search or filter through the complete diagnostic database below.
Power Range
0.1 – 3.0 kW (100W – 3 kW)
Supply Voltage
200–230V AC (1-Ph / 3-Ph)
Control Modes
Position / Speed / Torque Modes
Operator Interface
Integrated 5-Digit 7-Segment LED Keypad
Complete Delta ASDA-A Servo Drive Fault Code Directory
Use the search box in the table below to quickly find your alarm code (e.g., type AL001, AL003, AL009, or Overload).
| Fault Code and Meaning | Other |
|---|---|
| ALE01: Overcurrent | Potential Cause - Short-circuit at drive output (U, V, W) - Motor wiring error - IGBT error - Control parameter setting error - Control command setting error Checking Method - Check the wiring connections between drive and motor. 2. Check if the wire is short-circuited. - Check if the wiring steps are all correct when connecting motor to drive. - Heat sink overheated - Check if the setting value exceeds the factory default setting. - Check if the control input command is unstable (too much fluctuation). Corrective Actions - Repair the short-circuited and avoid metal conductor being exposed. - Follow the wiring steps in the user manual to reconnect wiring. - Please contact your distributor for assistance or contact with Delta. - Set the setting back to factory default setting and then reset and adjust the parameter setting again. - Ensure that input command frequency is stable (too much fluctuation). 2. Activate filter function. |
| ALE02: Overvoltage | Potential Cause - The main circuit voltage has exceeded its maximum allowable value. - Input power error (Incorrect power input) Checking Method - Use voltmeter to check whether the input voltage falls within the rated input voltage. (For voltage specification, please refer to section 11.1 in Chapter11.) - Use voltmeter to check whether the input voltage is within the specified limit. Corrective Actions - Use correct power supply or stabilizing power. - Use correct power supply or stabilizing power. |
| ALE03: Undervoltage | Potential Cause - The main circuit voltage is below its minimum specified value. - No input voltage at main circuit. - Input power error (Incorrect power input) Checking Method - Check whether the wiring of main circuit input voltage is normal. - Use voltmeter to check whether input voltage at main circuit is normal. - Use voltmeter to check whether the input voltage is within the specified limit. Corrective Actions - Reconfirm voltage wiring. - Reconfirm power switch. - Use correct power supply or serial stabilizing power. |
| ALE04: Reserved | Corrective Actions - (Note: This applies to the standard ASDA-A series. This code has a different meaning for the ASDA-A+ series, listed separately below.) |
| ALE05: Regeneration error | Potential Cause - Regenerative resistor is not connected. - Regenerative switch transistor fault - Parameter setting is in error Checking Method - Check the wiring connection of regenerative resistor. - Check if regenerative switch transistor is short-circuited. - Confirm the parameter setting and specifications of regenerative resistor. Corrective Actions - Reconnect regenerative resistor. - Please contact your distributor for assistance or contact with Delta. - Correctly reset parameter again. |
| ALE06: Overload | Potential Cause - The drive has exceeded its rated load during continuous operation. - Control system parameter setting is incorrect. - The wiring of drive and encoder is in error. Checking Method - Check if the drive is overloaded. - Check if there is mechanical vibration. - Accel/Decel time setting is too fast. - Check the wiring of U, V, W and encoder. Corrective Actions - Increase motor capacity or reduce load. - Adjust gain value of control circuit. - Decrease Accel/Decel time setting. - Ensure all wiring is correct. |
| ALE07: Overspeed | Potential Cause - Speed input command is not stable (too much fluctuation). - Over-speed parameter setting is defective. Checking Method - Use signal detector to detect if input signal is abnormal. - Check if over-speed parameter setting value is too low. Corrective Actions - Ensure that input command frequency is stable (not fluctuate too much) and activate filter function (P1-06, P1-07 and P1-08). - Correctly set over-speed parameter setting (P2-34). |
| ALE08: Abnormal pulse control command | Potential Cause - Pulse command frequency is higher than rated input frequency. Checking Method - Use pulse frequency detector to measure input frequency. Corrective Actions - Correctly set the input pulse frequency. |
| ALE09: Excessive deviation | Potential Cause - Maximum deviation parameter setting is too small. - Gain value is too small. - Torque limit is too low. - There is an overload. Checking Method - Check the maximum deviation parameter setting and observe the position error value when the motor is running. - Check for proper gain value. - Check torque limit value. - Check for overload condition. Corrective Actions - Increases the parameter setting value of P2-35. - Correctly adjust gain value. - Correctly adjust torque limit value. - Reduce external applied load or re-estimate the motor capacity. |
| ALE10: Watch dog execution time out | Potential Cause - Watch dog execution error. Checking Method - Check and reset the power supply. Corrective Actions - If there are any abnormal conditions after resetting the power supply, please contact your distributor for assistance or contact with Delta. |
| ALE11: Encoder error (Position detector fault) | Potential Cause - The wiring of encoder is in error. - Encoder is loose - The wiring of encoder is defective. - Encoder is damage - The circuit (loop) of Encoder is in error. Checking Method - Check if all wiring is correct. 2. Check if the users conduct the wiring by the wiring information in the user manual. - Examine the encoder connector. - Check if all connections are tight. - Check the motor for the damage. - Check the drive for the damage. Corrective Actions - Ensure all wiring is correct. - Install the motor again. - Conduct the wiring again. - Repair or replace the motor. - Repair or replace the drive. |
| ALE12: Adjustment error | Potential Cause - The setting value of drift adjustment has exceeded its maximum allowable value. Checking Method - Remove CN1 wiring. 2. Execute the drift adjustment again. (Set P2-08 to 20 first, and then set P4-10 to 5.) Corrective Actions - If the error does not clear after executing the drift adjustment again, please contact your distributor for assistance or contact with Delta. |
| ALE13: Emergency stop activated | Potential Cause - Emergency stop switch is activated. Checking Method - Check if emergency stop switch is On or Off. Corrective Actions - Activate emergency stop switch. |
| ALE14: Reverse (CWL) limit switch error | Potential Cause - Reverse limit switch is activated. - Servo system is not stable. Checking Method - Check if reverse limit switch is On or Off. - Check the value of control parameter setting and load inertia. Corrective Actions - Activate reverse limit switch. - Modify parameter setting and re-estimate motor capacity. |
| ALE15: Forward (CCWL) limit switch error | Potential Cause - Forward limit switch is activated. - Servo system is not stable. Checking Method - Check if forward limit switch is On or Off. - Check the value of control parameter setting and load inertia. Corrective Actions - Activate forward limit switch. - Modify parameter setting and re-estimate motor capacity. |
| ALE16: IGBT temperature error | Potential Cause - The drive has exceeded its rated load during continuous operation. - Short-circuit at drive output. Checking Method - Check if there is overload or the motor current is too high. - Check the drive input wiring. Corrective Actions - Increase motor capacity or reduce load. - Ensure all wiring is correct. |
| ALE17: Memory error | Potential Cause - Data error in Memory read-out/write-in. Checking Method - Reset parameter or power supply. Corrective Actions - If the error does not clear after resetting the power supply, please contact your distributor for assistance or contact with Delta. |
| ALE18: DSP communication error | Potential Cause - Control power is in error. Checking Method - Check and reset control power Corrective Actions - If the error does not clear after resetting the power supply, please contact your distributor for assistance or contact with Delta. |
| ALE19: Serial communication error | Potential Cause - Communication parameter setting is defective. - Communication address is incorrect. - Communication value is incorrect. - Setting value in time out parameter is not correct. - Not receiving communication command for a long time. Checking Method - Check the communication parameter setting. - Check the communication address. - Check the communication value. - Check communication time out parameter setting. - Check whether communication cable is loose or broken. Corrective Actions - Correctly set parameter setting. - Correctly set communication address. - Correctly set communication value. - Correctly set P3-07. - Tighten the communication cable, make sure the communication cable is not damaged and ensure all wiring is correct. |
| ALE20: Serial communication time out | Potential Cause - Communication parameter setting is defective. - Communication address is incorrect. - Communication value is incorrect. - Setting value in time out parameter is not correct. - Not receiving communication command for a long time. Checking Method - Check the communication parameter setting. - Check the communication address. - Check the communication value. - Check communication time out parameter setting. - Check whether communication cable is loose or broken. Corrective Actions - Correctly set parameter setting. - Correctly set communication address. - Correctly set communication value. - Correctly set P3-07. - Tighten the communication cable, make sure the communication cable is not damaged and ensure all wiring is correct. |
| ALE21: Command write-in error | Potential Cause - Control power is in error. Checking Method - Check and reset control power Corrective Actions - If the error does not clear after resetting the power supply, please contact your distributor for assistance or contact with Delta. |
| ALE22: Input power phase loss | Potential Cause - Control power supply is in error. Checking Method - Check the power cable and connections of R, S. T. Check whether the power cable is loose or the possible loss of phase on input power. Corrective Actions - If the fault does not clear even when the three-phase power is connected correctly, please contact your distributor for assistance or contact with Delta. |
| ALE23: Pre-overload warning | Potential Cause - The drive is going to overload. Checking Method - Check the load condition of the servo motor and drive. - Check the setting value of P1-56. Check whether the setting value of P1-56 is to small. Corrective Actions - Please refer to the correction actions of ALE06. - Increase the setting value of P1-56 or set P1-56 to 100 and above. |
| ALES7: Internal command execution time out | Potential Cause - An error occurs when internal command is executing. Checking Method - Check and reset control power Corrective Actions - If the error does not clear after resetting the power supply, please contact your distributor for assistance or contact with Delta. |
| ALE98: DSP communication error | Potential Cause - Maybe the hardware is damaged. Checking Method - Check and reset control power Corrective Actions - If the error does not clear after resetting the power supply, please contact your distributor for assistance or contact with Delta. |
| ALE99: DSP communication error | Potential Cause - Maybe the hardware is damaged. Checking Method - Check and reset control power Corrective Actions - If the error does not clear after resetting the power supply, please contact your distributor for assistance or contact with Delta. |
| ALE04: "Mismatch" error (ASDA-A+ Series Only) | Potential Cause - The type of the servo motor is incorrect. Checking Method - Check if the servo drive and servo motor are not correctly matched for size (power rating). Corrective Actions - Repair or replace the servo drive or the servo motor. |
| ALE24: Encoder error (Position detector fault) (ASDA-A+ Series Only) | Potential Cause - Maybe the Encoder is damaged. Checking Method - N/A (See corrective action) Corrective Actions - If the error does not clear after resetting the power supply, please contact your distributor for assistance or contact with Delta. |
| ALE25: Encoder error (Position detector fault) (ASDA-A+ Series Only) | Potential Cause - The servo drive automatically detect the servo motor is in error. Checking Method - Check if the servo motor is properly grounded. - Check if the encoder signal cables are placed in separate conduits from the cables connected to R, S, T and U, V, W terminals to prevent the interference. - Check if the shielded cables are used when performing Encoder wiring. Corrective Actions - Please connect the grounding (green color) of U, V, W terminal to the heatsink of the servo drive. - Ensure that the encoder signal cables are placed in separate conduits from the cables connected to R, S, T and U, V, W terminals to prevent the interference. - Please use shielded cables for Encoder wiring. |
How to Clear & Reset Delta ASDA-A Servo Drive Faults
- Keypad Reset: Press and hold the SHIFT key on the integrated 5-digit LED keypad for more than 3 seconds after diagnosing and rectifying the alarm root cause.
- Digital Input Signal (ARST): Trigger the external digital input configured for Alarm Reset (ARST, assigned via Parameter Group P2-10 through P2-17 set to value 0x0002 or 0x0102).
- Delta ASDA-Soft PC Tool: Connect your PC via the RS-232 / RS-485 serial communication port (CN3), open Delta ASDA-Soft software, and click “Alarm Reset” on the diagnostic status monitor.
- Modbus Serial Communication: Transmit an alarm clear command or reset control word via the built-in RS-485 / RS-232 Modbus RTU/ASCII communication protocol.
- Mains Power Cycle: Disconnect the incoming AC power supply line (R, S, T), wait until the 5-digit LED display and the internal “CHARGE” indicator LED extinguish completely (allowing bus capacitors to discharge), then turn on mains power.
⚠️ High-Voltage Electrical Safety Warning:
Hazardous residual electrical charge remains stored in the intermediate DC bus capacitors after disconnecting the main power supply. Always verify with a calibrated digital multimeter that the DC bus potential measures strictly below 25VDC across terminals [P / +] and [D / -] before handling wiring, inspecting motor terminals U, V, and W, or performing maintenance on the Delta ASDA-A servo drive.