Delta ASDA-B2 drive

Home / Delta / Delta ASDA-B2 drive

Delta ASDA-B2 Servo Drive Fault Codes & Diagnostic Guide

Comprehensive fault code reference directory, AL alarm definitions, and step-by-step troubleshooting procedures for the Delta ASDA-B2 high-precision AC servo drive series. Search or filter through the complete diagnostic database below.

High-Precision AC Servo Drive Power: 0.1 to 3.0 kW (100W to 3 kW) 17-bit Optical Encoder & Built-in Modbus
Power Range 0.1 – 3.0 kW (100W – 3 kW)
Supply Voltage 200–230V AC (1-Ph / 3-Ph)
Control Modes Position / Speed / Torque Modes
Operator Interface Integrated 5-Digit 7-Segment LED Keypad

Complete Delta ASDA-B2 Servo Drive Fault Code Directory

Use the search box in the table below to quickly find your alarm code (e.g., type AL001, AL003, AL009, or Overload).

Fault Code and MeaningCause and Remedy
AL001

Over current

Cause:

  • The drive output is short-circuited.

  • The motor wiring is in error.

  • IGBT is abnormal (heat sink temperature abnormal).

  • The control parameter setting is in error.

  • Unreasonable command (acceleration time too fast).




Remedy:


  • Eliminate short-circuit and avoid metal conductor being exposed.

  • Rewire by following the wiring description from the user manual.

  • Send the drive back to the distributors or contact Delta.

  • Set back to the default setting and then gradually adjust the value.

  • Use less steep command or apply filter to smooth command.


AL002

Over voltage

Cause:

  • The input voltage of the main circuit is higher than the rated allowable voltage.

  • Wrong power input (incorrect power system).

  • The hardware of the servo drive is damaged.




Remedy:


  • Apply to the correct power supply or serial voltage regulator.

  • Apply to the correct power supply or serial adaptor.

  • Send the drive back to the distributors or contact Delta.


AL003

Under voltage

Cause:

  • The input voltage of the main circuit is lower than the rated allowable voltage.

  • No power supply for the main circuit.

  • Wrong power input (incorrect power system).




Remedy:


  • Re-confirm the voltage wiring.

  • Check the power switch.

  • Apply to the correct power supply or serial adaptor.


AL004

Motor combination error

Cause:

  • The encoder is damaged.

  • The encoder is loose.

  • Motor Combination Error (Connected to wrong motor).




Remedy:


  • Change the motor.

  • Install the motor again.

  • Change the motor / Connect to the right motor.


AL005

Regeneration error

Cause:

  • Chose wrong regenerative resistor or did not connect to external regenerative resistor.

  • Parameter P1-53 is not set to zero when the regenerative resistor is not in use.

  • Wrong parameter setting.




Remedy:


  • Calculate the value of the regenerative resistor again and correctly set P1-52 and P1-53.

  • Set parameter P1-53 of regenerative resistor to zero when it is not applying.

  • Correctly reset the value of P1-52 and P1-53.


AL006

Overload

Cause:

  • Over the rated loading of the drive and continuously excessive use.

  • The setting of the control system parameter is inappropriate.

  • Wrong wiring of the motor and the encoder.

  • The encoder of the motor is defective.




Remedy:


  • Increase the motor capacity or reduce the load.

  • Adjust the gain value of the control circuit; Slow down acceleration/deceleration setting.

  • Correct the wiring of U, V, W and the encoder.

  • Send the drive back to the distributors or contact Delta.


AL007

Overspeed

Cause:

  • Unreasonable command (Analog voltage abnormal).

  • Inappropriate parameter setting (P2-34 is too small).

  • Torque limit issue.




Remedy:


  • Use less steep command or apply filter to smooth command.

  • Correctly set parameter P2-34 (condition of over-speed warning).

  • Disable torque limit DI; Disable default setting; Set P1-12 ~ P1-14 to 100%.


AL008

Abnormal pulse command

Cause:

  • The pulse command frequency is higher than the rated input frequency.




Remedy:


  • Correctly set the input pulse frequency.


AL009

Excessive deviation of Position Command

Cause:

  • Parameter P2-35 is set too small.

  • The setting of the gain value is too small.

  • The torque limit is too low.

  • Excessive external load.




Remedy:


  • Increase the setting value of P2-35.

  • Correctly adjust the gain value.

  • Correctly adjust the torque limit value.

  • Reduce the external load or evaluate the motor capacity again.


AL011

Encoder error

Cause:

  • Wrong wiring of the encoder.

  • The encoder is loose.

  • Bad connection of the encoder (CN2 loose).

  • The encoder is damaged.




Remedy:


  • Correct wiring following the user manual.

  • Install the encoder again.

  • Reconnect the wiring.

  • Change the motor.


AL012

Adjustment error

Cause:

  • The analog input contact is incorrectly set back to zero.

  • The detection device is damaged.




Remedy:


  • Correctly ground the analog input contact.

  • Reset the power supply. If issue persists, send drive back to Delta.


AL013

Emergency stop

Cause:

  • Press the emergency stop button.




Remedy:


  • Activate (Release) emergency stop.


AL014

Reverse limit error

Cause:

  • Reverse limit switch is activated.

  • The servo system is unstable.




Remedy:


  • Enable the reverse limit switch.

  • Re-adjust the parameter or evaluate the motor capacity.


AL015

Forward limit error

Cause:

  • Forward limit switch is activated.

  • The servo system is unstable.




Remedy:


  • Enable the forward limit switch.

  • Re-adjust the parameter or evaluate the motor capacity.


AL016

IGBT Overheat

Cause:

  • Over the rated loading of the drive and continuously excessive using.

  • The drive output is short-circuit.




Remedy:


  • Increase the motor capacity or reduce the load.

  • Check the drive output wiring and correct it.


AL017

Abnormal EEPROM

Cause:

  • Error when DSP accesses EEPROM (Code EXGAB).

  • Abnormal hidden parameter (Code E100X).

  • Data in ROM is damaged (Code E0001).




Remedy:


  • If parameter is over reasonable range: Re-power on after adjusting.

  • If error writing parameter: Alarm can be cleared by DI.ARST.

  • Set the correct type of the drive.

  • Send the drive back to the distributors or contact Delta.


AL018

Abnormal signal output

Cause:

  • The encoder is in error (Check for AL011, AL024, AL025, AL026).

  • The output pulse exceeds the hardware allowable range.




Remedy:


  • Conduct the corrective actions for AL.011, AL.024, AL.025, AL.026.

  • Correctly set parameter P1-76 and P1-46 so P1-76 > Motor Speed.


AL019

Serial communication error

Cause:

  • Improper setting of the communication parameter.

  • Incorrect communication address.

  • Incorrect communication value.




Remedy:


  • Correctly set the parameter value.

  • Correctly set the communication address.

  • Correctly set the value.


AL020

Serial communication time out

Cause:

  • Improper setting of the time-out parameter.

  • The drive hasn’t received the communication command for a long time.




Remedy:


  • Correctly set the value.

  • Check if communication cable is loose/broken and correct wiring.


AL022

Main circuit power lack phase

Cause:

  • The main circuit power is abnormal (RST cable loose or not connected).




Remedy:


  • Make sure power applies. If issue persists, send drive back to Delta.


AL023

Early warning for overload

Cause: Early warning for overload.

Checking Method:

  • Check if it is used in overload condition.

  • Check if the value of parameter P1-56 is set too small.




Remedy:

  • Please refer to the corrective actions of AL006.

  • Please increase the setting value of parameter P1-56.

  • Or set the value over 100 and deactivate the overload warning function.


AL024

Encoder initial magnetic field error

Cause: The initial magnetic field of the encoder is in error (Signal U, V, W).

Checking Method:

  • Check if the servo motor is properly grounded.

  • Check if the encoder cable separates from the power supply or high-current circuit to avoid interference.

  • Check if shielding cables are used in the wiring of the encoder.




Remedy:

  • If issue persists, please send the drive back to the distributors or contact Delta.


AL025

The internal of the encoder is in error

Cause: Internal memory and internal counter are in error.

Checking Method:

  • Check if the servo is properly grounded.

  • Check if the encoder cable separates from the power supply or high-current circuit.

  • Check if shielding cables are used.




Remedy:

  • Please connect the UVW connector (color green) to the heat sink of the servo drive.

  • Ensure encoder cable separates from power supply/high-current circuits.

  • Please use shielding mesh.

  • If issue persists, send the drive back to the distributors or contact Delta.


AL026

Unreliable internal data of the encoder

Cause: Errors occur in the internal data for three times continuously.

Checking Method:

  • Check if the servo is properly grounded.

  • Check if the encoder cable separates from the power supply or high-current circuit.

  • Check if shielding cables are used.




Remedy:

  • Please connect the UVW connector (color green) to the heat sink of the servo drive.

  • Ensure encoder cable separates from power supply.

  • Please use shielding mesh.

  • If issue persists, send the drive back to the distributors or contact Delta.


AL027

The internal of the encoder is in error

Cause: The internal reset of the encoder is in error.

Checking Method:

  • Check if the servo is properly grounded.

  • Check if the encoder cable separates from the power supply or high-current circuit.

  • Check if shielding cables are used.




Remedy:

  • Please connect the UVW connector (color green) to the heat sink of the servo drive.

  • Ensure encoder cable separates from power supply.

  • Please use shielding mesh.

  • If issue persists, send the drive back to the distributors or contact Delta.


AL028

The internal of the encoder is in error

Cause: The encoder U, V, W signals are in error.

Checking Method:

  • Check if the servo is properly grounded.

  • Check if the encoder cable separates from the power supply or high-current circuit.

  • Check if shielding cables are used.




Remedy:

  • Please connect the UVW connector (color green) to the heat sink of the servo drive.

  • Ensure encoder cable separates from power supply.

  • Please use shielding mesh.

  • If issue persists, send the drive back to the distributors or contact Delta.


AL029

The internal of the encoder is in error

Cause: The internal address of the encoder is in error.

Checking Method:

  • Check if the servo is properly grounded.

  • Check if the encoder cable separates from the power supply or high-current circuit.

  • Check if shielding cables are used.




Remedy:

  • Please connect the UVW connector (color green) to the heat sink of the servo drive.

  • Ensure encoder cable separates from power supply.

  • Please use shielding mesh.

  • If issue persists, send the drive back to the distributors or contact Delta.


AL030

Motor crash error

Cause: Motor Crash Error.

Checking Method:

  • Check if P1-57 is enabled.

  • Check if P1-57 is set too small and the time of P1-58 is set too short.




Remedy:

  • If it is enabled by mistake, please set P1-57 to zero.

  • Adjust torque setting: if value is too small, alarm triggers by mistake. If too big, protection is lost.


AL031

Incorrect wiring of the motor power line U, V, W

Cause: The wiring of U, V, W of the motor is incorrect connected or the connection is breakdown.

Checking Method:

  • Check if U, V, W of the motor is incorrect connected.




Remedy:

  • Follow the user manual to correctly wire U, V, and W.

  • Make sure it is grounded.


AL035

Encoder temperature exceeds the protective range

Cause: Encoder temperature is over 120°C.

Checking Method:

  • Check if the environment temperature is excessive or the motor temperature is over 105°C.




Remedy:

  • Try to reduce operating temperature.


AL048

Excessive encoder output error

Cause: Encoder error causes abnormal output OR Output pulse exceeds hardware tolerance.

Checking Method:

  • Exam error recording (P4-00 ~ P4-05) to check if encoder error also occurs (AL011, AL024, AL025, AL026).

  • Check if P1-76 < Motor speed equation condition occurs.




Remedy:

  • Please refer to the corrective actions of AL011, AL024, AL025, and AL026.

  • Correctly set P1-76 and P1-46 according to the formula.


AL067

Encoder temperature warning

Cause: Encoder temperature is over 100°C.

Checking Method:

  • Check if the operating temperature is excessive or the motor temperature is over 85°C.




Remedy:

  • Try to reduce operating temperature.


AL083

Servo Drive Outputs Excessive Current

Cause: UVW cable short-circuited, Wrong motor wiring, or Analog signal interference.

Checking Method:

  • Check configuration of motor power cable. See if metal wire is exposed or AWG is worn.

  • Check if wiring sequence of UVW is correct.

  • Check for lack of phase when connecting UVW.

  • Check if GND of analog signal is misconnected to other signal.




Remedy:

  • Replace by new UVW cable and avoid exposed metal conductors.

  • Refer to Chapter 3 description and conduct wiring again.

  • GND of analog signal cannot be grounded with other signals.


AL085

Regeneration error

Cause: Wrong regenerative resistor chosen/connected, or Parameter P1-53 not set correctly.

Checking Method:

  • Check the connection of regenerative resistor.

  • Check if parameter P1-53 is set to zero when resistor is not in use.

  • Check the setting value of parameter P1-52 and P1-53.




Remedy:

  • Calculate value of regenerative resistor and correctly set P1-52 and P1-53.

  • Set P1-53 to zero when external resistor is not applying.

  • If issue persists, send drive back to distributors or contact Delta.


AL099

DSP firmware upgrade

Cause: Upgrade DSP firmware.

Checking Method:

  • Check if the firmware is upgraded.




Remedy:

  • Firstly set P2-08 to 30.

  • Then set P2-08 to 28, the alarm will be cleared when re-power on.


AL555

System failure

Cause: DSP processing error.



Remedy:

  • If AL555 occurs, do not do anything.

  • Send the drive back to the distributors or contact Delta.


AL880

System failure

Cause: DSP processing error.



Remedy:

  • If AL880 occurs, do not do anything.

  • Send the drive back to the distributors or contact Delta.


How to Clear & Reset Delta ASDA-B2 Servo Drive Faults

  1. Keypad Reset: Press and hold the SHIFT button on the built-in 5-digit LED operator keypad for more than 3 seconds after eliminating the alarm cause.
  2. Digital Input Signal (ARST): Trigger the external digital input configured as Alarm Reset (ARST, assigned via Parameter Group P2-10 through P2-17 set to value 0x0002 or 0x0102).
  3. Delta ASDA-Soft PC Tool: Connect your PC via the front Mini-USB or RS-232/RS-485 serial communication port, open Delta ASDA-Soft software, and click “Alarm Reset” on the diagnostic screen.
  4. Modbus Serial Communication: Transmit an alarm clear command or write the reset trigger command over the integrated RS-485/RS-232 Modbus network.
  5. Mains Power Cycle: Shut down the main AC power supply line, wait until the 5-digit LED display and the internal “CHARGE” indicator LED extinguish completely (allowing bus capacitors to discharge), then turn on mains power.
⚠️ High-Voltage Electrical Safety Warning: Dangerous residual DC voltage remains stored in the intermediate bus capacitors after disconnecting the main power supply. Always confirm with a calibrated digital multimeter that the DC bus potential drops strictly below 25VDC across terminals [P / +] and [D / -] before touching motor output terminals U, V, and W or performing service on the Delta ASDA-B2 servo drive.