Delta VFD-L Drive Fault Codes & Diagnostic Guide

Complete fault code directory, trip alarm root causes, and step-by-step troubleshooting procedures for the Delta VFD-L sub-fractional compact AC drive series. Search or filter through the complete diagnostic database below.

Sub-Fractional AC Drive Power: 0.2 to 1.5 kW (0.25 to 2.0 HP) Built-in EMI Filter & Potentiometer
Power Range 0.2 – 1.5 kW (0.25 – 2.0 HP)
Supply Voltage 115V / 230V AC (1-Ph / 3-Ph)
Control Modes Adjustable V/F Curve
Operator Interface Built-in Keypad & Speed Knob

Complete Delta VFD-L Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type oc, ov, oL, or Overcurrent).

Fault CodeCause & Solution
EF
External
fault
Cause: The external terminal EF-GND goes from OFF to ON.
‹
Soultion:

1. When external terminal EF-GND is closed, the output will be turned off. (Under N.O. E.F.)
2. Press RESET after fault has been cleared.
bb
External
Base
Block
Cause: This fault comes when drive received this command.

Soultion:

1. When the external input terminal (B.B) is active, the AC drive output will be turned off.
2. Disable this connection and the AC drive will begin to work again.
oc
Overcurrent
Cause: Output current of the AC drive exceeds the OC level
‹
Soultion:

- Extend the accel/decel time
- Check whether the motor rating and the AC drive rating match up with each other
- Check whether there is short-circuit among U-V-W of the AC drive
- Check whether the wiring to the motor is short-circuited or grounded
- Check whether the screw between the AC drive and the motor is tightened or not
- Check whether the motor is over loaded
ov/ou
overvoltage
Cause: DC voltage of the main circuit exceeds the over-voltage detection level
- The DC bus voltage has exceeded its maximum allowable value.
Soultion:

- Check whether the input voltage is within the scope of the rated input voltage of the AC drive, and monitor whether there is any occurrence of the voltage transients
- If it is of the motor inertia uprising voltage that caused the exceeding voltage on the DC high-voltage side within the AC drive, the solution is to extend the accel/decel time or install the braking resistor (optional)
oH
Overheating
Cause: Overheating- Heat sink temperature too high

Soultion:

1. Ensure that the ambient temperature falls within the specified temperature range.
2. Make sure that the ventilation holes are not obstructed.
3. Remove any foreign objects from the heatsinks and check for possible dirty heat sink fins.
4. Check the fan and clean it.
5. Provide enough spacing for adequate ventilation
Lu/Lv
Low
Voltage
Cause: DC high-voltage side is exceedingly low within the AC drive

Soultion:

- Check whether the input power voltage is normal
- Check whether the loading will be put on another unexpected heavy loading
- Whether the 3-phase model is of the single-phase power input or the phase-lacking
oL
overload
Cause: AC drive overload- Output current exceeds the AC drive-bearable current; e.g. could sustain for 60 seconds if the output is 150% of the AC drive rated current.
‹
Soultion:

- Decrease the loading and extend the acceleration time
- Check whether the motor is overloaded
- Reduce torque compensation setting as set in Pr.7-02.
- Increase the AC drive output capacity
oL1
Overload 1
Cause: Overload 1- Internal electronic overload trip

Soultion:

1. Check for possible motor overload.
2. Check electronic thermal overload setting.
3. Use a higher power motor.
4. Reduce the current level so that the drive output current does not exceed the value set by the Motor Rated Current Pr.7-00.
oL2
Motor
overload
Cause: OL2- motor overload Motor with exceedingly great loading
‹
Soultion:

- Check whether the loading of the motor is too great
- Adjust the over-torque detection setting to an appropriate setting (Pr.06-03 to Pr.06-05).
cE1
Communication
Error
Cause: Communication Error.

Soultion:

1. Check the connection between the AC drive and computer for loose wires.
2. Check if the communication protocol is properly set.
ocA
Over-current
during
acceleration
Cause: Over-current during acceleration (Output current exceeds triple rated current during acceleration.).

Soultion:

1. Short-circuit at motor output: Check for possible poor insulation at the output lines.
2. Acceleration Time too short: Increase the Acceleration Time.
3. AC motor drive output power is too small: Replace the AC motor drive with the next higher power model.
ocd
Over-current
during
deceleration
Cause: Over-current during deceleration (Output current exceeds triple rated current during deceleration.)

Soultion:

1. Short-circuit at motor output: Check for possible poor insulation at the output line.
2. Deceleration Time too short: Increase the Deceleration Time.
3. AC motor drive output power is too small: Replace the AC motor drive with the next higher power model.
ocn
Over-current
during steady
state
operation
Cause: Over-current during steady state operation (Output current exceeds triple rated current during constant speed.)

Soultion:

1. Short-circuit at motor output: Check for possible poor insulation at the output line.
2. Sudden increase in motor loading: Check for possible motor stall.
3. AC motor drive output power is too small: Replace the AC motor drive with the next higher power model.
cF1
Internal
EEPROM
can not be
programmed
Cause: Internal EEPROM can not be programmed.

Soultion:

1. Press “RESET” key to the factory setting
2. After this same fault comes then there is an hardware issue in drive need to repair or replace drive.
cF2
Internal
EEPROM
can not be
read
Cause: Internal EEPROM can not be read.

Soultion:

1. Press “RESET” key to the factory setting
2. After this same fault comes then there is an hardware issue in drive need to repair or replace drive.
EF
External
fault
Cause: The external terminal EF-GND goes from OFF to ON.
‹
Soultion:

1. When external terminal EF-GND is closed, the output will be turned off. (Under N.O. E.F.)
2. Press RESET after fault has been cleared.
cF3
Drive’s
internal
circuitry
abnormal
Cause: Drive’s internal circuitry abnormal.

Soultion: There is an hardware or software issue in drive. Need to repair or replace drive.
HPFCause: Hardware protection failure.

Soultion: There is an hardware or software issue in drive. Need to repair or replace drive.
CodE
Software
protection
failure
Cause: Software protection failure.

Soultion: There is an hardware or software issue in drive. Need to repair or replace drive.
cFA
Auto
accel/decel
failure
Cause: Auto accel/decel failure.

Soultion:

1. Check if the motor is suitable for operation by AC motor drive.
2. Check if the regenerative energy is too large.
3. Load may have changed suddenly.
bb
External
Base
Block
Cause: This fault comes when drive received this command.

Soultion:

1. When the external input terminal (B.B) is active, the AC drive output will be turned off.
2. Disable this connection and the AC drive will begin to work again.

How to Clear & Reset Delta VFD-L Drive Faults

  1. Keypad Reset: Press the red STOP/RESET key on the integrated front keypad once the fault cause has been identified and corrected.
  2. Digital Input Reset (External Reset): Assign any multi-function input terminal (M1, M2, or M3) to function 06 (External Reset) in parameters Pr. 4-04 to Pr. 4-06, then close the contact to GND.
  3. Modbus Serial Communication: If equipped with RS-485 serial communication, send a reset command over Modbus RTU/ASCII by writing Bit 1 to control command word 2000H.
  4. Parameter Factory Reset: Set parameter 0-02 to 9 (50Hz factory settings) or 10 (60Hz factory settings) to restore all drive parameters to default factory values.
  5. Power Cycle: Disconnect AC input mains power, wait at least 5 minutes until the digital keypad LED display and the internal charging indicator extinguish completely, then re-apply power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 25VDC across terminals [+1/+] and [-], and verify that the internal Charge LED is completely extinguished before inspecting motor leads, opening terminal covers, or touching terminals U/T1, V/T2, and W/T3 on the Delta VFD-L drive.