Emotron FDU Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Emotron FDU dedicated pump and fan drive series. Search or filter through the complete diagnostic directory below.

Flow & Pressure Dedicated AC Drive Power: 0.55 to 3,000 kW (0.75 to 4,000 HP) Integrated Shaft Power Monitor
Power Range 0.55 – 3,000 kW (0.75 – 4,000 HP)
Supply Voltage 230 – 690V AC (3-Phase)
Control Modes V/Hz, Direct Torque Control (DTC)
Operator Interface Detachable Multi-Language Control Panel

Complete Emotron FDU Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type Overcurrent, Overvoltage, Desat, or Motor Temp).

Trip ConditionCause and Remedy
Motor I2t

“I2t”

Cause:


I2t value is exceeded.

  • Overload on the motor according to the programmed I2t settings.





Remedy:



  • Check on mechanical overload on the motor or the machinery (bearings, gearboxes, chains, belts, etc.)

  • Change the Motor I2t Current setting in menu group [230]


PTC

Motor thermistor (PTC)

Cause:


Motor thermistor (PTC) exceeds maximum level.



Note: Only valid if option board PTC/PT100 is used.



Remedy:



  • Check on mechanical overload on the motor or the machinery (bearings, gearboxes, chains, belts, etc.)

  • Check the motor cooling system.

  • Self-cooled motor at low speed, too high load.

  • Set PTC, menu [234] to OFF


Motor PTC

Motor thermistor (PTC)

Cause:


Motor thermistor (PTC) exceeds maximum level.



Note: Only valid if [337] is enabled.



Remedy:



  • Check on mechanical overload on the motor or the machinery (bearings, gearboxes, chains, belts, etc.)

  • Check the motor cooling system.

  • Self-cooled motor at low speed, too high load.

  • Set PTC, menu [237] to OFF




Applicable Sizes: 002 - 105
PT100

Motor PT100 elements

Cause:


Motor PT100 elements exceeds maximum level.



Note: Only valid if option board PTC/PT100 is used.



Remedy:



  • Check on mechanical overload on the motor or the machinery (bearings, gearboxes, chains, belts, etc.)

  • Check the motor cooling system.

  • Self-cooled motor at low speed, too high load.

  • Set PT100 to OFF, menu [234]


Motor lost

Phase loss or imbalance

Cause:


Phase loss or too great imbalance on the motor phases.



Remedy:



  • Check the motor voltage on all phases.

  • Check for loose or poor motor cable connections.

  • If all connections are OK, contact your supplier.

  • Set motor lost alarm to OFF.


Locked rotor

Rotor blocking

Cause:


Torque limit at motor standstill:

  • Mechanical blocking of the rotor.





Remedy:



  • Check for mechanical problems at the motor or the machinery connected to the motor.

  • Set locked rotor alarm to OFF.


Ext trip 1

External input (DigIn 1-8)

Cause:


External input (DigIn 1-8) active:

  • active low function on the input.


Note: Exact trip message is dependent on [431] ExtTrip1 Text.



Remedy:



  • Check the equipment that initiates the external input.

  • Check the programming of the digital inputs DigIn 1-8.


Ext trip 2

External input (DigIn 1-8)

Cause:


External input (DigIn 1-8) active:

  • active low function on the input.


Note: Exact trip message is dependent on [432] ExtTrip2 Text.



Remedy:



  • Check the equipment that initiates the external input.

  • Check the programming of the digital inputs DigIn 1-8.


Ext trip 3

External input (DigIn 1-8)

Cause:


External input (DigIn 1-8) active:

  • active low function on the input.


Note: Exact trip message is dependent on [433] ExtTrip3 Text.



Remedy:



  • Check the equipment that initiates the external input.

  • Check the programming of the digital inputs DigIn 1-8.


Ext trip 4

External input (DigIn 1-8)

Cause:


External input (DigIn 1-8) active:

  • active low function on the input.


Note: Exact trip message is dependent on [434] ExtTrip4 Text.



Remedy:



  • Check the equipment that initiates the external input.

  • Check the programming of the digital inputs DigIn 1-8.


Ext Mot Temp

External input (DigIn 1-8)

Cause:


External input (DigIn 1-8) active:

  • active low function on the input.





Remedy:



  • Check the equipment that initiates the external input.

  • Check the programming of the digital inputs DigIn 1-8.


Internal error

Internal alarm

Cause:


Internal alarm.



Remedy:


Contact service.
Mon MaxAlarm

Max alarm level (overload)

Cause:


Max alarm level (overload) has been reached.



Remedy:



  • Check the load condition of the machine.

  • Check the monitor setting in section 11.4.1, page 149.


Mon MinAlarm

Min alarm level (underload)

Cause:


Min alarm level (underload) has been reached.



Remedy:



  • Check the load condition of the machine.

  • Check the monitor setting in section 11.4.1, page 149.


Comm error

Serial communication error

Cause:


Error on serial communication (option).



Remedy:



  • Check cables and connection of the serial communication.

  • Check all settings with regard to the serial communication.

  • Restart the equipment including the AC drive.


Encoder

Encoder loss/speed deviation

Cause:


Lost encoder board, encoder cable or encoder pulses. Motor speed deviation in between reference and measured speed detected.



Note: Only valid if option board Encoder is used.



Remedy:



  • Check encoder board.

  • Check encoder cable and signals.

  • Check motor operation.

  • Check speed deviation settings [22G#].

  • Check speed PI controller settings [37#].

  • Check torque limit setting [351].

  • Disable encoder, set menu [22B] to OFF.


Pump

Master pump selection error

Cause:


No master pump can be selected due to error in feedback signalling.



Note: Only used in Pump Control.



Remedy:



  • Check cables and wiring for Pump feedback signals.

  • Check settings with regard to the pump feedback digital inputs.


Over temp

Heatsink overtemperature

Cause:


Heatsink temperature too high:

  • Too high ambient temperature of the AC drive.

  • Insufficient cooling.

  • Too high current.

  • Blocked or stuffed fans.





Remedy:



  • Check the cooling of the AC drive cabinet.

  • Check the functionality of the built-in fans. The fans must switch on automatically if the heatsink temperature gets too high. At power up the fans are briefly switched on.

  • Check AC drive and motor rating.

  • Clean fans.

  • Check / reduce switching frequency settings in [22A] / [22E1].


Over curr F

Motor peak current exceeded

Cause:


Motor current exceeds the peak AC drive current:

  • Too short acceleration time.

  • Too high motor load.

  • Excessive load change.

  • Soft short-circuit between phases or phase to earth.

  • Poor or loose motor cable connections.

  • Too high IxR Compensation level.





Remedy:



  • Check the acceleration time settings and make them longer if necessary.

  • Check the motor load.

  • Check on bad motor cable connections.

  • Check on bad earth cable connection.

  • Check on water or moisture in the motor housing and cable connections.

  • Lower the level of IxR Compensation [352].


Over volt D(eceleration)
Over volt G(eneration)

High DC Link voltage

Cause:


Too high DC Link voltage:

  • Too short deceleration time with respect to motor/machine inertia.

  • Too small brake resistor malfunctioning.

  • Brake chopper.





Remedy:



  • Check the deceleration time settings and make them longer if necessary.

  • Check the dimensions of the brake resistor and the functionality of the Brake chopper (if used).


Over volt (Mains)
O(ver) volt M(ains) cut

High supply voltage

Cause:


Too high DC Link voltage, due to too high mains voltage.



Remedy:



  • Check the main supply voltage.

  • Try to take away the interference cause or use other main supply lines.


Under voltage

Low DC Link voltage

Cause:


Too low DC Link voltage:

  • Too low or no supply voltage.

  • Mains voltage dip due to starting other major power consuming machines on the same line.





Remedy:



  • Make sure all three phases are properly connected and that the terminal screws are tightened.

  • Check that the mains supply voltage is within the limits of the AC drive.

  • Try to use other mains supply lines if dip is caused by other machinery.

  • Use the function low voltage override [421].


LC Level

Liquid cooling level low

Cause:


Low liquid cooling level in external reservoir. External input (DigIn 1-8) active:

  • active low function on the input.


Note: Only valid for AC drive types with Liquid Cooling option.



Remedy:



  • Check liquid cooling.

  • Check the equipment and wiring that initiates the external input.

  • Check the programming of the digital inputs DigIn 1-8.


OPTION

Option specific trip

Cause:


If an Option specific trip occurs.



Remedy:


Check the description of the specific option.
Desat / Desat U± / Desat V± / Desat W± / Desat BCC

Output stage failure

Cause:


Failure in output stage:

  • desaturation of IGBTs.

  • Hard short circuit between phases or phase to earth.

  • Earth fault.

  • For size B - D also the Brake IGBT.





Remedy:



  • Check on bad motor cable connections.

  • Check on bad earth cable connection.

  • Check on water and moisture in the motor housing and cable connections.

  • Check that the rating plate data of the motor is correctly entered.

  • Check the brake resistor, brake IGBT and wiring.

  • For size H and up, check the cables from the PEBBs to the motor, that all are in correct order in parallel connection.




Applicable Sizes: 002 - 105 (Standard Desat), 090 & Up (Desat Phase / BCC trips)
DC link error

Voltage ripple high

Cause:


DC link voltage ripple exceeds maximum level.



Remedy:



  • Make sure all three phases are properly connected and that the terminal screws are tightened.

  • Check that the mains supply voltage is within the limits of the AC drive.

  • Try to use other mains supply lines if dip is caused by other machinery.


Power Fault

Undetermined Power Fault

Cause:


One of the PF (Power Fault) trips below has occurred, but could not be determined.



Remedy:


Check the PF errors and try to determine the cause. The trip history can be helpful.
PF Fan Err *

Fan module error

Cause:


Error in fan module.



Remedy:


Check for clogged air inlet filters in panel door and blocking material in fan module.



Applicable Sizes: 090 & Up
PF HCB Err *

Controlled rectifier error

Cause:


Error in controlled rectifier module (HCB).



Remedy:


Check mains supply voltage.



Applicable Sizes: 060 & Up
PF Curr Err

Current balance error

Cause:


Error in current balancing:

  • between different modules.

  • between two phases within one module.





Remedy:



  • Check motor.

  • Check fuses and line connections.

  • Check the individual motor current leads with an clamp on amp meter.




Applicable Sizes: 430 & Up
PF Overvolt

Power module overvoltage

Cause:


Error in voltage balancing, overvoltage detected in one of the power modules (PEBB).



Remedy:



  • Check motor.

  • Check fuses and line connections.




Applicable Sizes: 430 & Up
PF Comm Err *

Internal communication error

Cause:


Internal communication error.



Remedy:


Contact service.
PF Int Temp *

Internal temperature high

Cause:


Internal temperature too high.



Remedy:


Check internal fans.
PF Temp Err *

Temperature sensor malfunction

Cause:


Malfunction in temperature sensor.



Remedy:


Contact service.
PF DC Err *

DC-link / Mains supply fault

Cause:


DC-link error and mains supply fault.



Remedy:



  • Check mains supply voltage.

  • Check fuses and line connections.




Applicable Sizes: 060 & Up
PF Sup Err *

Mains supply fault

Cause:


Mains supply fault.



Remedy:



  • Check mains supply voltage.

  • Check fuses and line connections.


PF PBuC *

Powerboard microcontroller reset

Cause:


Powerboard micro controller reset by watchdog.



Remedy:


Not specified.
Brake

Brake fault / engagement fail

Cause:


Brake tripped on brake fault (not released) or Brake not engaged during stop.



Remedy:



  • Check Brake acknowledge signal wiring to selected digital input.

  • Check programming of digital input DigIn 1-8, [520].

  • Check circuit breaker feeding mechanical brake circuit.

  • Check mechanical brake if acknowledge signal is wired from brake limit switch.

  • Check brake contactor.

  • Check settings [33C], [33D], [33E], [33F].


AnIn
Analogue input signal low

Cause:


An analogue input signal is below 75% of the configured minimum value.



Remedy:



  • Check cables and connections of the analogue inputs.

  • Check the configured minimum values for the analogue inputs.

  • Disable AI Flt Mode in menu [51D].


How to Clear & Reset Emotron FDU Drive Faults

  1. Keypad Reset: Press the red RESET button on the front control panel display. If operating via remote control, ensure the drive is permitted to reset from the keypad via menu [21A] Keypad Reset.
  2. Digital Input Reset (DigIn): Trigger an external contact if configured in menu [520] Digital Inputs (e.g., assign parameter [261] Reset to an active digital input terminal such as DigIn 1 to DigIn 8).
  3. Serial Communication / Fieldbus: Send a reset pulse by setting Bit 3 (Fault Acknowledge/Reset) in the Fieldbus Control Word over Modbus RTU, Profibus, Profinet, or Ethernet/IP networks.
  4. Autoreset Function: If enabled in menu [250] Autoreset, the drive will automatically attempt a programmed number of reset cycles for specific faults (such as Overvoltage or Motor Thermal Overload) before latching a hard trip.
  5. Full Power Cycle: Switch off main 3-phase incoming AC power, wait at least 5 to 7 minutes until the control panel display goes completely dark and intermediate DC link capacitors discharge, then reapply power.
⚠️ High-Voltage Electrical Safety Warning: Always wait a minimum of 5 to 7 minutes after disconnecting mains power. Verify with a calibrated digital DC voltmeter that the intermediate DC link bus voltage measures strictly below 50VDC across terminals [DC+] and [DC-] before opening terminal covers, checking output motor wiring, or servicing terminals U, V, and W on the Emotron FDU drive.