Emotron VFX drive

Home / Emotron / Emotron VFX drive

Emotron VFX Drive Fault Codes & Diagnostic Guide

Complete trip alarm directory, root cause analysis, and step-by-step diagnostic procedures for the Emotron VFX high-performance AC drive series. Search or filter through the master fault code table below to resolve drive trips quickly.

Direct Torque Control (DTC) Power: 0.55 to 3,000 kW (0.75 to 4,000 HP) High Dynamic Cranes & Industrial Drives
Power Range 0.55 – 3,000 kW (0.75 – 4,000 HP)
Supply Voltage 230V / 380–480V / 500–690V AC
Control Modes Direct Torque Control (DTC) & V/Hz
Operator Interface Detachable Multi-Language LCD Panel

Complete Emotron VFX Drive Fault Code Directory

Use the search box in the table below to quickly find your fault message (e.g., type Overcurrent, Overvoltage, or Motor I2t).

Trip ConditionCause and Remedy
Motor I2t

“I2t”

Cause:


I2t value is exceeded.

  • Overload on the motor according to the programmed I2t settings.





Remedy:



  • Check on mechanical overload on the motor or the machinery (bearings, gearboxes, chains, belts, etc.)

  • Change the Motor I2t Current setting in menu group [230]


PTC

Motor thermistor (PTC)

Cause:


Motor thermistor (PTC) exceeds maximum level.



Note: Only valid if option board PTC/PT100 is used.



Remedy:



  • Check on mechanical overload on the motor or the machinery (bearings, gearboxes, chains, belts, etc.)

  • Check the motor cooling system.

  • Self-cooled motor at low speed, too high load.

  • Set PTC, menu [234] to OFF.


Motor PTC

Motor thermistor (PTC)

Cause:


Motor thermistor (PTC) exceeds maximum level.



Note: Only valid if [337] is enabled.



Remedy:



  • Check on mechanical overload on the motor or the machinery (bearings, gearboxes, chains, belts, etc.)

  • Check the motor cooling system.

  • Self-cooled motor at low speed, too high load.

  • Set PTC, menu [237] to OFF.




Applicable Sizes: 002 - 105
PT100

Motor PT100 elements

Cause:


Motor PT100 elements exceeds maximum level.



Note: Only valid if option board PTC/PT100 is used.



Remedy:



  • Check on mechanical overload on the motor or the machinery (bearings, gearboxes, chains, belts, etc.)

  • Check the motor cooling system.

  • Self-cooled motor at low speed, too high load.

  • Set PT100 to OFF, menu [234].


Motor lost

Phase loss or imbalance

Cause:


Phase loss or too great imbalance on the motor phases.



Remedy:



  • Check the motor voltage on all phases.

  • Check for loose or poor motor cable connections.

  • If all connections are OK, contact your supplier.

  • Set motor lost alarm to OFF.


Locked rotor

Rotor blocking

Cause:


Torque limit at motor standstill:

  • Mechanical blocking of the rotor.





Remedy:



  • Check for mechanical problems at the motor or the machinery connected to the motor.

  • Set locked rotor alarm to OFF.


Ext trip 1

External input (DigIn 1-8)

Cause:


External input (DigIn 1-8) active:

  • active low function on the input.


Note: Exact trip message is dependent on [431] ExtTrip1 Text.



Remedy:



  • Check the equipment that initiates the external input.

  • Check the programming of the digital inputs DigIn 1-8.


Ext trip 2

External input (DigIn 1-8)

Cause:


External input (DigIn 1-8) active:

  • active low function on the input.


Note: Exact trip message is dependent on [432] ExtTrip2 Text.



Remedy:



  • Check the equipment that initiates the external input.

  • Check the programming of the digital inputs DigIn 1-8.


Ext trip 3

External input (DigIn 1-8)

Cause:


External input (DigIn 1-8) active:

  • active low function on the input.


Note: Exact trip message is dependent on [433] ExtTrip3 Text.



Remedy:



  • Check the equipment that initiates the external input.

  • Check the programming of the digital inputs DigIn 1-8.


Ext trip 4

External input (DigIn 1-8)

Cause:


External input (DigIn 1-8) active:

  • active low function on the input.


Note: Exact trip message is dependent on [434] ExtTrip4 Text.



Remedy:



  • Check the equipment that initiates the external input.

  • Check the programming of the digital inputs DigIn 1-8.


Ext Mot Temp

External input (DigIn 1-8)

Cause:


External input (DigIn 1-8) active:

  • active low function on the input.





Remedy:



  • Check the equipment that initiates the external input.

  • Check the programming of the digital inputs DigIn 1-8.


Internal error

Internal alarm

Cause:


Internal alarm.



Remedy:


Contact service.
Mon MaxAlarm

Max alarm level (overload)

Cause:


Max alarm level (overload) has been reached.



Remedy:



  • Check the load condition of the machine.

  • Check the monitor setting in section 11.4.1, page 145.


Mon MinAlarm

Min alarm level (underload)

Cause:


Min alarm level (underload) has been reached.



Remedy:



  • Check the load condition of the machine.

  • Check the monitor setting in section 11.4.1, page 145.


Comm error

Serial communication error

Cause:


Error on serial communication (option).



Remedy:



  • Check cables and connection of the serial communication.

  • Check all settings with regard to the serial communication.

  • Restart the equipment including the AC drive.


Crane Deviat

Motor operation deviation

Cause:


CRANE board detecting deviation in motor operation.



Note: Only used in Crane Control.



Remedy:



  • Check encoder signals.

  • Check Deviation jumper on Crane option board.

  • Check the settings in menus [3AB] & [3AC].


CraneComm

Crane communication lost

Cause:


Lost communication with CRANE board.



Note: Only used in Crane Control.



Remedy:



  • Check CRIO board.

  • Check CRIO cable and signals.


Encoder

Encoder loss/speed deviation

Cause:


Lost encoder board, encoder cable or encoder pulses. Motor speed deviation in between reference and measured speed detected.



Note: Only valid if option board Encoder is used.



Remedy:



  • Check encoder board.

  • Check encoder cable and signals.

  • Check motor operation.

  • Check speed deviation settings [22G#].

  • Check speed PI controller settings [37#].

  • Check torque limit setting [351].

  • Disable encoder, set menu [22B] to OFF.


Pump

Master pump selection error

Cause:


No master pump can be selected due to error in feedback signalling.



Note: Only used in Pump Control.



Remedy:



  • Check cables and wiring for Pump feedback signals.

  • Check settings with regard to the pump feedback digital inputs.


Over temp

Heatsink overtemperature

Cause:


Heatsink temperature too high:

  • Too high ambient temperature of the AC drive.

  • Insufficient cooling.

  • Too high current.

  • Blocked or stuffed fans.





Remedy:



  • Check the cooling of the AC drive cabinet.

  • Check the functionality of the built-in fans. The fans must switch on automatically if the heatsink temperature gets too high. At power up the fans are briefly switched on.

  • Check AC drive and motor rating.

  • Clean fans.

  • Check / reduce switching frequency settings in [22A] / [22E1].


Over curr F

Motor peak current exceeded

Cause:


Motor current exceeds the peak AC drive current:

  • Too short acceleration time.

  • Too high motor load.

  • Excessive load change.

  • Soft short-circuit between phases or phase to earth.

  • Poor or loose motor cable connections.

  • Too high IxR Compensation level.





Remedy:



  • Check the acceleration time settings and make them longer if necessary.

  • Check the motor load.

  • Check on bad motor cable connections.

  • Check on bad earth cable connection.

  • Check on water or moisture in the motor housing and cable connections.

  • Lower the level of IxR Compensation [352].


Over volt D(eceleration)
Over volt G(eneration)

High DC Link voltage

Cause:


Too high DC Link voltage:

  • Too short deceleration time with respect to motor/machine inertia.

  • Too small brake resistor malfunctioning.

  • Brake chopper.





Remedy:



  • Check the deceleration time settings and make them longer if necessary.

  • Check the dimensions of the brake resistor and the functionality of the Brake chopper (if used).


Over volt (Mains)
O(ver) volt M(ains) cut

High supply voltage

Cause:


Too high DC Link voltage, due to too high mains voltage.



Remedy:



  • Check the main supply voltage.

  • Try to take away the interference cause or use other main supply lines.


Over speed

Maximum speed exceeded

Cause:


Motor speed measurement exceeds maximum level. 110% of max speed (all parameter sets).



Remedy:



  • Check encoder cables, wiring and setup.

  • Check motor data setup [22x].

  • Perform short ID-run.


Under voltage

Low DC Link voltage

Cause:


Too low DC Link voltage:

  • Too low or no supply voltage.

  • Mains voltage dip due to starting other major power consuming machines on the same line.





Remedy:



  • Make sure all three phases are properly connected and that the terminal screws are tightened.

  • Check that the mains supply voltage is within the limits of the AC drive.

  • Try to use other mains supply lines if dip is caused by other machinery.

  • Use the function low voltage override [421].


LC Level

Liquid cooling level low

Cause:


Low liquid cooling level in external reservoir. External input (DigIn 1-8) active:

  • active low function on the input.


Note: Only valid for AC drive types with Liquid Cooling option.



Remedy:



  • Check liquid cooling.

  • Check the equipment and wiring that initiates the external input.

  • Check the programming of the digital inputs DigIn 1-8.


OPTION

Option specific trip

Cause:


If an Option specific trip occurs.



Remedy:


Check the description of the specific option.
Desat / Desat U± / Desat V± / Desat W± / Desat BCC

Output stage failure

Cause:


Failure in output stage:

  • desaturation of IGBTs.

  • Hard short circuit between phases or phase to earth.

  • Earth fault.

  • For size B - D also the Brake IGBT.





Remedy:



  • Check on bad motor cable connections.

  • Check on bad earth cable connection.

  • Check on water and moisture in the motor housing and cable connections.

  • Check that the rating plate data of the motor is correctly entered.

  • Check the brake resistor, brake IGBT and wiring.

  • For size H and up, check the cables from the PEBBs to the motor, that all are in correct order in parallel connection.




Applicable Sizes: 002 - 105 (Standard Desat), 090 & Up (Desat Phase / BCC trips)
DC link error

Voltage ripple high

Cause:


DC link voltage ripple exceeds maximum level.



Remedy:



  • Make sure all three phases are properly connected and that the terminal screws are tightened.

  • Check that the mains supply voltage is within the limits of the AC drive.

  • Try to use other mains supply lines if dip is caused by other machinery.


Power Fault

Undetermined Power Fault

Cause:


One of the PF (Power Fault) trips below has occurred, but could not be determined.



Remedy:


Check the PF errors and try to determine the cause. The trip history can be helpful.
PF Fan Err *

Fan module error

Cause:


Error in fan module.



Remedy:


Check for clogged air inlet filters in panel door and blocking material in fan module.



Applicable Sizes: 090 & Up
PF HCB Err *

Controlled rectifier error

Cause:


Error in controlled rectifier module (HCB).



Remedy:


Check mains supply voltage.



Applicable Sizes: 060 & Up
PF Curr Err

Current balance error

Cause:


Error in current balancing:

  • between different modules.

  • between two phases within one module.





Remedy:



  • Check motor.

  • Check fuses and line connections.

  • Check the individual motor current leads with a clamp on amp meter.




Applicable Sizes: 430 & Up
PF Overvolt

Power module overvoltage

Cause:


Error in voltage balancing, overvoltage detected in one of the power modules (PEBB).



Remedy:



  • Check motor.

  • Check fuses and line connections.




Applicable Sizes: 430 & Up
PF Comm Err *

Internal communication error

Cause:


Internal communication error.



Remedy:


Contact service.
PF Int Temp *

Internal temperature high

Cause:


Internal temperature too high.



Remedy:


Check internal fans.
PF Temp Err *

Temperature sensor malfunction

Cause:


Malfunction in temperature sensor.



Remedy:


Contact service.
PF DC Err *

DC-link / Mains supply fault

Cause:


DC-link error and mains supply fault.



Remedy:



  • Check mains supply voltage.

  • Check fuses and line connections.




Applicable Sizes: 060 & Up
PF Sup Err *

Mains supply fault

Cause:


Mains supply fault.



Remedy:



  • Check mains supply voltage.

  • Check fuses and line connections.


PF PBuC *

Powerboard microcontroller reset

Cause:


Powerboard micro controller reset by watchdog.



Remedy:


Not specified.
Brake

Brake fault / engagement fail

Cause:


Brake tripped on brake fault (not released) or Brake not engaged during stop.



Remedy:



  • Check Brake acknowledge signal wiring to selected digital input.

  • Check programming of digital input DigIn 1-8, [520].

  • Check circuit breaker feeding mechanical brake circuit.

  • Check mechanical brake if acknowledge signal is wired from brake limit switch.

  • Check brake contactor.

  • Check settings [33C], [33D], [33E], [33F].


AnIn
Analogue input signal low

Cause:


An analogue input signal is below 75% of the configured minimum value.



Remedy:



  • Check cables and connections of the analogue inputs.

  • Check the configured minimum values for the analogue inputs.

  • Disable AI Flt Mode in menu [51D].


How to Clear & Reset Emotron VFX Drive Faults

  1. Keypad Reset: Press the red RESET key on the front detachable control panel. Verify menu [216] (Reset Control) is configured to accept keypad resets (Keyboard or Keyb+Rem).
  2. Digital Input (DI) Terminal Reset: Configure an assigned digital input (DigIn 1 to DigIn 8 in menus [521]–[528]) to "Reset". Pulse the terminal with +24 VDC to acknowledge and clear the trip condition.
  3. EmoSoftCom Software Tool: Connect your PC to the drive via RS232/RS485 or fieldbus communication interface, launch EmoSoftCom, and trigger a fault reset command directly from the diagnostic status window.
  4. Fieldbus Control Word: If controlling over Modbus RTU, Profibus, EtherCAT, or Profinet, set menu [216] to Com or Com+Keyb and toggle the Reset bit in the fieldbus Control Word from 0 to 1.
  5. Mains Power Cycle: Switch off the primary AC mains supply. Wait at least 7 minutes until the control panel display turns off and intermediate DC bus capacitors fully discharge, then reapply power.
⚠️ High-Voltage Electrical Safety Warning: Always wait at least 7 minutes after removing mains supply voltage and verify with a calibrated digital multimeter that the DC bus voltage across terminals [+DC] and [-DC] measures safely below 50V DC before inspecting terminals, opening enclosures, or handling motor output leads U, V, and W on the Emotron VFX drive.