Emotron VS10 drive

Home / Emotron / Emotron VS10 drive

Emotron VS10 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the CG Emotron VS10 micro AC drive series. Search or filter through the complete fault code directory below.

Compact Micro Drive Power: 0.25 to 2.2 kW (0.33 to 3.0 HP) Integrated EMC Filter
Power Range 0.25 – 2.2 kW (0.33 – 3.0 HP)
Supply Voltage 230V AC (1-Phase, 190–264V)
Control Modes V/f Control & Sensorless Vector (SLVC)
Operator Interface LED Keypad / “EASY Starter” PC Tool

Complete Emotron VS10 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type 2310, 3210, or Overcurrent).

Fault Code and MeaningCause and Remedy
8784 | 0x2250

PU over current
CiA: Continuous over current (internal)

Cause:


This message contains three errors:

  • Continuous overcurrent on the inverter/motor side.

  • Overcurrent at the brake chopper (brake transistor).

  • DC bus relay has not been closed due to a malfunction.





Remedy:


Response: Fault (The error can only be reset after a blocking time of 5 s. Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)

No adjustment parameters defined.
8992 | 0x2320

Earth leak
CiA: Short circuit/earth leakage (internal)

Cause:


Short circuit/earth leakage detected on the internal/motor side.



Remedy:


Response: Fault (The error can only be reset after a blocking time of 5 s. Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)

No adjustment parameters defined.
9024 | 0x2340

Motor shorted
CiA: Short circuit (device internal)

Cause:


Device internal short circuit or short circuit of motor cable.



Remedy:


Response: Fault (The error can only be reset after a blocking time of 5 s. Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)

No adjustment parameters defined.
9040 | 0x2350

Motor i2t OL
CiA: i²*t overload (thermal state)

Cause:


Thermal overload of the motor.



Remedy:


Response: Fault (The error can only be reset after a blocking time of 5 s.)

No adjustment parameters defined.
9090 | 0x2382

Ixt error
I*t error

Cause:


The device utilisation has exceeded the warning threshold set in 0x2D40:002 (default setting: 95 %).



Remedy:


Response: Fault (The error can only be reset after a blocking time of 3 s. Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)

Adjustable in: 0x2D40:005 (P135.05)
9091 | 0x2383

Ixt warning
I*t warning

Cause:


The device utilisation has exceeded the permanent error threshold of 100 %.



Remedy:


Response: Warning (Logging only inside Error history buffer/Logbook)

No adjustment parameters defined.
9095 | 0x2387

Clamp timeout
Imax: Clamp responded too often

Cause:


"Clamp" = short-time inhibit of the inverter in V/f operation when the current limit shown in 0x2DDF:002 is reached.



Remedy:


Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)

No adjustment parameters defined.
9096 | 0x2388

SLPSM stall det.
SLPSM stall detection active

Cause:


Stalling protection for the sensorless control for synchronous motors (SLPSM) is active.

  • Possible cause: Overload of the motor.





Remedy:


Response: Trouble (Serious fault: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)

No adjustment parameters defined.
12576 | 0x3120

Mains Phase fail
Mains phase fault

Cause:


Mains phase fault.



Remedy:


Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)

No adjustment parameters defined.
12816 | 0x3210

DC Bus OV
DC bus overvoltage

Cause:


The DC-bus voltage of the inverter has exceeded the error threshold for overvoltage. The error threshold results from the setting of the rated mains voltage in 0x2540:001 (P208.01).



Remedy:


Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)

No adjustment parameters defined.
12817 | 0x3211

Warn.DC Bus OV
DC bus overvoltage warning

Cause:


The DC-bus voltage of the inverter has exceeded the warning threshold for overvoltage set in 0x2540:005 (P208.05).



Remedy:


Response: Warning (Logging only inside Error history buffer/Logbook)

No adjustment parameters defined.
12832 | 0x3220

DC Bus UV
DC bus undervoltage

Cause:


The DC-bus voltage of the inverter has fallen below the error threshold for undervoltage. The error threshold results from the setting of the rated mains voltage in 0x2540:001 (P208.01).



Remedy:


Response: Trouble

No adjustment parameters defined.
12833 | 0x3221

Warn.DC Bus UV
DC bus undervoltage warning

Cause:


The DC-bus voltage of the inverter has fallen below the warning threshold for undervoltage set in 0x2540:002 (P208.02).



Remedy:


Response: Warning (Logging only inside Error history buffer/Logbook)

No adjustment parameters defined.
12834 | 0x3222

DC-bus on-UV
DC-bus voltage to low for power up

Cause:


DC-bus voltage is too low for power up.



Remedy:


Response: Warning (Logging only inside Error history buffer/Logbook)

No adjustment parameters defined.
16912 | 0x4210

PU Overtemp.
PU: overtemperature fault

Cause:


Temperature monitoring of the power unit has been triggered.

  • Ambient temperature too high.

  • Fan or ventilation slots are polluted.

  • Fan is defective.





Remedy:


Response: Fault


  • Provide for a sufficient cooling of the device.

  • Clean fan and ventilation slots.

  • If required, replace fan.

  • Set a variable switching frequency in for the inverter. The switching frequency is then automatically reduced if the output current or temperature of the power unit are too high.


17024 | 0x4280

Heatsink sensor
Heat sink temperature sensor fault

Cause:


The sensor for temperature monitoring of the power unit provides implausible measured values. This indicates a hardware defect of the sensor. As a result of the failure of the temperature monitoring, there is a risk of fire by overheating!



Remedy:


Response: Fault


  • This error cannot be corrected by the user. Consultation with the manufacturer is required.


17025 | 0x4281

Heatsink fan
Heat sink fan warning

Cause:


Heat sink fan warning triggered.



Remedy:


Response: Warning (Logging only inside Error history buffer/Logbook)

No adjustment parameters defined.
17029 | 0x4285

Warn.PU Overtemp
PU overtemperature warning

Cause:


The temperature of the power section has exceeded the warning threshold for overtemperature.



Remedy:


Response: Warning (Logging only inside Error history buffer/Logbook)

No adjustment parameters defined.
17168 | 0x4310

Overtemp. motor
Motor temperature error

Cause:


Motor temperature error.



Remedy:


Response: Fault (The error can only be reset after a blocking time of 5 s.)

No adjustment parameters defined.
20754 | 0x5112

24V supply low
24 V supply critical

Cause:


24 V supply is critical.



Remedy:


Response: Warning (Logging only inside Error history buffer/Logbook)

No adjustment parameters defined.
20864 | 0x5180

Overlaod 24V
Overload 24 V supply

Cause:


Overload on the 24 V supply.



Remedy:


Response: Warning (Logging only inside Error history buffer/Logbook)

No adjustment parameters defined.
21376 | 0x5380

Incomp. OEM HW
OEM hardware incompatible

Cause:


OEM hardware incompatible.



Remedy:


Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts). The error can only be reset by mains switching.)

No adjustment parameters defined.
24592 | 0x6010

Watchdog timeout
Watchdog time-out

Cause:


Watchdog time-out.



Remedy:


Response: Warning (Logging only inside Error history buffer/Logbook)

No adjustment parameters defined.
24961 | 0x6181

Timeout-125usTsk
Time-out in 125 us task

Cause:


Time-out in 125 us task.



Remedy:


Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts). The error can only be reset by mains switching.)

No adjustment parameters defined.
24962 | 0x6182

Timeout-250usTsk
Time-out in 250 us task

Cause:


Time-out in 250 us task.



Remedy:


Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts). The error can only be reset by mains switching.)

No adjustment parameters defined.
24963 | 0x6183

Timeout-1ms-Task
Time-out in 1 ms task

Cause:


Time-out in 1 ms task.



Remedy:


Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts). The error can only be reset by mains switching.)

No adjustment parameters defined.
24964 | 0x6184

Timeout-8ms-Task
Time-out in 8 ms task

Cause:


Time-out in 8 ms task.



Remedy:


Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts). The error can only be reset by mains switching.)

No adjustment parameters defined.
24968 | 0x6188

Internal error
Internal error

Cause:


Internal system error.



Remedy:


Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts). The error can only be reset by mains switching.)

No adjustment parameters defined.
24969 | 0x6189

PU Prog. error
PU: programming fault

Cause:


PU: programming fault.



Remedy:


Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)

No adjustment parameters defined.
24970 | 0x618A

Internal fan
Internal fan warning

Cause:


Internal fan warning.



Remedy:


Response: Warning (Logging only inside Error history buffer/Logbook)

No adjustment parameters defined.
24976 | 0x6190

PU comm mismatch
PU: communication mismatch

Cause:


PU: communication mismatch.



Remedy:


Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)

No adjustment parameters defined.
24977 | 0x6191

PU Sync. Fault
PU: communication not synchronous

Cause:


PU: communication not synchronous.



Remedy:


Response: Trouble (Serious fault: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)

No adjustment parameters defined.
24978 | 0x6192

Comm.error PU-CU
Communication error PU-CU

Cause:


Communication error PU-CU.



Remedy:


Response: Trouble (Serious fault: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)

No adjustment parameters defined.
24979 | 0x6193

PU comm error
PU: communication error

Cause:


If this error occurs, the motor may not be able to be brought to standstill anymore. If communication is lost completely, the power output stage will switch off.



Remedy:


Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)

No adjustment parameters defined.
24980 | 0x6194

PU SDO comm err.
SDO communication with PU aborted

Cause:


SDO communication with PU aborted.



Remedy:


Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)

No adjustment parameters defined.
24981 | 0x6195

I2C conn. error
I2C connection lost

Cause:


I2C connection lost.



Remedy:


Response: Warning (Logging only inside Error history buffer/Logbook)

No adjustment parameters defined.
24982 | 0x6196

I2C bus error
I2C bus error

Cause:


I2C bus error.



Remedy:


Response: Warning (Logging only inside Error history buffer/Logbook)

No adjustment parameters defined.
25008 | 0x61B0

PU uC supply err
PU: uC supply voltage drop down

Cause:


A supply voltage drop for the microprocessor of the power unit has been detected.



Remedy:


Response: Fault

No adjustment parameters defined.
25009 | 0x61B1

PU general error
PU: general error

Cause:


PU: general error.



Remedy:


Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)

No adjustment parameters defined.
25216 | 0x6280

P400 config err
Trigger/functions connected incorrectly

Cause:


The assignment directives have not been observed:

  • If the "flexible I/O configuration" is active as control source, the "Enable inverter" or "Run" function must be connected to a digital input in order that the motor can be stopped again any time!

  • In case of keypad or network control, the two functions "Enable inverter" and "Run" can also be set to "Constant TRUE [1]" to start the motor.

  • The use of the "Start forward (CW)" and "Start reverse (CCW)" functions excludes the use of the "Run forward (CW)" and "Run reverse (CCW)" and viceversa.





Remedy:


Response: Trouble

No adjustment parameters defined.
25217 | 0x6281

User fault 1
User-defined fault 1

Cause:


The "Activate fault 1" function was triggered via the flexible I/O configuration. The error can only be reset after the function has been deactivated again.



Remedy:


Response: Fault

No adjustment parameters defined.
25218 | 0x6282

User fault 2
User-defined fault 2

Cause:


The "Activate fault 2" function was triggered via the NetWordIN1 data word (or flexible I/O configuration). The error can only be reset after the function has been deactivated again.



Remedy:


Response: Fault

No adjustment parameters defined.
25232 | 0x6290

Invert rotation
Warning invert rotation

Cause:


The "Invert rotation" function was requested with an active limitation of rotation.



Remedy:


Response: Warning (Logging only inside Error history buffer/Logbook)

No adjustment parameters defined.
25233 | 0x6291

Trouble overflow
Maximum allowed troubles exceeded

Cause:


Maximum allowed troubles exceeded.



Remedy:


Response: Fault

No adjustment parameters defined.
25248 | 0x62A0

AC Dr. UserFault
AC Drive: user fault

Cause:


The "Activate fault" function was triggered via the AC drive control word. The error can only be reset after the function has been deactivated again.



Remedy:


Response: Fault

No adjustment parameters defined.
25249 | 0x62A1

Netw.UserFault 1
Network: user fault 1

Cause:


The "Activate fault 1" function was triggered via the NetWordIN1 data word. The error can only be reset after the function has been deactivated again.



Remedy:


Response: Fault

No adjustment parameters defined.
25250 | 0x62A2

Netw.UserFault 2
Network: user fault 2

Cause:


The "Activate fault 2" function was triggered via the NetWordIN1 data word. The error can only be reset after the function has been deactivated again.



Remedy:


Response: Fault

No adjustment parameters defined.
25265 | 0x62B1

NetWordIN1 error
NetWordIN1 configuration incorrect

Cause:


Two bits of the NetWordIN1 data word were assigned to the same function.



Remedy:


Response: Trouble

Check and correct the NetWordIN1 data word. The functions that are to be triggered via bit 0 ... 15 of the NetWordIN1 data word, are defined in 0x400E:001 (P505.01) ... 0x400E:016 (P505.16).
25504 | 0x63A0

EEPROM fault
On-board EEPROM: access error

Cause:


On-board EEPROM: access error.



Remedy:


Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts). The error can only be reset by mains switching.)

No adjustment parameters defined.
25505 | 0x63A1

CU ID tag error
CU: load error ID tag

Cause:


CU: load error ID tag.



Remedy:


Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts). The error can only be reset by mains switching.)

No adjustment parameters defined.
25506 | 0x63A2

PU ID tag error
PU: load error ID tag

Cause:


PU: load error ID tag.



Remedy:


Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts). The error can only be reset by mains switching.)

No adjustment parameters defined.
25507 | 0x63A3

PU unknown
Power unit unknown

Cause:


Power unit unknown.



Remedy:


Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts). The error can only be reset by mains switching.)

No adjustment parameters defined.
25508 | 0x63A4

EEPROM overflow
On-board EEPROM: timer overflow

Cause:


On-board EEPROM: timer overflow.



Remedy:


Response: Warning (Logging only inside Error history buffer/Logbook)

No adjustment parameters defined.
28800 | 0x7080

Assertionlevel
Assertion level monitoring (Low/High)

Cause:


The last setting of the connection level differs from the saved setting.



Remedy:


Response: Fault

Check setting in Assertationlevel. Execute device command "Save user data" 0x2022:003 (P700.03). Switch inverter off and on again.
28801 | 0x7081

AI1 fault
Analog input 1 fault

Cause:


The monitoring function of the input signal configured for the analog input 1 has been triggered.



Remedy:


Response: Fault

Adjustable in: 0x2636:010 (P430.10)
28802 | 0x7082

AI2 fault
Analog input 2 fault

Cause:


The monitoring function of the input signal configured for the analog input 2 has been triggered.



Remedy:


Response: Fault

Adjustable in: 0x2637:010 (P431.10)
28803 | 0x7083

HTL input fault
HTL input fault

Cause:


HTL input fault. Error message is not available for the inverter Emotron VS10/30.



Remedy:


Response: Warning (When the error type is set to "Warning", only logging takes place inside Error history buffer/Logbook)

No adjustment parameters defined.
28833 | 0x70A1

AO1 fault
Analog output 1 fault

Cause:


Analog output 1 fault.



Remedy:


Response: Warning (Logging only inside Error history buffer/Logbook)

No adjustment parameters defined.
28834 | 0x70A2

AO2 fault
Analog output 2 fault

Cause:


Analog output 2 fault. Error message is not available for the inverter Emotron VS10/30.



Remedy:


Response: Warning (Logging only inside Error history buffer/Logbook)

No adjustment parameters defined.
28961 | 0x7121

Pole pos. error
Pole position identification fault

Cause:


Pole position identification fault.



Remedy:


Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)

Adjustable in: 0x2C60
29056 | 0x7180

Mot max current
Motor overcurrent

Cause:


Motor overcurrent threshold exceeded.



Remedy:


Response: Fault (The error can only be reset after a blocking time of 1 s.)

Adjustable in: 0x2D46:002 (P353.02)
30336 | 0x7680

EPM full
Memory module is full

Cause:


The memory module contains too many parameter settings. The inverter copies the current backup to the user memory without overwriting the data in the RAM.



Remedy:


Response: Warning (Logging only inside Error history buffer/Logbook)

Execute device command "Save user data" 0x2022:003 (P700.03) again. This reinitialises the user memory with the current parameter settings. By this means, parameter settings no longer required are deleted automatically.
30337 | 0x7681

EPM not present
Memory module not present

Cause:


The default setting saved in the inverter firmware is loaded. The error cannot be reset by the user.



Remedy:


Response: Fault


  • Switch off inverter.

  • Plug the memory module into the inverter.

  • Switch the inverter on again.


30338 | 0x7682

EPM invalid data
Memory module invalid user data

Cause:


The user parameter settings are invalid both in the user memory and in the backup. Thus, the user parameter settings are lost. The default setting is loaded automatically.



Remedy:


Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)


  • Execute user parameter settings again.

  • Execute device command "Save user data" 0x2022:003 (P700.03).


30340 | 0x7684

Save incomplete
Data not compl. saved before powerdown

Cause:


Saving the parameter settings was interrupted by an unexpected disconnection. The user parameter settings were not saved completely. When the inverter is switched on the next time, the backup data is copied to the user memory.



Remedy:


Response: Warning (Logging only inside Error history buffer/Logbook)


  • Check user parameter settings. (The loaded backup is an older version.)

  • If required, repeat the changes made last.

  • Execute device command "Save user data" 0x2022:003 (P700.03).


30342 | 0x7686

Net.config.error
Network: configuration error

Cause:


The expected network option is missing. This error can only occur if the control unit has been replaced by a control unit with different features.



Remedy:


Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)


  • Switch off inverter.

  • Install control unit with matching network option.

  • Switch the inverter on again.


30343 | 0x7687

EPM timer overfl
Memory module: timer overflow

Cause:


During the read/write access to the memory module, a time-out has occurred, e.g. because the memory module has been removed.



Remedy:


Response: Warning (Logging only inside Error history buffer/Logbook)

No adjustment parameters defined.
30345 | 0x7689

OEM data invalid
Memory module: invalid OEM data

Cause:


The OEM memory contains invalid parameter settings or is empty. The user parameter settings are loaded automatically.



Remedy:


Response: Warning (Logging only inside Error history buffer/Logbook)

Execute device command "Save OEM data" 0x2022:006 (P700.06). Thus, the user parameter settings get lost!
30346 | 0x768A

Wrong EPM
Memory module: wrong type

Cause:


The plugged-in memory module is not supported by the inverter. The default setting saved in the inverter firmware is loaded. The error cannot be reset by the user.



Remedy:


Response: Fault


  • Switch off inverter.

  • Replace plugged-in memory module by a memory module that matches the inverter.

  • Switch the inverter on again.


30352 | 0x7690

EPM-FW incomp.
EPM firmware version incompatible

Cause:


The parameter settings saved in the memory module do not match the firmware version. The data are loaded into the RAM memory, but are incompatible.



Remedy:


Response: Fault

Execute device command "Load default settings" 0x2022:001 (P700.01). Execute device command "Save user data" 0x2022:003 (P700.03) or "Save OEM data" 0x2022:006 (P700.06) in order that the error does not occur at the next switch-on.
30353 | 0x7691

EPM: FW incomp.
EPM data: firmware type incompatible

Cause:


The parameter settings saved in the memory module do not match the firmware type. The data are loaded into the RAM memory, but are incompatible.



Remedy:


Response: Fault

Execute device command "Load default settings" 0x2022:001 (P700.01). Execute device command "Save user data" 0x2022:003 (P700.03) or "Save OEM data" 0x2022:006 (P700.06) in order that the error does not occur at the next switch-on.
30354 | 0x7692

UserCU not match
EPM data: new firmware type detected

Cause:


The parameter settings saved in the memory module do not match in the inverter hardware. The data is loaded into the RAM memory and is compatible. However, the settings must be accepted by the user.



Remedy:


Response: Fault

Reset error. Execute device command "Save user data" 0x2022:003 (P700.03) or "Save OEM data" 0x2022:006 (P700.06) in order that the error does not occur at the next switch-on. Alternatively, the default setting can be loaded and then saved.
30355 | 0x7693

EPM PU size inco
EPM data: PU size incompatible

Cause:


The parameter settings saved in the memory module do not match the power unit. The data are loaded into the RAM memory, but are incompatible.



Remedy:


Response: Fault

Execute device command "Load default settings" 0x2022:001 (P700.01). Execute device command "Save user data" 0x2022:003 (P700.03) or "Save OEM data" 0x2022:006 (P700.06) in order that the error does not occur at the next switch-on.
30356 | 0x7694

EPM new PU size
EPM data: new PU size detected

Cause:


The parameter settings saved in the memory module do not match in the inverter hardware. The data is loaded into the RAM memory and is compatible. However, the settings must be accepted by the user.



Remedy:


Response: Fault

Reset error. Execute device command "Save user data" 0x2022:003 (P700.03) or "Save OEM data" 0x2022:006 (P700.06) in order that the error does not occur at the next switch-on. Alternatively, the default setting can be loaded and then saved.
30357 | 0x7695

InvalidChgovrCfg
Invalid parameter changeover configuration

Cause:


One or several parameters cannot be used for the "parameter change-over" function. The parameter change-over is deactivated.



Remedy:


Response: Warning (Logging only inside Error history buffer/Logbook)

Check error message for parameter change-over in 0x4047:001 (P756.01) and correct the list entry displayed in 0x4047:002 (P756.02).
30358 | 0x7696

Unkn. Par in EPM
EPM data: unknown parameter found

Cause:


The memory module contains parameter settings for one or several parameters that are not known to the inverter.



Remedy:


Response: Info (Information only)

Execute device command "Save user data" 0x2022:003 (P700.03). This reinitialises the user memory with the current parameter settings. By this means, parameter settings no longer required are deleted automatically.
30359 | 0x7697

Parameter loss
Parameter changes lost

Cause:


Changed parameter settings got lost due to the removal of the 24-V voltage supply.



Remedy:


Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts).)

In order to reset the error, there are the following options: Execute device command "Load default settings" 0x2022:001 (P700.01). Execute device command "Save user data" 0x2022:003 (P700.03). Switch inverter off and on again without plugged-in USB module.
33045 | 0x8115

Time-out (PAM)
Time-out (PAM)

Cause:


The parameter access monitoring has been triggered.



Remedy:


Response: No response

Adjustable in: 0x2552:004 (P595.04)
33154 | 0x8182

CAN bus off
CAN: bus off

Cause:


A change to the "Bus-Off" state has been made.



Remedy:


Response: Trouble

Adjustable in: 0x2857:010
33155 | 0x8183

CAN bus warning
CAN: warning

Cause:


CAN bus warning level reached.



Remedy:


Response: Warning (When the error type is set to "Warning", only logging takes place inside Error history buffer/Logbook)

Adjustable in: 0x2857:011
33156 | 0x8184

CAN heartb. C1
CAN: heartbeat time-out consumer 1

Cause:


Heartbeat time-out consumer 1 triggered.



Remedy:


Response: Fault

Adjustable in: 0x2857:005
33157 | 0x8185

CAN heartb. C2
CAN: heartbeat time-out consumer 2

Cause:


Heartbeat time-out consumer 2 triggered.



Remedy:


Response: Fault

Adjustable in: 0x2857:006
33158 | 0x8186

CAN heartb. C3
CAN: heartbeat time-out consumer 3

Cause:


Heartbeat time-out consumer 3 triggered.



Remedy:


Response: Fault

Adjustable in: 0x2857:007
33159 | 0x8187

CAN heartb. C4
CAN: heartbeat time-out consumer 4

Cause:


Heartbeat time-out consumer 4 triggered.



Remedy:


Response: Fault

Adjustable in: 0x2857:008
33168 | 0x8190

Watchdog timeout
Network: watchdog timeout

Cause:


Network watchdog timeout triggered.



Remedy:


Response: Fault

No adjustment parameters defined.
33170 | 0x8192

Net. Init. error
Network: initialisation error

Cause:


Network communication stack initialisation failed.



Remedy:


Response: Fault

No adjustment parameters defined.
33171 | 0x8193

Inv. cyclic data
Network: invalid cyclic process data

Cause:


Invalid cyclic process data packets received.



Remedy:


Response: Trouble

No adjustment parameters defined.
33184 | 0x81A0

Modbus TX error
Modbus transmit message error

Cause:


Modbus transmit message error.



Remedy:


Response: Warning (Logging only inside Error history buffer/Logbook)

No adjustment parameters defined.
33185 | 0x81A1

Modbus time-out
Modbus: network time-out

Cause:


No valid messages have been received via the Modbus for a longer time than the time-out time set in 0x2858:002 (P515.02).



Remedy:


Response: Fault

Adjustable in: 0x2858:001 (P515.01)
33186 | 0x81A2

Modbus request
Modbus: incorrect request by master

Cause:


Modbus: incorrect request sent by master.



Remedy:


Response: Warning (Logging only inside Error history buffer/Logbook)

No adjustment parameters defined.
33414 | 0x8286

PDO map error
Network: PDO mapping error

Cause:


Network: PDO mapping configuration error.



Remedy:


Response: Fault

No adjustment parameters defined.
33425 | 0x8291

Timeout RPDO1
CAN: RPDO1 time-out

Cause:


The RPDO was not received within the monitoring time set for the RPDO or not with the configured sync.



Remedy:


Response: Fault

Adjustable in: 0x2857:001
33426 | 0x8292

Timeout RPDO2
CAN: RPDO2 time-out

Cause:


The RPDO was not received within the monitoring time set for the RPDO or not with the configured sync.



Remedy:


Response: Fault

Adjustable in: 0x2857:002
33427 | 0x8293

Timeout RPDO3
CAN: RPDO3 time-out

Cause:


The RPDO was not received within the monitoring time set for the RPDO or not with the configured sync.



Remedy:


Response: Fault

Adjustable in: 0x2857:003
33553 | 0x8311

Torque limit
Torque limit reached

Cause:


The maximum possible torque has been reached and the deceleration time set in 0x2D67:002 (P329.02) has elapsed.



Remedy:


Response: No response

Adjustable in: 0x2D67:001 (P329.01)
36992 | 0x9080

Keypad removed
Keypad removed

Cause:


The keypad was removed while the keypad control was activated.



Remedy:


Response: Fault

Plug on the keypad again or activate another control source.
65282 | 0xFF02

BrkResistor OL.F
Brake resistor: overload fault

Cause:


Brake resistor overload fault. Error message is not available for the inverter Emotron VS10/30.



Remedy:


Response: Fault (The error can only be reset after a blocking time of 5 s.)

No adjustment parameters defined.
65285 | 0xFF05

STO error
Safe Torque Off error

Cause:


Safe Torque Off error detected.



Remedy:


Response: Fault (Serious error: The inverter is inhibited immediately. The motor becomes torqueless (coasts). The error can only be reset by mains switching.)

No adjustment parameters defined.
65286 | 0xFF06

Motor overspeed
Motor overspeed

Cause:


The motor speed has reached the error threshold for overspeed.



Remedy:


Response: Fault (The error can only be reset after a blocking time of 1 s.)

Adjustable in: 0x2D44:002 (P350.02)
65289 | 0xFF09

Mot.Phase miss.
Motor phase missing

Cause:


A failure of several motor phases has been detected.



Remedy:


Response: No response (The error can only be reset after a blocking time of 2 s.)

Adjustable in: 0x2D45:001 (P310.01)

Check wiring between inverter and motor. In case of a false tripping, adapt the settings for the motor phase failure detection.
65290 | 0xFF0A

Phase U failure
Motor phase failure phase U

Cause:


A failure of the motor phase U has been detected.



Remedy:


Response: No response (The error can only be reset after a blocking time of 2 s.)

Adjustable in: 0x2D45:001 (P310.01)

Check wiring between inverter and motor. In case of a false tripping, adapt the settings for the motor phase failure detection.
65291 | 0xFF0B

Phase V failure
Motor phase failure phase V

Cause:


A failure of the motor phase V has been detected.



Remedy:


Response: No response (The error can only be reset after a blocking time of 2 s.)

Adjustable in: 0x2D45:001 (P310.01)

Check wiring between inverter and motor. In case of a false tripping, adapt the settings for the motor phase failure detection.
65292 | 0xFF0C

Phase W failure
Motor phase failure phase W

Cause:


A failure of the motor phase W has been detected.



Remedy:


Response: No response (The error can only be reset after a blocking time of 2 s.)

Adjustable in: 0x2D45:001 (P310.01)

Check wiring between inverter and motor. In case of a false tripping, adapt the settings for the motor phase failure detection.
65305 | 0xFF19

Motor ID fault
Motor parameter identification fault

Cause:


During the automatic identification of the motor, an error has occurred.



Remedy:


Response: Fault

No adjustment parameters defined.
65334 | 0xFF36

BrkResistor OL.W
Brake resistor: overload warning

Cause:


Brake resistor overload warning. Error message is not available for the inverter Emotron VS10/30.



Remedy:


Response: Warning (When the error type is set to "Warning", only logging takes place inside Error history buffer/Logbook)

No adjustment parameters defined.
65335 | 0xFF37

Auto start disab
Automatic start disabled

Cause:


When the mains power was switched on, there was already a start command and the automatic start at power-up is set to "Off [0]" in 0x2838:002 (P203.02).



Remedy:


Response: Fault

Deactivate start command and reset error.
65366 | 0xFF56

Max. motor freq.
Maximum motor frequency reached

Cause:


The maximum motor speed set in 0x6080 (P322.00) is active.



Remedy:


Response: Warning (Logging only inside Error history buffer/Logbook)

No adjustment parameters defined.
65413 | 0xFF85

Keypad full ctrl
Keypad full control active

Cause:


The "Keypad Full Control" control mode is active. Both the control and the setpoint selection are made via the keypad. A renewed click of the keypad key CTRL serves to stop the control mode again.



Remedy:


Response: Warning (Logging only inside Error history buffer/Logbook)

No adjustment parameters defined.

How to Clear & Reset Emotron VS10 Drive Faults

  1. Keypad Reset: Press the red Stop / Reset key on the plug-in control panel display. Ensure that the active run command is removed before clearing the trip.
  2. Digital Input Reset (DI): If assigned in parameter P400.04 (0x2631:004 – Fault reset), send a 24VDC pulse to the assigned terminal (default DI5) to clear pending trip errors.
  3. EASY Starter PC Software: Connect via the USB diagnostic interface module or WiFi adapter, launch Emotron EASY Starter, and select “Reset Fault” in the diagnostics toolbar.
  4. Fieldbus Control Word: Toggle Bit 7 (Fault Reset) in the Control Word (index 0x6040) from 0 to 1 over Modbus RTU or CANopen communication.
  5. Mains Power Cycle: Disconnect AC input mains power (L1/N), wait approximately 3 to 5 minutes until internal DC capacitors fully discharge and the status LED turns off, then re-energize the drive.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that the internal DC bus voltage has dropped strictly below 50VDC across terminals [+UG / -UG] (or [+DC / -DC]) before opening wiring covers or inspecting motor output terminals U, V, and W on the Emotron VS10 drive.