Emotron VSB Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Emotron VSB compact AC drive series. Search or filter through the complete fault code directory below.
Power Range
0.75 – 5.5 kW (1 – 7.5 HP)
Supply Voltage
1-Ph 200–240V / 3-Ph 380–480V
Control Modes
Sensorless Vector (SVC) & V/F
Operator Interface
Detachable Keypad with Potentiometer
Complete Emotron VSB Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type OC-1, OV-2, or OL-1).
| Fault Display | Description, Causes, and Solutions |
|---|---|
| oC1 (Code: 1) | oC1 fault indicates Accel overcurrent. This means the inverter's output current has exceeded the safe threshold during the motor's acceleration phase. Possible Causes: 1: Torque boost is too big under V/f control. 2: Starting frequency is too high. 3: Accel time is too short. 4: Motor parameters are improperly set. 5: Output short circuit (phase-to-phase short circuit or output ground short circuit). 6: Overload is too heavy. 7: Inappropriate V/f curve under V/f control. 8: Restart the rotating motor. Solutions: 1: Reduce torque boost value. 2: Drop starting frequency. 3: Prolong the Accel time. 4: Set the parameters correctly according to motor nameplate. 5: Check motor connection and output ground impedance. 6: Reduce the load. 7: Set V/f curve correctly. 8: Reduce current limited value or start through speed search. |
| oC2 (Code: 2) | oC2 fault indicates Constant-speed overcurrent. This means the inverter's output current has exceeded the safe threshold while the motor was operating at a steady, constant speed. Possible Causes: 1: Output short circuit (phase-to-phase short circuit or output ground short circuit). 2: Overload is too heavy. 3: Power rating of the drive is relatively small. 4: Input voltage is too low. Solutions: 1: Check motor connection and output ground impedance. 2: Reduce the load. 3: Select appropriate drive power rating. 4: Check power grid voltage. |
| oC3 (Code: 3) | oC3 fault indicates Decel overcurrent. This means the inverter's output current has exceeded the safe threshold during the motor's deceleration phase. Possible Causes: 1: Output short circuit (phase-to-phase short circuit or output ground short circuit). 2: Load inertia is too big. 3: Decel time is too short. 4: Input voltage is too low. Solutions: 1: Check motor connection and output ground impedance. 2: Use dynamic brake. 3: Prolong the Decel time. 4: Check power grid voltage. |
| ov1 (Code: 4) | ov1 fault indicates Accel overvoltage. This means the drive's internal DC bus voltage has risen above the maximum safe limit during motor acceleration. Possible Causes: 1: Load inertia is too big. 2: Abnormal input voltage. 3: Output short circuit (phase-to-phase short circuit or output ground short circuit). Solutions: 1: Use dynamic brake. 2: Check power grid voltage. 3: Check motor connection and output ground impedance. |
| ov2 (Code: 5) | ov2 fault indicates Constant-speed overvoltage. This means the inverter's internal DC bus voltage exceeded the safe limit while the motor was operating at a steady, constant speed. Possible Causes: 1: Load variation is too big. 2: Abnormal input voltage. 3: Output short circuit (phase-to-phase short circuit or output ground short circuit). 4: Improper parameter setting of regulator under SVC control. Solutions: 1: Check the load. 2: Check power grid voltage. 3: Check motor connection and output ground impedance. 4: Properly set regulator parameters. |
| ov3 (Code: 6) | ov3 fault indicates Decel overvoltage. This means the drive's internal DC bus voltage has risen above the maximum safe limit during motor deceleration. Possible Causes: 1: Load inertia is too big. 2: Abnormal input voltage. Solutions: 1: Use dynamic braking. 2: Check power grid voltage. |
| FAL (Code: 7) | FAL fault indicates Module protection. This means the inverter's internal hardware protection for the power module has been triggered due to abnormal operating conditions. Possible Causes: 1: Output short circuit (phase-to-phase short circuit or output ground short circuit). 2: Fan damaged or air duct blocked. 3: Direct connection of inverter module. 4: Switching power supply damaged. 5: Control board abnormal. 6: Ambient temperature is too high. 7: Loose connection of control board. 8: Overvoltage or overcurrent. Solutions: 1: Check motor connection and output ground impedance. 2: Clear the air duct or replace the fan. 3: Seek services. 4: Seek services. 5: Seek services. 6: Reduce ambient temperature. 7: Pull out and reinsert the cables of control board. 8: Handle it with the solutions of overvoltage or overcurrent. |
| tUN (Code: 8) | tUN fault indicates Parameter identification failed. This means the drive could not successfully complete the auto-tuning process to determine the motor's electrical characteristics. Possible Causes: 1: Bad motor connection. 2: Identification during rotation of the motor. 3: Bias between motor parameters and their setting is too big. Solutions: 1: Check motor connection. 2: Identification in stationary status of the motor. 3: Set the parameters correctly according to motor nameplate. |
| oL1 (Code: 9) | oL1 fault indicates Drive overloaded. This means the inverter is outputting a current higher than its rated capacity for a duration that exceeds its thermal overload limits. Possible Causes: 1: Torque boost is too big under V/f control. 2: Starting frequency is too high. Solutions: 1: Reduce torque boost value. 2: Drop starting frequency. |
| oL2 (Code: 10) | oL2 fault indicates Motor overloaded. This means the motor is drawing current exceeding its rated capacity, triggering the drive's thermal protection algorithm for the motor. Possible Causes: 1: Torque boost is too big under V/f control. 2: Inappropriate V/f curve under V/f control. 3: Motor parameters are improperly set. 4: Improper setting of motor overloaded protection time. 5: Motor stalled or sharp variation of load. 6: Long-term running of ordinary motor at low speed with heavy load. Solutions: 1: Reduce torque boost value. 2: Set V/f curve correctly. 3: Set the parameters correctly according to motor nameplate. 4: Properly set the motor overloaded protection time. 5: Identify the causes of motor stalling or check the load condition. 6: Select variable frequency motor. |
| CtC (Code: 11) | CtC fault indicates Current detection abnormal. This means the drive's internal current sensing circuitry has failed or detected an implausible current reading. Possible Causes: 1: Abnormal connection of control board. 2: Switching power supply damaged. 3: Hall device damaged. 4: Output ground leakage. Solutions: 1: Seek services. 2: Seek services. 3: Seek services. 4: Seek services. |
| GdP (Code: 12) | GdP fault indicates Output ground short-circuit protection. This means a short circuit to ground has been detected on the output side of the drive or the motor. Possible Causes: 1: Output connection ground short circuit. 2: Motor insulation abnormal. 3: Inverter module abnormal. 4: Output ground leakage current is too big. Solutions: 1: Check motor connection and output ground impedance. 2: Check the motor. 3: Seek services. 4: Seek services. |
| ISF (Code: 13) | ISF fault indicates Input power supply abnormal. This means there is an issue with the incoming AC power supply, such as severe phase imbalance or a wiring issue. Possible Causes: 1: Serious voltage imbalance among three phases of power supply. 2: Abnormal bus capacitance. 3: Abnormal input wiring of power supply. Solutions: 1: Check power grid voltage. 2: Seek services. 3: Check power supply input wiring. |
| oPL (Code: 14) | oPL fault indicates Output phase loss. This means one or more phases in the power being delivered from the inverter to the motor are disconnected or severely unbalanced. Possible Causes: 1: Motor cable connection abnormal. 2: Imbalance among motor three phases. 3: Incorrect setting of vector control parameters. Solutions: 1: Check motor connection. 2: Check or replace the motor. 3: Correctly set vector control parameters. |
| oH1 (Code: 16) | oH1 fault indicates Heat sink thermal protection. This means the temperature of the drive's internal heat sink has exceeded the safe operating threshold. Possible Causes: 1: Ambient temperature is too high. 2: Fan damaged. 3: Air duct blocked. 4: Temperature sensor abnormal. 5: Inverter module abnormal. Solutions: 1: Drop ambient temperature. 2: Replace the fan. 3: Clear air duct. 4: Seek services. 5: Seek services. |
| oH3 (Code: 18) | oH3 fault indicates Module temperature detection undisconnected. This means the drive's internal temperature sensing circuit is failing to provide valid readings or is detecting an extreme out-of-bounds temperature. Possible Causes: 1: Module detection circuit damaged. 2: Thermistor damaged. 3: Ambient temperature is too low. Solutions: 1: Seek services. 2: Seek services. 3: Raise ambient temperature. |
| PEr (Code: 24) | PEr fault indicates External equipment error. This means the drive has received a fault signal from external machinery or an external sensor via its digital input terminals. Possible Causes: 1: External fault terminal is enabled. 2: Stall condition lasts too long. Solutions: 1: Check the status of external fault terminal. 2: Check if the load is abnormal. |
| to2 (Code: 26) | to2 fault indicates Consecutive running time attained. This means the drive has been operating without stopping for a continuous duration that exceeds the pre-programmed time limit. Possible Causes: 1: "Consecutive running time attained" enabled. Solutions: 1: See specification of Group E0. |
| to3 (Code: 27) | to3 fault indicates Cumulative running time attained. This means the total accumulated running time of the drive has reached the user-defined maximum threshold. Possible Causes: 1: "Cumulative running time attained" enabled. Solutions: 1: See specification of Group E0. |
| TrC (Code: 31) | TrC fault indicates Port communication abnormal. This means the serial communication link between the drive and an external controller or PC has been disrupted or configured incorrectly. Possible Causes: 1: Improper setting of baud rate. 2: Communication port disconnection. 3: Upper computer/device does not work. 4: Drive communication parameter error. Solutions: 1: Set properly. 2: Reconnect. 3: Make upper computer/device work. 4: Set properly. |
| oCr (Code: 37) | oCr fault indicates Benchmark protection. This means an internal hardware fault, specifically related to the reference voltage or benchmark switching power, has been detected. Possible Causes: 1: Switching power supply damaged. 2: Control board damaged. Solutions: 1: Seek services. 2: Seek services. |
| SP1 (Code: 38) | SP1 fault indicates 5V power supply out-of-limit. This means the drive's internal 5-volt DC control power supply has drifted outside of acceptable operational limits. Possible Causes: 1: Switching power supply damaged. 2: Control board damaged. Solutions: 1: Seek services. 2: Seek services. |
| AIP (Code: 40) | AIP fault indicates AI input out-of-limit. This means the analog input signal received by the drive is either too high or too low compared to the configured allowable range. Possible Causes: 1: Control board damaged. 2: AI input is too high or low. Solutions: 1: Seek services. 2: Set AI input within correct range. |
| LoU (Code: 41) | LoU fault indicates Undervoltage protection. This means the incoming mains voltage or internal DC bus voltage has dropped below the minimum required for safe operation. Possible Causes: 1: Input voltage abnormal. 2: Switching power supply abnormal. Solutions: 1: Check input power grid voltage. 2: Seek services. |
| Plo (Code: 45) | Plo fault indicates PID detection out-of-limit. This means the feedback signal for the closed-loop PID controller has exceeded the acceptable deviation limits. Possible Causes: 1: PID feedback channel abnormal. 2: Inappropriate setting of PID parameters. Solutions: 1: Check the feedback channel. 2: Set properly. |
| ICF (Code: 46) | ICF fault indicates Inside communication fault. This means the internal data communication between the control board and the power board or microprocessors has failed. Possible Causes: 1: Drive chip abnormal. 2: Severe noise on site. Solutions: 1: Seek services. 2: Take corresponding countermeasures to the noise or seek service. |
How to Clear & Reset Emotron VSB Drive Faults
- Keypad Reset: Press the red STOP/RESET button on the front operator panel. If the drive is commanded from remote terminals, ensure keypad reset authority is enabled in control parameter settings.
- Digital Input (DI) Terminal Reset: Configure any multi-function digital input terminal (X1 to X4) to the fault reset function. Apply a momentary 24V DC signal to reset the active trip condition.
- Modbus RTU Communication: Send a fault clear command via the onboard RS-485 serial communication port (terminals 485+ and 485-) by setting the reset bit in the serial control register.
- Automatic Fault Reset: For non-critical trip conditions such as transient overvoltage or temporary overcurrent, configure the auto-reset parameters to allow automatic clearance after a programmed delay.
- Mains Power Cycle: Disconnect AC input mains power. Wait at least 5 minutes until the LED display and charge lamp turn off completely to discharge intermediate capacitors, then reapply power.
⚠️ High-Voltage Electrical Safety Warning:
Always wait at least 5 minutes after disconnecting AC supply power and verify with a calibrated digital multimeter that intermediate DC bus voltage across terminals [+ / -] measures strictly below 36V DC before inspecting terminals, removing covers, or touching motor leads U, V, and W on the Emotron VSB drive.