Hitachi L200 Inverter Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Hitachi L200 compact variable frequency drive series. Search or filter through the complete fault code directory below.
Power Range
0.2 – 7.5 kW (1/4 – 10 HP)
Supply Voltage
200–240V / 380–460V AC
Control Modes
V/f Control & Sensorless Vector
Operator Interface
Built-in Digital Keypad & Potentiometer
Complete Hitachi L200 Inverter Fault Code Directory
Use the search box in the table below to quickly find your error code (e.g., type E01, E07, E12, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| E01 Over-current event while at constant speed | Cause: The inverter output was short-circuited, or the motor shaft is locked or has a heavy load. These conditions cause excessive current for the inverter, so the inverter output is turned OFF. The dual-voltage motor is wired incorrectly. Remedy:
|
| E02 Over-current event during deceleration | Cause: The inverter output was short-circuited, motor shaft is locked, heavy load, or incorrectly wired motor. (Excessive current detected during deceleration). Remedy:
|
| E03 Over-current event during acceleration | Cause: The inverter output was short-circuited, motor shaft is locked, heavy load, or incorrectly wired motor. (Excessive current detected during acceleration). Remedy:
|
| E04 Over-current event during other conditions | Cause: The inverter output was short-circuited, motor shaft is locked, heavy load, or incorrectly wired motor. (Detected in conditions other than constant speed, accel, or decel). Remedy:
|
| E05 Overload protection | Cause: When a motor overload is detected by the electronic thermal function, the inverter trips and turns OFF its output. Remedy:
|
| E07 Over-voltage protection | Cause: When the DC bus voltage exceeds a threshold, due to regenerative energy from the motor. Remedy:
|
| E08 EEPROM error | Cause: When the built-in EEPROM memory has problems due to noise or excessive temperature, the inverter trips and turns OFF its output to the motor. Remedy:
|
| E09 Under-voltage error | Cause: A decrease of internal DC bus voltage below a threshold results in a control circuit fault. This condition can also generate excessive motor heat or cause low torque. Remedy:
|
| E11 / E22 CPU error | Cause: A malfunction in the built-in CPU has occurred, so the inverter trips and turns OFF its output to the motor. Remedy:
|
| E12 External trip | Cause: A signal on an intelligent input terminal configured as EXT has occurred. The inverter trips and turns OFF the output to the motor. Remedy:
|
| E13 USP (Unattended Start Protection) | Cause: When USP is enabled, an error occurred when power is applied while a Run signal is present. The inverter trips and does not go into Run Mode. Remedy:
|
| E14 Ground fault | Cause: The inverter is protected by the detection of ground faults between the inverter output and the motor during powerup tests. Remedy:
|
| E15 Input over-voltage | Cause: The inverter tests for input over-voltage after the inverter has been in Stop Mode for 100 seconds. If an over-voltage condition exists, the inverter enters a fault state. Remedy:
|
| E21 Inverter thermal trip | Cause: When the inverter internal temperature is above the threshold, the thermal sensor detects excessive temperature of power devices and trips. Remedy:
|
| E30 Driver error | Cause: An internal inverter error has occurred at the safety protection circuit between the CPU and main driver unit. Excessive electrical noise may be the cause. Remedy:
|
| E35 Thermistor | Cause: When a thermistor is connected to terminals [6] and [L] and the inverter has sensed the temperature is too high. Remedy:
|
| E60 Communications error | Cause: The inverter’s watchdog timer for the communications network has timed out. Remedy:
|
| --- Under-voltage (brown-out) with output shutoff | Cause: Due to low input voltage, the inverter turns its output OFF and tries to restart. If it fails to restart, the alarm trips. Remedy:
|
How to Clear & Reset Hitachi L200 Inverter Faults
- Keypad Stop/Reset Key: Press the red STOP/RESET key on the front digital operator panel when the drive displays a trip code (E01–E60). The Stop/Reset key clears trip states only when the inverter is in an alarm condition.
- Intelligent Input Terminal Reset [RS]: Pulse the digital input terminal assigned to the Reset function (Terminal 5 is mapped by default to RS in parameter
C005 = 18). The inverter resets when the RS terminal signal transitions from ON to OFF. - Serial Network Reset (RS-485): Send a trip reset command word via the built-in Modbus RTU communication network over the serial port interface to clear the active alarm status remotely.
- Power Cycle: Disconnect main AC supply line power. Wait at least 10 minutes for internal capacitors to fully discharge and the front display/charge indicator LED to turn completely dark before reapplying power.
⚠️ High-Voltage Electrical Safety Warning:
Hazardous residual voltages remain stored in the intermediate DC bus capacitors even after main AC power is disconnected. Wait at least 10 minutes after turning off the power and verify that the red “CHARGE” LED has completely extinguished. Always verify with a calibrated digital multimeter that the DC voltage across terminals [+] and [-] (or P and N) has dropped below 50VDC before inspecting motor leads, wiring terminal blocks, or touching inverter terminals U/T1, V/T2, and W/T3.