Hitachi L300P Drive Fault Codes & Diagnostic Guide

Comprehensive fault code reference directory, trip alarm causes, and step-by-step diagnostic procedures for the Hitachi L300P variable frequency drive series. Search or filter through the complete fault code directory below.

Fan & Pump Application Drive Power: 1.5 to 132 kW (2 to 175 HP) Automatic Energy-Saving (AES)
Power Range 1.5 – 132 kW (2 – 175 HP)
Supply Voltage 200–240V / 380–480V (3-Phase)
Control Modes V/f Control & Auto Energy Saving
Operator Interface Digital Operator (OPE-SR / OPE-S)

Complete Hitachi L300P Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type E01, E07, or Overcurrent).

Fault Code and MeaningCause and Remedy
E01
Over current event while at constant speed

Cause: The inverter output was short-circuited, or the motor shaft is locked or has a heavy load. These conditions cause excessive current for the inverter, so the inverter output is turned OFF. The dual-voltage motor might be wired incorrectly.



Remedy:

  • Check for short circuits at the output.

  • Inspect the motor shaft for locking or mechanical obstruction.

  • Reduce the load on the motor.

  • Verify the dual-voltage motor wiring connections.


E02
Over current event during deceleration

Cause: Excessive current detected during deceleration. Similar causes to E01 (short circuit, heavy load, or locked shaft).



Remedy:

  • Check for output short circuits.

  • Increase the deceleration time.

  • Check if the load inertia is too high.


E03
Over current event during acceleration

Cause: Excessive current detected during acceleration. The dual-voltage motor is wired incorrectly or load is too heavy.



Remedy:

  • Check motor wiring configuration.

  • Increase the acceleration time.

  • Check for mechanical binding or heavy startup load.


E04
Over current event during other conditions

Cause: DC braking power (A054) is set too high, a current transformer (CT) error occurred, or a noise source induced the error.



Remedy:

  • Lower the setting for DC braking power (A054).

  • Check for electrical noise sources near the inverter.

  • If the error persists, the internal CT may be faulty.


E05
Overload protection

Cause: When a motor overload is detected by the electronic thermal function, the inverter trips and turns OFF its output.



Remedy:

  • Reduce the motor load.

  • Check the electronic thermal setting parameters to ensure they match the motor.


E06
Braking resistor overload

Cause: When the regenerative braking resistor exceeds the usage time allowance or usage ratio.



Remedy:

  • Increase the deceleration time to reduce regenerative energy.

  • Check if the braking resistor is sized correctly for the application.

  • Review usage ratio settings.


E07
Over voltage protection

Cause: When the DC bus voltage exceeds a threshold, due to regenerative energy from the motor.



Remedy:

  • Increase the deceleration time.

  • Install an external braking resistor or braking unit.

  • Check input voltage level.


E08
EEPROM error

Cause: When the built-in EEPROM memory has problems due to noise or excessive temperature.



Remedy:

  • Check the ambient temperature and cooling.

  • Check for external noise sources.

  • Verify all parameter data values are still correct (Factory Reset might be required).


E09
Under-voltage error

Cause: A decrease of internal DC bus voltage below a threshold results in a control circuit fault. Can be caused by low input voltage.



Remedy:

  • Check the input power supply voltage.

  • Check for loose power connections.

  • Verify the capacity of the power supply.


E10
CT (current transformer) error

Cause: If a strong source of electrical interference is close to the inverter or a fault occurs in a built-in CT.



Remedy:

  • Remove sources of electrical interference/noise.

  • Check grounding connections.

  • If persistent, the internal CT hardware may need repair.


E11
CPU error

Cause: A malfunction in the built-in CPU has occurred.



Remedy:

  • Cycle power (OFF/ON) to the inverter.

  • Check for extreme electrical noise.

  • If error recurs, replace the control unit/inverter.


E12
External trip

Cause: A signal on an intelligent input terminal configured as EXT has occurred.



Remedy:

  • Check the external device connected to the EXT input.

  • Verify the configuration of the intelligent input terminals.

  • Clear the external fault condition.


E13
USP (Unattended Start Protection)

Cause: Power was applied while a Run signal was present (and USP is enabled).



Remedy:

  • Turn off the Run signal (switch or command).

  • Reset the inverter.

  • Ensure the Run signal is OFF before powering up the inverter.


E14
Ground fault

Cause: Detection of ground faults between the inverter output and the motor during powerup tests.



Remedy:

  • Check wiring between inverter and motor for damage.

  • Megger test the motor (disconnect inverter first).

  • Check motor insulation.


E15
Input over-voltage

Cause: Input voltage is higher than the specified value detected 60 seconds after powerup.



Remedy:

  • Measure and lower the input AC voltage.

  • Check the transformer tap settings supplying the inverter.


E16
Instantaneous power failure

Cause: Input power removed for more than 15ms. If duration exceeds B002 setting, it counts as a failure.



Remedy:

  • Check the stability of the incoming power supply.

  • Check for loose connections on the input side.

  • Adjust parameter B002 if frequent short drops occur.


E21
Inverter thermal trip

Cause: Internal temperature is above threshold. Thermal sensor detects excessive temp of power devices.



Remedy:

  • Check if the cooling fan is working and clean.

  • Check for blocked heatsink or air vents.

  • Reduce ambient temperature or improve cabinet ventilation.


E23
Gate array error

Cause: An internal inverter error occurred in communications between the CPU and gate array IC.



Remedy:

  • Cycle power to the inverter.

  • If the error persists, replace the inverter unit.


E24
Phase failure detection

Cause: One of three lines of the 3-phase power is missing.



Remedy:

  • Check input fuses and circuit breakers.

  • Check input wiring for loose connections (R, S, T).

  • Verify 3-phase voltage balance.


E30
IGBT error

Cause: Instantaneous over-current condition on any IGBT (output transistor) device.



Remedy:

  • Check for short circuits at the motor or cable.

  • Disconnect motor and run inverter; if E30 persists, the inverter IGBT is damaged.

  • Check for ground faults.


E35
Thermistor error

Cause: Thermistor connected to terminals [TH] and [CM1] indicates temperature is too high.



Remedy:

  • Check motor temperature.

  • Allow motor to cool down.

  • Check thermistor wiring and resistance values.


----
Under-voltage (brownout)

Cause: Low input voltage caused output shutoff. The alarm trips to record the event if restart fails.



Remedy:

  • Check input power lines for voltage drops.

  • Verify power supply capacity.


oooo
Automatic restart and phase loss

Cause: The inverter is restarting due to over-current, over-voltage, under-voltage, or phase loss event (See parameter B001).



Remedy:

  • Monitor the inverter to see which specific error caused the restart.

  • Check settings in "Automatic Restart Mode and Phase Loss" (Page 3-28).


E6X
Expansion card #1 connection error

Cause: An error has occurred in expansion card #1 or at its connecting terminals.



Remedy:

  • Check the connection of the expansion card.

  • Refer to the specific manual for the expansion card.

  • Re-seat the card.


E7X
Expansion card #2 connection error

Cause: An error has occurred in expansion card #2 or at its connecting terminals.



Remedy:

  • Check the connection of the expansion card.

  • Refer to the specific manual for the expansion card.

  • Re-seat the card.


How to Clear & Reset Hitachi L300P Drive Faults

  1. Keypad Reset: Press the red STOP/RESET key on the digital operator keypad (OPE-SR or OPE-S). If an instantaneous overcurrent or thermal error has triggered, wait at least 10 seconds before initiating the reset.
  2. Intelligent Terminal Reset (RS): Pulse the intelligent input terminal configured with function code 18 [RS] (Reset) (assigned via parameters C001–C007) for at least 12 ms, then open the circuit.
  3. Run Command Interlock Check: Ensure that the Run forward [FW] or Run reverse [RV] terminals are switched OFF before resetting; initiating a reset with an active Run signal will cause the drive to automatically restart or trip on E13 (USP – Unattended Start Protection).
  4. Serial RS-485 Communication: Issue a fault reset command bit via the built-in RS485 Modbus RTU communication port from your PLC or automation network to clear the trip record.
  5. Main Power Cycle: Switch off main 3-phase line power, wait at least 5 minutes until the charge lamp and keypad LED display turn completely dark (allowing internal DC bus filter capacitors to fully discharge), and then reapply input power.
⚠️ High-Voltage Electrical Safety Warning: Hazardous voltage remains stored in the internal DC bus capacitors even after turning OFF the power supply. Always wait a minimum of five (5) minutes after powering down, and verify with a calibrated DC voltmeter that voltage between terminals [+1] / [P] and [-] / [N] has dropped below 50VDC before inspecting motor leads, opening terminal shields, or servicing output terminals U, V, and W.