Hitachi S1 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Hitachi S1 sensorless vector drive series. Search or filter through the complete fault code directory below.

Sensorless Vector Control (SVC) Power: 0.4 to 500 kW (0.5 to 670 HP) Integrated Safe Torque Off (STO SIL2)
Power Range 0.4 – 500 kW (0.5 – 670 HP)
Supply Voltage 200–240V / 380–480V AC (1/3-Phase)
Control Modes Sensorless Vector (SVC) & V/f
Operator Interface LED Keypad / Optional LCD Panel

Complete Hitachi S1 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OC1, OV2, or Overcurrent).

Fault Code and MeaningCause and Remedy
OUt1
Inverter unit Phase-U protection

Cause: Acceleration is too fast; IGBT module is damaged; Misacts caused by interference; drive wires are poorly connected.



Remedy:

  • Increase acceleration time.

  • Replace the power unit.

  • Check drive wires.

  • Check whether there is strong interference surrounding the peripheral equipment.


OUt2
Inverter unit Phase-V protection

Cause: Acceleration is too fast; IGBT module is damaged; Misacts caused by interference; drive wires are poorly connected.



Remedy:

  • Increase acceleration time.

  • Replace the power unit.

  • Check drive wires.

  • Check whether there is strong interference surrounding the peripheral equipment.


OUt3
Inverter unit Phase-W protection

Cause: To-ground short circuit occurs; IGBT module damage; Interference.



Remedy:

  • Check peripheral equipment.

  • Check drive wires.

  • Replace power unit if necessary.


OV1
Over-voltage during acceleration

Cause: Exception occurred to input voltage; Large energy feedback; Lack of brake units; Dynamic brake is not enabled.



Remedy:

  • Check input power.

  • Check whether load deceleration time is too short.

  • Check if the motor starts during rotating.

  • Install dynamic brake units.

  • Check the setup of related function codes.


OV2
Over-voltage during deceleration

Cause: Exception occurred to input voltage; Large energy feedback; Lack of brake units.



Remedy:

  • Check input power.

  • Check whether load deceleration time is too short.

  • Install dynamic brake units.

  • Check the setup of related function codes.


OV3
Over-voltage during constant speed running

Cause: Exception occurred to input voltage; Large energy feedback; Dynamic brake is not enabled.



Remedy:

  • Check input power.

  • Install dynamic brake units.

  • Check the setup of related function codes.


OC1
Over-current during acceleration

Cause: Acceleration is too fast; Grid voltage is too low; Inverter power is too small; Load transient or exception occurred.



Remedy:

  • Increase acceleration time.

  • Check input power.

  • Select the inverter with larger power.

  • Check if the load is short circuited (to-ground or line-to-line).

  • Check if the rotation is smooth.


OC2
Over-current during deceleration

Cause: Deceleration is too fast; Load transient; Inverter power is too small.



Remedy:

  • Increase deceleration time.

  • Check input power.

  • Select the inverter with larger power.

  • Check the output wiring.


OC3
Over-current during constant speed running

Cause: Load transient; To-ground short circuit or output phase loss occur; Strong external interference sources; Overvoltage stall protection is not enabled.



Remedy:

  • Check if the load is short circuited.

  • Check the output wiring.

  • Check if there is strong interference.

  • Check the setup of related function codes.


UV
Bus undervoltage fault

Cause: Grid voltage is too low; Overvoltage stall protection is not enabled.



Remedy:

  • Check grid input power.

  • Check the setup of related function codes.


OL1
Motor overload

Cause: Grid voltage is too low; Rated motor current is set improperly; Motor stall or load jumps violently.



Remedy:

  • Check grid voltage.

  • Reset rated motor current.

  • Check the load and adjust torque boost.


OL2
Inverter overload

Cause: Acceleration is too fast; The motor in rotating is restarted; Grid voltage is too low; Load is too large; Power is too small.



Remedy:

  • Increase acceleration time.

  • Avoid restart after stop.

  • Check grid voltage.

  • Select the inverter with larger power.

  • Select proper motor.


SPI
Phase loss on input side

Cause: Phase loss or violent fluctuation occurred to R, S and T input.



Remedy:

  • Check the input power.

  • Check installation wiring.


SPO
Phase loss on output side

Cause: Phase loss occurred to U, V, W output (or the three phases of motor is asymmetrical).



Remedy:

  • Check the output wiring.

  • Check the motor and cable.


OH1
Overheat of rectifier module

Cause: Air duct is blocked or fan is damaged; Ambient temperature is too high; Long-time overload running.



Remedy:

  • Ventilate the air duct or replace the fan.

  • Lower the ambient temperature.


OH2
Overheat of inverter module

Cause: Air duct blocked; Fan damaged; High ambient temperature; Long-time overload.



Remedy:

  • Ventilate the air duct or replace the fan.

  • Lower the ambient temperature.


EF
External fault

Cause: External fault input terminal acts.



Remedy:

  • Check external device input.


CE
485 communication fault

Cause: Baud rate is set improperly; Communication line fault; Communication address error; Communication suffers from strong interference.



Remedy:

  • Set proper baud rate.

  • Check the wiring of communication interfaces.

  • Set proper communication address.

  • Replace or change the wiring to enhance anti-interference capacity.


ItE
Current detection fault

Cause: Poor contact of the connector of control board; Hall component is damaged; Exception occurred to amplification circuit.



Remedy:

  • Check the connector and re-plug.

  • Replace the hall component.

  • Replace the main control board.


tE
Motor autotuning fault

Cause: Motor capacity does not match inverter; Motor parameter set improperly; Autotuning parameters deviate sharply; Autotuning timeout.



Remedy:

  • Change the inverter model, or adopt V/F mode for control.

  • Set proper motor type and nameplate parameters.

  • Empty the motor load and carry out autotuning again.

  • Check motor wiring and parameter setup.

  • Check whether upper limit frequency is larger than 2/3 of the rated frequency.


EEP
EEPROM fault

Cause: R/W error occurred to the control parameters; EEPROM is damaged.



Remedy:

  • Press STOP/RST to reset.

  • Replace the main control board.


PIDE
PID feedback offline fault

Cause: PID feedback offline; PID feedback source disappears.



Remedy:

  • Check PID feedback signal wires.

  • Check PID feedback source.


bCE
Brake unit fault

Cause: Brake circuit fault or brake tube is damaged; The resistance of external brake resistor is too small.



Remedy:

  • Check the brake unit, replace with new brake tubes.

  • Increase brake resistance.


END
Running time is up

Cause: The actual running time of the inverter is larger than the set running time.



Remedy:

  • Ask help from the supplier.

  • Adjust the set running time.


OL3
Electronic overload fault

Cause: The inverter releases overload pre-alarm based on the set value.



Remedy:

  • Check the load and overload pre-alarm threshold.


PCE
Keypad communication fault

Cause: Keypad wire poorly contacted or disconnected; Keypad wire too long/strong interference; Circuit fault to keypad/main board.



Remedy:

  • Check the keypad wires to confirm whether fault exists.

  • Check the surroundings to rule out interference source.

  • Replace the hardware and ask for maintenance service.


UPE
Parameter upload error

Cause: Keypad wire poorly contacted or disconnected; Keypad wire too long/strong interference; Circuit fault.



Remedy:

  • Check the surroundings to rule out interference source.

  • Replace the hardware and ask for maintenance service.


DNE
Parameter download error

Cause: Keypad wire poorly contacted/disconnected; Keypad wire too long/interference; Data storage error.



Remedy:

  • Check the surroundings to rule out interference source.

  • Replace the hardware and ask for maintenance service.

  • Re-backup keypad data.


ETH1
To-ground short circuit fault 1

Cause: Inverter output is short connected to the ground; Current detection circuit is faulty; Actual motor power setup deviates sharply.



Remedy:

  • Check whether motor wiring is proper.

  • Replace the hall component.

  • Replace the main control board.

  • Reset the motor parameters properly.


ETH2
To-ground short circuit fault 2

Cause: Inverter output is short connected to ground; Current detection circuit is faulty; Actual motor power setup deviates sharply.



Remedy:

  • Check whether motor wiring is proper.

  • Replace the hall component.

  • Replace the main control board.

  • Reset the motor parameters properly.


LL
Electronic underload fault

Cause: The inverter performs underload pre-alarm based on the set value.



Remedy:

  • Check the load and overload pre-alarm threshold.


STO
Safe torque off

Cause: Safe torque off function is enabled by external forces.



Remedy:

  • (No corrective measure listed for normal operation/external trigger).


STL1
Exception occurred to safe circuit of channel H1

Cause: The wiring of STO is improper; Fault occurred to external switch of STO; Hardware fault occurred to safety circuit of channel H1.



Remedy:

  • Check whether terminal wiring of STO is proper and firm enough.

  • Check whether external switch of STO can work properly.

  • Replace the control board.


STL2
Exception occurred to channel H2 safe circuit

Cause: The wiring of STO is improper; Fault occurred to external switch of STO; Hardware fault occurred to safety circuit of channel H2.



Remedy:

  • Check whether terminal wiring of STO is proper and firm enough.

  • Check whether external switch of STO can work properly.

  • Replace the control board.


STL3
Exception occurred to channel H1 and channel H2

Cause: Hardware fault occurred to STO circuit.



Remedy:

  • Replace the control board.


CrCE
Safety code FLASH CRC check fault

Cause: Control board is faulty.



Remedy:

  • Replace the control board.


PoFF
System power failure

Cause: The system is powered off or the bus voltage is too low.



Remedy:

  • Check the grid conditions.


How to Clear & Reset Hitachi S1 Drive Faults

  1. Keypad Reset: Press the red STOP/RESET button on the front LED or optional LCD keypad once the fault condition has been identified and corrected.
  2. Digital Terminal Reset (DI): If programmed via function parameter group P05 (Digital Inputs) for Fault Reset, momentarily pulse the assigned digital input terminal (e.g., S1 to S8 / DI1 to DI8).
  3. Modbus RTU Communication: Write a reset command to the drive control word register via the built-in RS-485 Modbus RTU communication bus.
  4. Fault Log Inspection: Review function group P07 parameters (P07.27 to P07.32) on the keypad to view recent trip records, output frequency, and current at the time of trip.
  5. Power Cycle: Switch off the main AC line supply, wait until the keypad display and internal charge indicator extinguish completely (minimum 5 minutes for bus capacitor discharge), then restore mains power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 36VDC across terminals [+] and [-] (or P+ and P-) before servicing motor cables, opening terminal covers, or touching terminals U, V, and W on the Hitachi S1 drive.