Hitachi SJ700 Inverter Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Hitachi SJ700 high-performance industrial inverter series. Search or filter through the complete fault code directory below.

Heavy-Duty Industrial Drive Power: 0.4 to 400 kW (0.5 to 536 HP) Sensorless & Closed-Loop Vector Control
Power Range 0.4 – 400 kW (0.5 – 536 HP)
Supply Voltage 3-Phase 200–240V / 380–480V
Control Modes Sensorless Vector (SLV), 0Hz SLV, Vector & V/f
Operator Interface Standard OPE-S / Optional Multi-Language LCD (WOP)

Complete Hitachi SJ700 Inverter Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type E01, E07, E14, or Overcurrent).

Fault Code and MeaningCause and Remedy

E01 / OC.Drive


Overcurrent protection (During constant speed operation)

Cause:

  • The motor load has fluctuated sharply.

  • Short circuit of output connections.

  • Ground fault.




Remedy:

  • Eliminate the load fluctuation.

  • Check the output cables for short circuits.

  • Check the output cables and motor for ground faults.



E02 / OC.Decel


Overcurrent protection (During deceleration)

Cause:
The inverter has decelerated the motor too quickly.



Remedy:
Increase the deceleration time.

E03 / OC.Accel


Overcurrent protection (During acceleration)

Cause:

  • The inverter has accelerated the motor too quickly.

  • The motor has been locked.

  • The torque boost current has been set too high.




Remedy:

  • Increase the acceleration time.

  • Check the motor and wiring.

  • Reduce the boost current.



E04 / Over.C


Overcurrent protection (Others)

Cause:

  • The DC braking force is too high.

  • Current detector (CT) failure.




Remedy:

  • Reduce the braking force.

  • Replace or repair the Current Detector (CT).



E05 / Over.L


Overload protection

Cause:

  • The motor load is too high.

  • The thermal level setting is inappropriate.




Remedy:

  • Reduce the load factor.

  • Adjust the thermal level appropriately.

  • If operating at 5Hz or less, reduce torque boost current.



E06 / OL.BRD


Braking resistor overload protection

Cause:

  • The inverter has decreased the motor speed too quickly.

  • The operation cycle is too short.

  • The set BRD operation rate is too low.




Remedy:

  • Increase the deceleration time.

  • Prolong the operation cycle.

  • Adjust the setting to an appropriate level (confirm resistor capacity).



E07 / Over.V


Overvoltage protection

Cause:

  • The inverter has decreased the motor speed too quickly (regenerative energy).

  • Ground fault.

  • Motor rotated by the action of the load.




Remedy:

  • Increase the deceleration time.

  • Check the output cables and motor for ground faults.

  • Reduce the regenerative energy.



E08 / EEPROM


EEPROM error

Cause:

  • Noise sources located near the inverter.

  • Cooling efficiency has deteriorated (overheating).




Remedy:

  • Remove noise sources.

  • Check the heat sink for clogging and clean it.

  • Replace the cooling fan.

  • Initialize inverter and reset parameters.



E09 / Under.V


Undervoltage error

Cause:

  • Power supply voltage has dropped.

  • Power supply capacity is insufficient.

  • Thyristor damage.




Remedy:

  • Check the power supply and capacity.

  • Check the thyristor (repair inverter).



E10 / CT


CT (Current Detector) error

Cause:
The internal Current Detector (CT) has failed.



Remedy:
Repair the inverter.

E11 / CPU


CPU error

Cause:

  • Internal CPU malfunction.

  • Noise interference.




Remedy:

  • Remove noise sources located near the inverter.

  • Repair the inverter if hardware failure.



E12 / EXTERNAL


External trip

Cause:
An error has occurred in the external equipment/device connected to the inverter.



Remedy:
Recover the external equipment from the error.

E13 / USP


USP error (Unattended Start Protection)

Cause:
The inverter power was turned on while an operation signal was already input/active.



Remedy:
Reset the operation command (turn switch off), and then turn on the inverter power.

E14 / GND.Flt


Ground-fault protection

Cause:

  • Ground fault between inverter output and motor.

  • Inverter hardware abnormality.




Remedy:

  • Check output cables and motor.

  • Remove output cables and check the inverter itself.



E15 / OV.SRC


Input overvoltage protection

Cause:
The input voltage is high while the inverter is stopped (kept above specification level for 100s).



Remedy:

  • Lower the input voltage.

  • Suppress power voltage fluctuation.

  • Connect an AC reactor between power supply and inverter.



E16 / Inst.P-F


Instantaneous power failure protection

Cause:

  • Power supply voltage dropped for 15ms or more.

  • Poor contacts in MCB or magnetic contactors.




Remedy:

  • Recover the power supply.

  • Replace the MCB and magnetic contactor.



E20 / OH.stFAN


Temperature error (Low cooling-fan speed)

Cause:

  • Cooling efficiency lowered (fan failure).

  • Heat sink clogged.




Remedy:

  • Replace the cooling fan.

  • Clean the heat sink.



E21 / OH.fin


Temperature error (Main circuit high temp)

Cause:

  • Improper installation (not vertical).

  • High ambient temperature.




Remedy:

  • Check the installation (ensure vertical mounting).

  • Lower the ambient temperature.



E23 / GA.COM


Gate array communication error

Cause:

  • Noise interference.

  • Internal communication cable disconnected.




Remedy:

  • Remove noise sources.

  • Check the internal connectors.



E24 / PH.fail


Phase loss input protection

Cause:

  • Phase loss in power input.

  • Poor contacts in MCB/Magnetic contactor.




Remedy:

  • Check power supply input wiring.

  • Replace MCB or magnetic contactor.



E25 / Main.Cir


Main circuit error

Cause:

  • Malfunction due to noise.

  • Main circuit element (IGBT) damage.




Remedy:

  • Remove noise sources.

  • Check the IGBT and output circuit.

  • Repair the inverter.



E30 / IGBT


IGBT error (Instantaneous overcurrent)

Cause:

  • Short circuit in output.

  • Ground fault.

  • Main circuit element (IGBT) damage.




Remedy:

  • Check output cables and motor for shorts/ground faults.

  • Check the IGBT.

  • Clean heat sink (if clogging caused overheat).



E35 / TH


Thermistor error

Cause:

  • Motor temperature is high.

  • Internal thermistor of motor damaged.

  • Noise in thermistor signal.




Remedy:

  • Check motor temperature.

  • Check the thermistor.

  • Separate thermistor wiring from other wiring (noise).



E36 / BRAKE


Braking error

Cause:

  • Brake has not turned on/off correctly.

  • Wait time (b124) is too short.

  • Braking confirmation signal wiring issue.




Remedy:

  • Check the brake.

  • Increase the wait time setting [b124].

  • Check the wiring.



E37 / EMR


Emergency stop

Cause:

  • Error in external equipment (emergency stop function enabled).

  • Noise sources.




Remedy:

  • Recover external equipment from error.

  • Remove noise sources.



E38 / OL-LowSP


Low-speed overload protection

Cause:
Overload occurred during motor operation at very low speed (0.2Hz or less).



Remedy:
Reduce the load factor.

E41 / NET.ERR


Modbus communication error

Cause:
Timeout due to line disconnection or setup issue.



Remedy:

  • Check communication speed setting.

  • Check wiring distance.

  • Check connections.



E60 to E69

(Remote: OP1-0 to OP1-9)


Option 1 Board Errors (Slot 1)

Cause:

  • E60: Encoder disconnection.

  • E61: Excessive speed.

  • E62: Positioning error.

  • E63: Position control range trip.

  • E69: Connection/Mounting error.




Remedy:

  • Check if option board is mounted correctly.

  • Check encoder wiring and settings.

  • Refer to the instruction manual for the specific Option Board (SJ-FB, SJ-DG, or SJ-DN).



E70 to E79

(Remote: OP2-0 to OP2-9)


Option 2 Board Errors (Slot 2)

Cause:
Similar causes to Option 1 errors but for the board in Slot 2.



Remedy:

  • Check board mounting.

  • Refer to the specific option board manual.



E43 / PRG.CMD


Invalid instruction (Easy Sequence)

Cause:
Invalid instruction found in downloaded program or PRG terminal active with no program.



Remedy:
Check the program code.

E44 / PRG.NST


Nesting count error

Cause:
Subroutines or loops nested more than 8 levels deep.



Remedy:
Correct the program nesting structure.

E45 / PRG.ERR1


Execution error 1

Cause:

  • Jump destination not found.

  • Arithmetic overflow/underflow or division by zero.

  • Undefined parameter or out of range setting.




Remedy:
Debug the Easy Sequence program.

E50 to E59

(PRG-0 to PRG-9)


User trips 0 to 9

Cause:
The inverter executed a "trip" instruction defined in the user program.



Remedy:
Check the condition in the program that triggers this trip.

How to Clear & Reset Hitachi SJ700 Inverter Faults

  1. Digital Operator Reset: Press the red STOP/RESET key on the front digital operator (OPE-SRmini / OPE-S / WOP). Note that on Hitachi drives, the reset triggers upon key release.
  2. Intelligent Terminal Reset (RS): Close the digital input terminal assigned to function 18: RS (Reset) for at least 12 ms, then open it. The trip clears on the falling edge of the RS signal.
  3. ProDriveNext PC Tool: Connect your PC via the RS-485 serial communication port or operator USB interface, inspect trip monitor parameters d081 through d086 (Trip History 1 to 6), and execute a software reset.
  4. Fieldbus Network Reset: Transmit a logic ‘1’ to the Reset control bit via Modbus RTU (terminals SP/SN) or optional fieldbus interfaces (DeviceNet, Profibus-DP, EtherCAT).
  5. Mains Power Cycle: Switch off the main AC line power (terminals R, S, T / L1, L2, L3). Wait at least 10 to 15 minutes until the red CHARGE lamp on the printed circuit board goes completely OFF and internal capacitors discharge, then restore mains power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [+1/P] and [-/N] before inspecting motor cables, opening terminal covers, or touching motor output terminals U/T1, V/T2, and W/T3 on the Hitachi SJ700 drive.