Hitachi SJ700B Drive Fault Codes & Diagnostic Guide

Comprehensive fault code reference directory, trip alarm causes, and step-by-step diagnostic procedures for the Hitachi SJ700B high-performance industrial inverter series. Search or filter through the complete fault code directory below.

Advanced Sensorless Vector (SLV) Power: 5.5 to 160 kW (7.5 to 215 HP) High Starting Torque & EzSQ Control
Power Range 5.5 – 160 kW (7.5 – 215 HP)
Supply Voltage 200–240V / 380–480V AC (3-Phase)
Control Modes SLV, 0Hz SLV & V/f Control
Operator Interface OPE-SRmini Digital / LCD Keypad

Complete Hitachi SJ700B Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type E01, E07, or Overcurrent).

Fault Code and MeaningCause and Remedy
E01, E02, E03, E04
Overcurrent protection

Cause:
If the motor is constrained or suddenly accelerated or decelerated, a high current will flow in the inverter and the inverter may fail. This protective function uses a DC current detector (CT) to detect overcurrent.

E01: Constant speed operation

E02: Deceleration

E03: Acceleration

E04: Others



Remedy:

Check for constraints on the motor, or sudden acceleration/deceleration conditions.
E05
Overload protection

Cause:
The internal electronic thermal protection circuit monitors the inverter output current and detects a motor overload. The inverter trips according to the setting of the electronic thermal function.



Remedy:

Check motor load and electronic thermal function settings. Note: The inverter will not accept any reset command within about 10 seconds after tripping.
E06
Braking resistor overload protection

Cause:
The BRD operation rate exceeds the setting of "b090".



Remedy:

Check the usage rate of the braking resistor and the "b090" parameter setting.
E07
Overvoltage protection

Cause:
The DC voltage across the P and N terminals rises too high (approx. 400 VDC for 200V class, 800 VDC for 400V class) due to energy regenerated by the motor or input voltage increase.



Remedy:

Check input voltage and motor regeneration conditions.
E08
EEPROM error

Cause:
Caused by external noise or an abnormal temperature rise. An EEPROM error may result in a CPU error.



Remedy:

Turn off the inverter power once. If "E08" appears again at power-on, the internal memory may have failed. Initialize the inverter and re-set parameters.
E09
Undervoltage

Cause:
The input voltage drops and the control circuit cannot function normally. DC voltage across P and N falls below about 175 VDC (200V class) or 380 VDC (400V class).



Remedy:

Check the input power supply voltage.
E11
CT error

Cause:
An error occurred in the internal current detector (CT). The CT outputs about 0.6 V or more at power-on.



Remedy:

Turn off the inverter power.
E12
CPU error

Cause:
The internal CPU malfunctions or an error occurs in it. Reading abnormal data from the EEPROM may result in a CPU error.



Remedy:

Turn off the inverter power. Reset commands may not be accepted via keypad; use RS terminal or power cycle.
E13
External trip

Cause:
An error occurred in the external equipment or device connected to the inverter, and the inverter fetched the error signal.



Remedy:

Check the external equipment connected to the external trip input.
E14
USP error

Cause:
The inverter power was turned on while an input operation signal was remaining in the inverter (USP function enabled).



Remedy:

Remove the input operation signal before powering on, or reset the alarm.
E15
Ground-fault protection

Cause:
Ground fault detected between the inverter output circuit and the motor upon power-on.



Remedy:

Check the motor and cabling for ground faults. Turn off the inverter power.
E16
Input overvoltage protection

Cause:
Input voltage kept above the specification level for 100 seconds while the inverter is stopped (approx. 390 VDC for 200V class, 780 VDC for 400V class).



Remedy:

Check the input power supply voltage.
E20
Instantaneous power failure protection

Cause:
An instantaneous power failure lasted 15 ms or more.



Remedy:

Check power supply stability. If restart mode is selected, inverter restarts after power recovery.
E21
Temperature error (Fan/Ambient)

Cause:
1. Lowering of cooling-fan speed is detected.

2. Main circuit temperature rises due to high ambient temperature or other reasons.



Remedy:

Check cooling fan operation and ambient temperature/ventilation.
E23
Gate array communication error

Cause:
Communication error between the internal CPU and gate array.



Remedy:

Internal circuit failure. Turn off power.
E24
Phase loss input protection

Cause:
Phase loss input detected (when enabled by b006=01). Phase loss continued for about 1 second or more.



Remedy:

Check input power phases/connections.
E25
Main circuit error

Cause:
The inverter cannot confirm the on/off state of IGBT due to malfunction, noise, short, or damage to the main circuit element.



Remedy:

Check for noise or hardware damage. Turn off the inverter power.
E30
IGBT error

Cause:
Instantaneous overcurrent occurred, main circuit element temperature is abnormal, or drive power dropped.



Remedy:

The inverter cannot retry operation. Check for short circuits or hardware failure.
E35
Thermistor error

Cause:
The resistance of the thermistor (in the motor) connected to the TH terminal indicates that the motor temperature rose.



Remedy:

Check motor temperature and cooling.
E37
Emergency stop

Cause:
The EMR signal is turned on (when slide switch SW1 is ON), or malfunction due to noise when EMR terminal is not ON.



Remedy:

Check EMR signal status and noise interference. Reset by turning on RS terminal (reset via digital operator not accepted).
E38
Low-speed overload protection

Cause:
Overload occurred during motor operation at very low speed (0.2 Hz or less).



Remedy:

Check load conditions at low speed.
E41
Modbus communication error

Cause:
Timeout occurred due to line disconnection during Modbus-RTU communication.



Remedy:

Check communication lines and timeout settings (C076).
E60 to E69
Option 1 error

Cause:
The inverter detects errors in the option board mounted in optional slot 1.



Remedy:

Refer to the instruction manual for the mounted option board.
E70 to E79
Option 2 error

Cause:
The inverter detects errors in the option board mounted in optional slot 2.



Remedy:

Refer to the instruction manual for the mounted option board.

How to Clear & Reset Hitachi SJ700B Drive Faults

  1. Digital Operator Reset: Press the red STOP/RESET key on the front digital keypad (OPE-SRmini) once the trip cause has been remedied. Note: on thermal overload trips (E05), allow an internal cooldown wait of 10 to 90 seconds before resetting.
  2. Intelligent Terminal Reset [RS]: Momentarily close and open the multi-function intelligent terminal assigned to Reset function 18 (terminal 5 by default, configurable via parameters C001 to C008). Turn the [RS] signal OFF to resume normal operation.
  3. Trip History Diagnosis: Navigate to monitor parameters d081 through d086 on the operator display to analyze the last 6 fault events, including output frequency, motor current, and DC bus voltage recorded at trip point.
  4. Network Communication Reset: Send a reset command bit over Modbus RTU (via integrated RS-485 port) or optional fieldbus communication network module (DeviceNet, Profibus, EtherCAT).
  5. AC Power Cycle: Disconnect the incoming 3-phase AC main power supply. Wait at least 10 minutes until the internal CHARGE lamp turns completely off and internal filter capacitors discharge, then restore mains power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [+] and [-] (or P and N) and wait at least 10 minutes after turning off input AC power before servicing motor cables or touching main circuit terminals U, V, and W on the Hitachi SJ700B drive.