Hitachi SJ700D Inverter Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Hitachi SJ700D high-performance industrial inverter series. Search or filter through the complete fault code directory below.
Power Range
0.4 – 400 kW (0.5 – 550 HP)
Supply Voltage
200–240V / 380–480V AC (3-Phase)
Control Modes
Sensorless Vector, 0Hz SLV & Closed Loop
Operator Interface
Detachable Digital Keypad / WOP Copy Unit
Complete Hitachi SJ700D Inverter Fault Code Directory
Use the search box in the table below to quickly find your error code (e.g., type E01, E09, E14, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| E01 / E02 / E03 / E04 Overcurrent protection | Cause: The motor was constrained or suddenly accelerated/decelerated, causing high current to flow. The inverter detected current higher than the specified level.
Remedy:
|
| E05 Overload protection | Cause: The internal electronic thermal protection circuit has detected a motor overload based on the output current. Remedy:
|
| E06 Braking resistor overload protection | Cause: The BRD (Braking Resistor) operation rate exceeded the setting of "b090". Remedy:
|
| E07 Overvoltage protection | Cause: DC voltage across P and N terminals is too high. This can happen due to regenerative energy from the motor or high input voltage. Trip levels: >400 VDC (200V class) or >800 VDC (400V class). Remedy:
|
| E08 EEPROM error | Cause: Internal EEPROM error caused by external noise, abnormal temperature rise, or CPU error. Remedy:
|
| E09 Under voltage | Cause: Input voltage dropped, causing the DC voltage across P and N terminals to fall below the specified level. Trip levels: <175 VDC (200V class) or <345 VDC (400V class). Remedy:
|
| E10 CT error | Cause: Error in the internal current detector (CT). The CT outputs about 0.6 V or more at power-on. Remedy:
|
| E11 CPU error | Cause: Internal CPU malfunction or error. Can also be caused by reading abnormal data from EEPROM. Remedy:
|
| E12 External trip | Cause: An error occurred in external equipment connected to the inverter, triggering the external trip signal. Remedy:
|
| E13 USP error | Cause: Power was turned on while an input operation signal was already active (remaining in the inverter). Remedy:
|
| E14 Ground-fault protection | Cause: A ground fault was detected between the inverter output circuit and the motor upon power-on. Remedy:
|
| E15 Input overvoltage protection | Cause: Input voltage kept above specification level for 100 seconds while stopped. Remedy:
|
| E16 Instantaneous power failure protection | Cause: Instantaneous power failure lasted 15 ms or more. Remedy:
|
| E20 Temperature error (Fan) | Cause: Cooling-fan speed lowering detected. Remedy:
|
| E21 Temperature error (Main) | Cause: Main circuit temperature rose due to high ambient temperature or other reasons. Remedy:
|
| E23 Gate array communication error | Cause: Communication error between the internal CPU and gate array. Remedy:
|
| E24 Phase loss input protection | Cause: Input phase loss detected (when enabled via b006=01). Phase loss continued for about 1 second or more. Remedy:
|
| E25 Main circuit error | Cause: Gate array cannot confirm the on/off state of IGBT due to noise, short, or damage. Remedy:
|
| E30 IGBT error | Cause: Instantaneous overcurrent, abnormal main circuit element temperature, or drive power drop. The inverter shuts off to protect the element. Remedy:
|
| E34 Phase loss output protection | Cause: Output phase loss detected (when enabled via b141=01) while output frequency is 5 Hz to 100 Hz. Remedy:
|
| E35 Thermistor error | Cause: The resistance of the thermistor connected to the TH terminal indicates the motor temperature has risen. Remedy:
|
| E37 Emergency stop | Cause: EMR signal (on three terminals) turned on, or slide switch (SW1) set to ON. Malfunction due to noise if EMR not ON. Remedy:
|
| E38 Low-speed overload protection | Cause: Overload occurred during motor operation at very low speed (0.2 Hz or less). Remedy:
|
| E41 Modbus communication error | Cause: Timeout occurred due to line disconnection during Modbus-RTU communication. Remedy:
|
| E43 Invalid instruction | Cause: Inverter detected error in "Easy Sequence". Remedy:
|
| E44 Nesting count error | Cause: Inverter detected error in "Easy Sequence". Remedy:
|
| E45 Execution error | Cause: Inverter detected error in "Easy Sequence". Remedy:
|
| E50 to E59 User Trip | Cause: The inverter detects errors in the easy sequence. Remedy:
|
| E60 to E69 Option 1 error | Cause: Error in the option board mounted in optional slot 1. Remedy:
|
| E70 to E79 Option 2 error | Cause: Error in the option board mounted in optional slot 2. Remedy:
|
How to Clear & Reset Hitachi SJ700D Inverter Faults
- Keypad Stop/Reset Key: Press the red STOP/RESET key on the front digital operator panel while a trip code (E01–E60) is displayed. The Stop/Reset key acts as a reset command only when the inverter is in an active trip state.
- Intelligent Input Terminal Reset [RS]: Energize and then release the control terminal mapped to the Reset function
18 (RS)(configurable across inputs 1 to 8). The inverter completes the fault reset when the assigned RS terminal transitions from ON to OFF. - Network Communication Reset: Send a trip reset command via the standard Modbus RTU RS-485 interface or optional communication fieldbus cards (Profibus-DP, DeviceNet, or CANopen) by asserting the communication reset control bit.
- Power Cycle: Disconnect main three-phase AC power. Wait at least 10 minutes until the internal DC bus capacitors have fully discharged and the front “CHARGE” indicator LED is completely unlit before restoring power.
⚠️ High-Voltage Electrical Safety Warning:
Lethal electrical voltages remain stored in the intermediate DC bus capacitors even after primary AC line power is turned off. Wait at least 10 to 15 minutes after power-down and verify that the red “CHARGE” LED has completely extinguished. Always verify with a calibrated digital multimeter that the DC bus voltage across terminals [+] and [-] (or P and N) measures strictly below 50VDC before removing terminal covers, checking connections, or touching terminals U/T1, V/T2, and W/T3.