Hitachi WL200 Inverter Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Hitachi WL200 compact micro-drive series. Search or filter through the complete fault code directory below.

Sensorless Vector & V/f Control Power: 0.2 to 18.5 kW (1/4 to 25 HP) Safe Torque Off (STO) & Modbus RTU
Power Range 0.2 – 18.5 kW (1/4 – 25 HP)
Supply Voltage 200–240V / 380–480V AC
Control Modes Sensorless Vector, V/f & Energy Saving
Operator Interface Integrated Digital Keypad & Potentiometer

Complete Hitachi WL200 Inverter Fault Code Directory

Use the search box in the table below to quickly find your error code (e.g., type E01, E07, E14, or Overcurrent).

Fault Code and MeaningCause and Remedy
E01

Over-current event while at constant speed

Cause:

The inverter output was short-circuited, or the motor shaft is locked or has a heavy load. These conditions cause excessive current for the inverter, so the inverter output is turned OFF. Setting in dual-voltage motor is wrong.



Remedy:

Check for short circuits, unlock the motor shaft, or reduce load. Press Stop/Reset key.
E02

Over-current event during deceleration

Cause:

Excessive current detected during deceleration. (Similar conditions to E01).



Remedy:

Check deceleration time parameters. Press Stop/Reset key.
E03

Over-current event during acceleration

Cause:

Excessive current detected during acceleration. (Similar conditions to E01).



Remedy:

Check acceleration time parameters. Press Stop/Reset key.
E04

Over-current event during other conditions

Cause:

Excessive current detected during conditions other than constant speed, accel, or decel.



Remedy:

Check motor and load conditions. Press Stop/Reset key.
E05

Overload protection

Cause:

When a motor overload is detected by the electronic thermal function, the inverter trips and turns OFF its output.



Remedy:

Reduce motor load. Press Stop/Reset key.
E06

Braking resistor overload protection

Cause:

When the BRD operation rate exceeds the setting of "b090", this protective function shuts off the inverter output and displays the error code.



Remedy:

Check braking usage and "b090" setting. Press Stop/Reset key.
E07

Over-voltage protection

Cause:

When the DC bus voltage exceeds a threshold, due to regenerative energy from the motor.



Remedy:

Check input voltage and deceleration times. Press Stop/Reset key.
E08

EEPROM error

Cause:

When the built-in EEPROM memory has problems due to noise or excessive temperature, the inverter trips and turns OFF its output to the motor.



Remedy:

Reset operation by RS terminal or STOP/RESET key is not accepted. Reset by cycling power. If error persists, perform initialization.
E09

Under-voltage error

Cause:

A decrease of internal DC bus voltage below a threshold results in a control circuit fault. This condition can also generate excessive motor heat or cause low torque.



Remedy:

Check input power source. Press Stop/Reset key.
E10

Current detection error

Cause:

If an error occurs in the internal current detection system, the inverter will shut off its output and display the error code.



Remedy:

Press Stop/Reset key. If error persists, contact support.
E11

CPU error

Cause:

A malfunction in the built-in CPU has occurred, so the inverter trips and turns OFF its output to the motor.



Remedy:

Press Stop/Reset key.
E12

External trip

Cause:

A signal on an intelligent input terminal configured as EXT has occurred. The inverter trips and turns OFF the output to the motor.



Remedy:

Remove the external trip signal. Press Stop/Reset key.
E13

USP (Unattended Start Protection)

Cause:

When the Unattended Start Protection (USP) is enabled, an error occurred when power is applied while a Run signal is present.



Remedy:

Clear the Run signal. Press Stop/Reset key.
E14

Ground fault

Cause:

The inverter is protected by the detection of ground faults between the inverter output and the motor during powerup tests.



Remedy:

Reset operation by RS terminal or STOP/RESET key is not accepted. Check motor/cable for ground faults. Reset by cycling power.
E15

Input over-voltage

Cause:

The inverter tests for input over-voltage after the inverter has been in Stop Mode for 100 seconds. If an over-voltage condition exists, the inverter enters a fault state.



Remedy:

Check input voltage. After the fault is cleared, the inverter can enter Run Mode again.
E19

Inverter thermal detection system error

Cause:

When the thermal sensor in the inverter module is not connected.



Remedy:

Press Stop/Reset key.
E21

Inverter thermal trip

Cause:

When the inverter internal temperature is above the threshold, the thermal sensor in the inverter module detects the excessive temperature of the power devices and trips.



Remedy:

Allow inverter to cool. Check cooling fans/ventilation. Press Stop/Reset key.
E22

CPU communication error

Cause:

When communication between two CPU fails, inverter trips and displays the error code.



Remedy:

Press Stop/Reset key.
E25

Main circuit error

Cause:

The inverter will trip if the power supply establishment is not recognized because of a malfunction due to noise or damage to the main circuit element.



Remedy:

Check power supply and for electrical noise. Press Stop/Reset key.
E30

Driver error

Cause:

An internal inverter error has occurred at the safety protection circuit between the CPU and main driver unit. Excessive electrical noise may be the cause.



Remedy:

Reset operation by RS terminal or STOP/RESET key is not accepted. Reset by cycling power.
E35

Thermistor

Cause:

When a thermistor is connected to terminals [5] and [L] and the inverter has sensed the temperature is too high.



Remedy:

Check thermistor temperature. Press Stop/Reset key.
E36

Braking error

Cause:

When "01" has been specified for the Brake Control Enable (b120), the inverter will trip if it cannot receive the braking confirmation signal within the Brake Wait Time.



Remedy:

Check brake signal wiring and timing. Press Stop/Reset key.
E37

Safe Stop

Cause:

Safe stop signal is given.



Remedy:

Check Safe Stop input. Press Stop/Reset key.
E38

Low-speed overload protection

Cause:

If overload occurs during the motor operation at a very low speed, the inverter will detect the overload and shut off the inverter output.



Remedy:

Reduce load at low speeds. Press Stop/Reset key.
E40

Operator connection

Cause:

When the connection between inverter and operator keypad failed.



Remedy:

Check keypad connection. Press Stop/Reset key.
E41

Modbus communication error

Cause:

When “trip” is selected (C076=00) as a behavior in case of communication error, inverter trips when timeout happens.



Remedy:

Check Modbus communication lines. Press Stop/Reset key.
E43

EzSQ invalid instruction

Cause:

The program stored in inverter memory has been destroyed, or the PRG terminal was turned on without a program downloaded to the inverter.



Remedy:

Check or reload EzSQ program. Press Stop/Reset key.
E44

EzSQ nesting count error

Cause:

Subroutines, if-statement, or for-next loop are nested in more than eight layers.



Remedy:

Correct EzSQ program structure. Press Stop/Reset key.
E45

EzSQ instruction error

Cause:

Inverter found the command which cannot be executed.



Remedy:

Correct EzSQ program command. Press Stop/Reset key.
E50 to E59

EzSQ user trip (0 to 9)

Cause:

When user-defined trip happens, inverter trips and displays the error code.



Remedy:

Check user program logic. Press Stop/Reset key.
E60 to E69

Option error

Cause:

The inverter detects errors in the option board mounted in the optional slot. For details, refer to the instruction manual for the mounted option board.



Remedy:

Refer to Option Board manual. Press Stop/Reset key.
H001

Frequency upper limit warning

Cause:

Frequency upper limit (A061) > Max. Frequency (A004).



Remedy:

Correct parameter settings.
H002

Frequency lower limit warning

Cause:

Frequency lower limit (A062) > Max. Frequency (A004).



Remedy:

Correct parameter settings.
H005

Multi-speed freq warning

Cause:

Output Frequency setting (F001) or Multi-speed freq. 0 (A020) > Max. Frequency (A004).



Remedy:

Correct parameter settings.
H015

Frequency setting warning

Cause:

Output Frequency setting (F001) or Multi-speed freq. 0 (A020) > Frequency upper limit (A061).



Remedy:

Correct parameter settings.
H025

Frequency lower limit conflict

Cause:

Frequency lower limit (A062) > Output Frequency setting (F001) or Multi-speed freq. 0 (A020).



Remedy:

Correct parameter settings.
H031

Start frequency conflict

Cause:

Start frequency (A082) > Frequency upper limit (A061).



Remedy:

Correct parameter settings.
Rotating Display

Reset

Cause:

RS input is ON or STOP/RESET key is pressed.



Remedy:

Release key or RS input.
----

Under-voltage (Indication)

Cause:

If input voltage is under the allowed level, inverter shuts off output and waits with this indication.



Remedy:

Restore input voltage to allowed level.
0000

Waiting to restart

Cause:

This indication is displayed after tripping before restarting.



Remedy:

Wait for restart.
Blinking

Communication error

Cause:

Communication between inverter and digital operator fails.



Remedy:

Check connection between inverter and operator.

How to Clear & Reset Hitachi WL200 Inverter Faults

  1. Keypad Stop/Reset Key: Press the red STOP/RESET key on the front digital operator panel while the inverter displays a trip code (E01–E60). Note: The Stop/Reset key functions as a fault reset only while a trip is active.
  2. Intelligent Input Terminal Reset [RS]: Energize and de-energize the control terminal assigned to Reset function 18 (RS) (configured by default on intelligent input terminal 5 via parameter C005 = 18). The inverter resets when the terminal signal transitions from ON to OFF.
  3. Modbus RTU Serial Reset: Transmit an inverter reset command register word over the standard RS-485 Modbus RTU interface (RJ45 / screw terminals) to clear the active alarm remotely.
  4. Power Cycle: Disconnect AC line power completely. Allow at least 10 minutes for internal DC link capacitors to discharge fully and the front “CHARGE” indicator LED to turn completely dark before restoring power.
⚠️ High-Voltage Electrical Safety Warning: Lethal electrical voltages remain stored in the intermediate DC bus capacitors even after primary AC line power is turned off. Wait at least 10 minutes after power-down and verify that the red “CHARGE” LED has completely extinguished. Always verify with a calibrated digital multimeter that the DC bus voltage across terminals [+] and [-] (or P and N) measures strictly below 50VDC before inspecting motor leads, replacing cables, or touching inverter terminals U/T1, V/T2, and W/T3.