Hitachi X200 drive

Home / Hitachi / Hitachi X200 drive

Hitachi X200 Drive Fault Codes & Diagnostic Guide

Comprehensive fault code reference directory, trip alarm causes, and step-by-step diagnostic procedures for the Hitachi X200 series compact micro-inverter. Search or filter through the complete fault code directory below.

Compact General Purpose Drive Power: 0.2 to 7.5 kW (0.25 to 10 HP) Automatic Energy Saving (AES)
Power Range 0.2 – 7.5 kW (0.25 – 10 HP)
Supply Voltage 200–240V / 380–480V (1/3-Phase)
Control Modes V/f Control & Auto Energy Saving
Operator Interface Integrated LED Display & Potentiometer

Complete Hitachi X200 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type E01, E07, or Overcurrent).

Fault Code and MeaningCause and Remedy
E 01

Over-current event while at constant speed

Cause: The inverter output was short-circuited, or the motor shaft is locked or has a heavy load. The dual-voltage motor is wired incorrectly.


Remedy:

  • Check for short circuits at the inverter output.

  • Check if the motor shaft is physically locked.

  • Reduce the load on the motor.

  • Verify dual-voltage motor wiring.

  • Press Stop/Reset key to clear.


E 02

Over-current event during deceleration

Cause: Excessive current detected during deceleration. Inverter output short-circuited, motor locked, or heavy load.


Remedy:

  • Check for short circuits or ground faults.

  • Increase deceleration time.

  • Check for mechanical lock-up.

  • Press Stop/Reset key to clear.


E 03

Over-current event during acceleration

Cause: Excessive current detected during acceleration. Inverter output short-circuited, motor locked, or heavy load.


Remedy:

  • Check for short circuits.

  • Increase acceleration time.

  • Check if motor load is too heavy for the inverter rating.

  • Press Stop/Reset key to clear.


E 04

Over-current event during other conditions

Cause: Excessive current detected during conditions other than constant speed, accel, or decel.


Remedy:

  • Check motor wiring and insulation.

  • Inspect for intermittent mechanical binding.

  • Press Stop/Reset key to clear.


E 05

Overload protection

Cause: Motor overload detected by the electronic thermal function. The inverter trips to protect the motor.


Remedy:

  • Reduce the motor load.

  • Check if the electronic thermal setting matches the motor.

  • Allow motor to cool before restarting.


E 07

Over-voltage protection

Cause: The DC bus voltage exceeds a threshold, often due to regenerative energy from the motor (acting as a generator).


Remedy:

  • Increase deceleration time.

  • Install a braking resistor if deceleration is too fast.

  • Check input voltage stability.


E 08

EEPROM error

Cause: Built-in EEPROM memory has problems due to electrical noise or excessive temperature.


Remedy:

  • Check ambient temperature and cooling.

  • Check for sources of electrical noise (grounding).

  • Important: Confirm parameter data values are still correct.

  • If power was turned OFF while [RS] Reset input was ON, this error occurs on restore.


E 09

Under-voltage error

Cause: Decrease of internal DC bus voltage below threshold (Control circuit fault). Can generate excessive motor heat or low torque.


Remedy:

  • Check input power supply voltage.

  • Check for loose power connections.

  • Press Stop/Reset key to clear.


E 11

CPU error

Cause: A malfunction in the built-in CPU has occurred.


Remedy:

  • Cycle power to the inverter.

  • Check for excessive electrical noise interference.

  • If the error persists, the unit may require service.


E 12

External trip

Cause: A signal on an intelligent input terminal configured as EXT (External Trip) has occurred.


Remedy:

  • Investigate the external device connected to the EXT terminal.

  • Remove the external error condition.

  • Press Stop/Reset key to clear.


E 13

USP (Unattended Start Protection)

Cause: Power was applied while a Run signal was already present (and USP is enabled).


Remedy:

  • Turn off the Run signal (switch or command).

  • Press Stop/Reset key to clear the error.

  • Re-apply Run signal to start.


E 14

Ground fault

Cause: Ground fault detected between the inverter output and the motor during powerup tests.


Remedy:

  • Check wiring between inverter and motor for damage.

  • Check motor insulation resistance.

  • Note: This feature protects the inverter, not humans.


E 15

Input over-voltage

Cause: Input over-voltage detected after the inverter has been in Stop Mode for 100 seconds.


Remedy:

  • Check the main power supply voltage.

  • Wait for the voltage to stabilize.

  • Once the fault is cleared, the inverter can enter Run Mode again.


E 21

Inverter thermal trip

Cause: Inverter internal temperature is above the threshold. Thermal sensor detected excessive temperature of power devices.


Remedy:

  • Check if cooling fan is running.

  • Check for blocked air vents or heatsink dust.

  • Reduce ambient temperature.

  • Reduce carrier frequency or load.


E 30

Driver error

Cause: Internal inverter error at the safety protection circuit between CPU and main driver unit. Excessive electrical noise may be the cause.


Remedy:

  • Check proper grounding and noise suppression.

  • Cycle power.

  • If persistent, replace unit/board.


E 35

Thermistor error

Cause: Thermistor connected to terminals [6] and [L] has sensed temperature is too high.


Remedy:

  • Check motor temperature.

  • Check thermistor wiring and connection at terminals [6] and [L].

  • Verify thermistor settings.


E 37

Safety Stop

Cause: Safety stop signal is given.


Remedy:

  • Identify source of Safety Stop signal.

  • Reset the safety circuit.


E 60

Communications error

Cause: The inverter’s watchdog timer for the communications network has timed out.


Remedy:

  • Check communication cables and connections.

  • Check master controller status.

  • Verify baud rate and communication settings.


- - -

Under-voltage (brownout) with output shutoff

Cause: Low input voltage caused the inverter to turn OFF output and try to restart. If restart fails, this alarm trips.


Remedy:

  • Check power supply stability.

  • Check for voltage sags or brownouts on the line.

  • Press Stop/Reset to clear if power is restored.


How to Clear & Reset Hitachi X200 Drive Faults

  1. Keypad Reset: Press the red STOP/RESET key on the front integrated keypad. For thermal overload (E05) or severe overcurrent trips (E01–E04), allow approximately 10 seconds before clearing to permit internal power module cooling.
  2. Intelligent Terminal Reset (RS): Pulse the digital input terminal assigned to function 18 [RS] (Reset) (configured via parameters C001–C005) for at least 12 ms, then release/open the circuit.
  3. Run Command Interlock Check: Confirm that the Run command (terminal [FW] or [RV]) is turned OFF before initiating a reset; clearing a fault with an active Run command will trigger an instant start or trip the inverter on E13 (USP – Unattended Start Protection).
  4. Modbus RTU RS-485 Communication: Write a trip reset command bit across the embedded RS-485 Modbus serial line from your PLC, HMI, or remote controller.
  5. Main Power Cycle: Switch off the primary AC power supply, wait at least 5 minutes until the Power LED / Charge indicator completely turns off (ensuring DC bus filter capacitors are fully discharged), and then restore mains power.
⚠️ High-Voltage Electrical Safety Warning: Hazardous residual electrical energy remains stored in the DC bus capacitors even after the AC line power has been disconnected. Wait a minimum of five (5) minutes after disconnecting power, and verify with a calibrated DC voltmeter that voltage between terminals [+1] / [P] and [-] / [N] has dropped below 50VDC before removing front covers, inspecting motor leads, or touching terminals U, V, and W.