Hitachi X200 Drive Fault Codes & Diagnostic Guide
Comprehensive fault code reference directory, trip alarm causes, and step-by-step diagnostic procedures for the Hitachi X200 series compact micro-inverter. Search or filter through the complete fault code directory below.
Power Range
0.2 – 7.5 kW (0.25 – 10 HP)
Supply Voltage
200–240V / 380–480V (1/3-Phase)
Control Modes
V/f Control & Auto Energy Saving
Operator Interface
Integrated LED Display & Potentiometer
Complete Hitachi X200 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type E01, E07, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| E 01 Over-current event while at constant speed | Cause: The inverter output was short-circuited, or the motor shaft is locked or has a heavy load. The dual-voltage motor is wired incorrectly. Remedy:
|
| E 02 Over-current event during deceleration | Cause: Excessive current detected during deceleration. Inverter output short-circuited, motor locked, or heavy load. Remedy:
|
| E 03 Over-current event during acceleration | Cause: Excessive current detected during acceleration. Inverter output short-circuited, motor locked, or heavy load. Remedy:
|
| E 04 Over-current event during other conditions | Cause: Excessive current detected during conditions other than constant speed, accel, or decel. Remedy:
|
| E 05 Overload protection | Cause: Motor overload detected by the electronic thermal function. The inverter trips to protect the motor. Remedy:
|
| E 07 Over-voltage protection | Cause: The DC bus voltage exceeds a threshold, often due to regenerative energy from the motor (acting as a generator). Remedy:
|
| E 08 EEPROM error | Cause: Built-in EEPROM memory has problems due to electrical noise or excessive temperature. Remedy:
|
| E 09 Under-voltage error | Cause: Decrease of internal DC bus voltage below threshold (Control circuit fault). Can generate excessive motor heat or low torque. Remedy:
|
| E 11 CPU error | Cause: A malfunction in the built-in CPU has occurred. Remedy:
|
| E 12 External trip | Cause: A signal on an intelligent input terminal configured as EXT (External Trip) has occurred. Remedy:
|
| E 13 USP (Unattended Start Protection) | Cause: Power was applied while a Run signal was already present (and USP is enabled). Remedy:
|
| E 14 Ground fault | Cause: Ground fault detected between the inverter output and the motor during powerup tests. Remedy:
|
| E 15 Input over-voltage | Cause: Input over-voltage detected after the inverter has been in Stop Mode for 100 seconds. Remedy:
|
| E 21 Inverter thermal trip | Cause: Inverter internal temperature is above the threshold. Thermal sensor detected excessive temperature of power devices. Remedy:
|
| E 30 Driver error | Cause: Internal inverter error at the safety protection circuit between CPU and main driver unit. Excessive electrical noise may be the cause. Remedy:
|
| E 35 Thermistor error | Cause: Thermistor connected to terminals [6] and [L] has sensed temperature is too high. Remedy:
|
| E 37 Safety Stop | Cause: Safety stop signal is given. Remedy:
|
| E 60 Communications error | Cause: The inverter’s watchdog timer for the communications network has timed out. Remedy:
|
| - - - Under-voltage (brownout) with output shutoff | Cause: Low input voltage caused the inverter to turn OFF output and try to restart. If restart fails, this alarm trips. Remedy:
|
How to Clear & Reset Hitachi X200 Drive Faults
- Keypad Reset: Press the red STOP/RESET key on the front integrated keypad. For thermal overload (E05) or severe overcurrent trips (E01–E04), allow approximately 10 seconds before clearing to permit internal power module cooling.
- Intelligent Terminal Reset (RS): Pulse the digital input terminal assigned to function 18 [RS] (Reset) (configured via parameters C001–C005) for at least 12 ms, then release/open the circuit.
- Run Command Interlock Check: Confirm that the Run command (terminal [FW] or [RV]) is turned OFF before initiating a reset; clearing a fault with an active Run command will trigger an instant start or trip the inverter on E13 (USP – Unattended Start Protection).
- Modbus RTU RS-485 Communication: Write a trip reset command bit across the embedded RS-485 Modbus serial line from your PLC, HMI, or remote controller.
- Main Power Cycle: Switch off the primary AC power supply, wait at least 5 minutes until the Power LED / Charge indicator completely turns off (ensuring DC bus filter capacitors are fully discharged), and then restore mains power.
⚠️ High-Voltage Electrical Safety Warning:
Hazardous residual electrical energy remains stored in the DC bus capacitors even after the AC line power has been disconnected. Wait a minimum of five (5) minutes after disconnecting power, and verify with a calibrated DC voltmeter that voltage between terminals [+1] / [P] and [-] / [N] has dropped below 50VDC before removing front covers, inspecting motor leads, or touching terminals U, V, and W.