Nidec Control Techniques Commander SE Fault Codes & Troubleshooting Guide
Complete trip code diagnostic directory, root cause analysis, and step-by-step troubleshooting procedures for the Nidec Control Techniques Commander SE AC drive series. Search or filter through the complete fault code list below.
Power Range
0.25 – 37 kW (0.33 – 50 HP)
Supply Voltage
200–240V / 380–480V (1Ø / 3Ø)
Control Modes
Open Loop Vector & V/Hz Control
Operator Interface
Integrated LED Keypad & Display
Complete Nidec Control Techniques Commander SE Trip Directory
Use the search box in the table below to quickly find your trip code (e.g., type OI.AC, OV, th, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| UU (1) DC link under voltage | Cause: Low AC supply voltage. Low DC link voltage when supplied by external DC power supply. Remedy: Check power supply voltage. |
| OU (2) DC link over voltage | Cause: Excessive inertia in the machine during deceleration. Deceleration rate set too fast for inertia of machine. Remedy: Adjust deceleration ramp times. Check for overvoltage trip levels (200V units: 420VDC, 400V units: 830VDC). |
| OI.AC** (3) AC instantaneous over current trip | Cause: Insufficient ramp times. Phase to phase or phase to earth short-circuit at the Drive output. Remedy: Drive requires autotuning to motor (see parameter 38). Note: These trips cannot be reset for 10 seconds. |
| OI.br** (4) Overcurrent on braking IGBT | Cause: Excessive current in braking resistor. Braking resistor value too small (Does not apply to Size 1 units). Remedy: Check braking resistor values. Note: These trips cannot be reset for 10 seconds. |
| Et (6) External trip | Cause: External trip terminal opened (when programmed). Remedy: Check external circuit connected to trip terminal. |
| O.SP (7) Over speed | Cause: Excessive motor speed (typically caused by the mechanical load driving the motor). Remedy: Check mechanical load conditions. |
| tunE (18) Auto-tune failure | Cause: Motor loaded or no motor connected. Remedy: Ensure motor is connected and free to rotate if necessary. |
| It.br (19) I x t on braking resistor | Cause: Excessive braking resistor energy (Does not apply to Size 1 units). Remedy: Check braking cycles and resistor sizing. |
| It.AC (20) Motor overload on current x time | Cause: Too much mechanical load. Remedy: Reduce mechanical load or check motor sizing. |
| Oht1 (21) Overheat | Cause: Overheat thermal model. Remedy: Check drive ventilation and ambient temperature. |
| Oht2 (22) Overheat (heatsink thermistor) | Cause: Temperature exceeds 95°C (203°F). Remedy: Check heatsink cooling and fans. |
| th (24) Over temperature (Motor thermistor) | Cause: Excessive motor temperature. Remedy: Check motor cooling and load. |
| O.Ld1* (26) +24V or digital output overload | Cause: Excessive load or short circuit on +24V output. Remedy: Check wiring on +24V output. The Enable/Reset terminal will not reset an O.Ld1 trip. Use the Stop/Reset key. |
| cL (28) Current loop loss on terminal 5 | Cause: Input current less than 3mA when 4-20 or 20-4 modes used. Remedy: Check current loop signal source and wiring. |
| SCL (30) User serial communications watchdog failure | Cause: Failure of serial communications between Drive and master. Remedy: Check serial communication cables and master status. |
| EEF (31) Failure of internal EEPROM | Cause: Possible loss of parameter values. Corruption due to severe electrical noise. Remedy: Set default parameters (see parameter 29). |
| PH (32) Phase loss | Cause: One of the input phases has become disconnected from the Drive. (This applies to 200V/400V three phase units only, not dual rated units). Remedy: Check input supply fuses and wiring. |
| rS (33) Stator resistance measurement failure | Cause: Motor cable disconnected during measurement. Motor too small for Drive. Remedy: See parameter 38 for more details. |
| trxx (40-99) User trips | Cause: User trips where xx is the user trip number. Remedy: Check user program or PLC logic generating the trip. |
| F.bus (180) Field bus disconnection | Cause: Field bus disconnection whilst in use. Remedy: Check field bus cables and connections. |
| C.Err (182) Quickey memory corrupt | Cause: Bad connection or memory corrupt. Remedy: Check Quickey insertion or replace Quickey. |
| C.dat (183) Quickey with no data | Cause: New / empty Quickey being read. Remedy: Program Quickey before reading. |
| C.Acc (185) Quickey write fail | Cause: Bad connection or faulty Quickey. Remedy: Re-insert or replace Quickey. |
| C.rtg (186) Quickey voltage rating change | Cause: Already programmed Quickey read by Drive of different rating. Remedy: Use Quickey compatible with drive rating. |
| O.Ld2 (188) +28V serial communications power supply overload | Cause: Overload of more than 110 mA or short circuit on +28V serial communications power supply. Remedy: Check serial comms wiring for shorts or excessive load. |
| O.cL (189) Current loop input overload | Cause: Input current exceeded 25mA. Remedy: Check current source signal level. |
| (No Code) Motor runs unstable | Cause: Motor or motor connections changed. Remedy: Check motor connections. Re-autotune Drive to motor (see parameter 38). |
How to Clear & Reset Nidec Control Techniques Commander SE Faults
- Keypad Reset: Press the red Stop / Reset (O) push button on the front control panel. Once the condition is rectified, the drive trip will clear and the display will show
InH(Inhibit) orrdy(Ready). - Digital Input Reset (Terminal 11): The default factory configuration assigns Terminal 11 as the Drive Enable / Reset input. Open and close the connection between Terminal 11 and +24V (Terminal 7/8) to clear active trips.
- SE Soft / CTSoft PC Tool: Connect your PC via the EIA-485 RJ45 communications port using the SE71 serial lead, open SE Soft / CTSoft, and click “Drive Reset” from the diagnostic toolbar.
- Serial / Fieldbus Communication: Toggle the trip reset bit in the serial control word (Pr 06.43 or assigned fieldbus control register via optional Profibus DP SE73, DeviceNet SE77, or Interbus SE74 modules).
- Mains Power Cycle: Switch off AC line supply power to the drive. Wait until the 7-segment LED display goes completely dark (minimum 5 minutes for internal DC link capacitors to discharge), then restore AC mains power.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [+DC] and [-DC] before opening terminal covers, checking dynamic braking resistors, or touching motor terminals U, V, and W on the Commander SE drive.