Nidec Control Techniques NE200 & NE300 Fault Codes & Diagnostic Guide
Complete trip alarm reference table, root causes, and diagnostic reset procedures for the Nidec Control Techniques NE200 compact and NE300 high-performance vector AC drive family. Search or filter through the complete trip list below.
Power Range
0.4 – 900 kW (0.5 – 1200 HP)
Supply Voltage
200–240V / 380–440V (1Ø / 3Ø)
Control Modes
Sensorless Vector, VC & V/Hz
Operator Interface
LED Keypad w/ Digital Potentiometer
Complete Nidec Control Techniques NE200 & NE300 Trip Directory
Use the search box in the table below to quickly find your trip code (e.g., type OC1, OU2, OL2, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| Uu1 Bus Under voltage during running | Cause: Power grid low voltage. Remedy:
|
| OC1 Over current in Acceleration | Cause: 1. Acceleration time too short. 2. Power grid low voltage. 3. Inverter power rating too small. Remedy:
|
| OC2 Over current in Deceleration | Cause: 1. Deceleration time too short. 2. Large load inertia. 3. Inverter power rating too small. Remedy:
|
| OC3 Over current at constant-speed | Cause: 1. Abnormal Load mutation. 2. Power grid low voltage. 3. Inverter power rating too small. 4. Encoder sudden offline in closed-loop vector control. Remedy:
|
| Ou1 Over Voltage in Acceleration | Cause: 1. Acceleration time too short. 2. Power supply abnormal. Remedy:
|
| Ou2 Over voltage in deceleration | Cause: 1. Deceleration time too short. 2. Large load inertia. Remedy:
|
| Ou3 Over voltage in constant speed | Cause: 1. Power supply abnormal. 2. Large load inertia. Remedy:
|
| GF (NE300 Only) Ground Fault | Cause: 1. One output phase got short circuit problem. Remedy:
|
| SC Load short-circuit | Cause: 1. Wiring of inverter and motor get phase-to-phase short circuit. 2. Damage of the inverting module IGBT. Remedy:
|
| OH1 Heat-sink over heat | Cause: 1. Ambient temperature too high. 2. Fan is damaged. 3. Fan air duct is blocked. Remedy:
|
| OL1 Motor overload | Cause: 1. Power supply abnormal. 2. Motor rated current set wrongly. 3. The Curve of V/F is not fit. 4. Motor always works with heavy load at low speed. 5. Motor blocked to stall or sudden large load change. 6. Motor power too low. Remedy:
|
| OL2 Inverter overload | Cause: 1. Low voltage in power grid. 2. Load too heavy. 3. Acceleration too fast. 4. Restart the motor still in turning. Remedy:
|
| EF0 Communication fault | Cause: 1. Baud rate and parity checksum is set incorrect. 2. Communication interrupted for long time. Remedy:
|
| EF1 External terminal fault | Cause: 1. Faults comes from external control circuit. Remedy:
|
| SP1 Input phase loss | Cause: 1. Input R,S,T have phase loss or imbalance. Remedy:
|
| SPO Output phase loss | Cause: 1. There is lack of U,V,W when output. 2. There is a serious unbalance in output. Remedy:
|
| EEP EEPROM error | Cause: 1. Function code parameter writing error. 2. EEPROM damaged. Remedy:
|
| CCF Keypad & control board communication interrupted | Cause: 1. Connection cable between keyboard and control panel is broken. Remedy:
|
| bCE Brake unit fault | Cause: 1. The braking line or braking pipe is broken. 2. Brake resistor is too lower. Remedy:
|
| PCE Parameter copy Error | Cause: 1. Too long connection cable between keypad and control board leads to interference in parameters transmission. 2. The downloading parameters do not match the existed parameters in the inverter. Remedy:
|
| IDE IDE Hall current detection fault | Cause: 1. The current sensoring or hall device get damaged. Remedy:
|
| ECE (NE300 Only) Encoder fault | Cause: 1. Encoder signal wires are connected reversely. 2. Encoder signal wires get damaged. 3. Encoder damaged. 4. Dual-way encoder detected motor direction is not match. Remedy:
|
| LC Fast current limit fault | Cause: 1. Load too large or motor blocked to stall. 2. Inverter power rating too small. 3. Inverter output circuit loop grounded or SC. Remedy:
|
| EF2 Terminal close fault | Cause: 1. The FWD or REV terminals close and get power on. But inverter is set to not allow the restart after power failure recovery. Remedy:
|
| PIDE PID feedback error | Cause: 1. PID feedback offline. Remedy:
|
| OLP2 Overload pre-alarm error | Cause: 1. Frequency inverter output current is higher than set pre-alarm threshold. Remedy:
|
How to Clear & Reset Nidec Control Techniques NE200 & NE300 Faults
- Keypad Reset: Press the red STOP / RESET key on the front LED operation panel. Once the underlying fault condition is resolved, the trip indicator will clear and the display will return to normal stop status.
- Digital Input Reset (Terminal X1–X6): Configure any multi-function digital input terminal (parameters F1.00 to F1.05) to function code 9 (Fault Reset). Pulse this terminal high relative to COM to clear active alarms remotely.
- Diagnostic Parameter Verification: Access parameter group FA (Fault Records) via the keypad. Inspect parameter FA.00 (Most recent fault code), FA.01 (Frequency at trip), and FA.02 (Output current at trip) to confirm root causes before resetting.
- Modbus RTU Reset (RS485): Send the fault reset bit command via the integrated RS485 communication port using standard Modbus RTU communication control registers.
- AC Mains Power Cycle: Turn off main incoming AC line power. Wait until the LED display and cooling fans turn off completely (approx. 5 minutes for intermediate DC capacitors to safely discharge), then re-apply power.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [(+)] and [(-)] or [(+)] and [PB] before touching terminals U, V, and W, checking dynamic braking resistors, or servicing motor cabling on the NE200 & NE300 drive.