L&T Drives Fault Codes & Troubleshooting
Complete diagnostic database for 2 L&T drive series (CX2000 & SX2000). Browse fault codes, alarms, causes, and step-by-step fixes for industrial AC variable frequency drives. Select your drive model series below to access parameter checks, root cause analysis, and physical inspection workflows.
2 AC Inverter Series
2 Total Series
L&T AC Variable Frequency Drives
2 Models
CX2000
→
Compact General Purpose AC Drive for Pumps, Fans, Conveyors & OEM Machinery
SX2000
→
Heavy-Duty Sensorless Vector Control Inverter with 200% Starting Torque at 0.5 Hz
Most Common L&T Drive Fault Codes
Diagnostic Quick Reference| Fault Code | LCD Keypad Name | Fault Name | Common Root Cause |
|---|---|---|---|
| OCt / OC1 | Over Current | Overcurrent Trip | Output current exceeded rated limit; acceleration ramp too aggressive, mechanical binding, or motor phase short circuit. |
| OVt / OV | Over Voltage | DC Link Overvoltage | Intermediate DC bus exceeded maximum threshold during motor deceleration; verify deceleration ramp or dynamic brake unit (DBU/DBR). |
| LUt / UV | Low Voltage | Undervoltage Trip | DC link voltage dropped below operating threshold; mains power sag, blown line-side fuse, or loose incoming terminal connections. |
| OLt | Over Load | Drive Overload | Continuous motor load exceeded drive current rating; mechanical jam or undersized drive for the application profile. |
| ETH | Elec-Thermal | Motor Thermal Trip | Motor electronic thermal protection activated (I²t calculation); prolonged low-speed operation without forced motor cooling. |
| OHt / OHT | Over Heat | Inverter Heatsink Overheat | Cooling fan failure, obstructed cooling air passage, or panel ambient temperature exceeding recommended limits (>50°C). |
| GFt / GFT | Ground Fault | Ground / Earth Fault | Earth leakage current detected on motor output terminals U, V, or W; damaged motor cable jacket or degraded stator insulation. |
| COL | Phase Open | Input Phase Loss | One of the incoming 3-phase supply lines (R, S, T) is disconnected, blown fuse, or unbalanced utility line voltage (>3%). |
How to Clear & Reset L&T Faults
- Keypad Reset: Press the red STOP/RST key directly on the front LED or LCD digital operator panel after resolving the fault condition.
- Multi-Function Input Terminal: Trigger the digital input terminal configured for external fault reset (e.g., configure multi-function terminal parameter IN-65 to IN-71 to
RST / Reseton the SX2000). - Communication Reset: Write a fault reset bit via Modbus RS485 communication command register.
- Power Disconnect Cycle: Turn off incoming 3-phase AC mains power, wait until the internal charge indicator LED turns completely dark (minimum 5 minutes), and re-energize the unit.
⚠️ High-Voltage Safety Warning:
Hazardous residual electrical energy remains stored in the intermediate DC bus capacitors even after turning off the main power supply. Always measure with a calibrated DC voltmeter across terminals (+/B1) and (-) to confirm the voltage is strictly below 30VDC before inspecting internal terminals or power cables.