INVT GD20-UL Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the INVT Goodrive20-UL (GD20-UL) series compact vector inverter. Search or filter through the complete fault code directory below.

UL & cUL Certified Vector VFD Power: 0.4 to 2.2 kW (0.5 to 3.0 HP) DIN-Rail & Wall Mountable
Power Range 0.4 – 2.2 kW (0.5 – 3 HP)
Supply Voltage 115V / 230V / 460V AC
Control Modes SVPWM & Sensorless Vector (SVC)
Operator Interface Membrane / External LED Keypad

Complete INVT GD20-UL Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OC1, OV3, OL1, or Overcurrent).

Fault Code and MeaningCause and Remedy
OUt1
[1] Inverter unit U phase protection

Cause:
The acceleration is too fast; IGBT module fault; Misacts caused by interference; Connection of driving wires is not good; Grounding is improper.



Remedy:

  • Increase ACC time.

  • Change the power unit.

  • Check the driving wires.

  • Inspect external equipment and eliminate interference.


OUt2
[2] Inverter unit V phase protection

Cause:
The acceleration is too fast; IGBT module fault; Misacts caused by interference; Connection of driving wires is not good; Grounding is improper.



Remedy:

  • Increase ACC time.

  • Change the power unit.

  • Check the driving wires.

  • Inspect external equipment and eliminate interference.


OUt3
[3] Inverter unit W phase protection

Cause:
The acceleration is too fast; IGBT module fault; Misacts caused by interference; Connection of driving wires is not good; Grounding is improper.



Remedy:

  • Increase ACC time.

  • Change the power unit.

  • Check the driving wires.

  • Inspect external equipment and eliminate interference.


OC1
[4] Overcurrent during acceleration

Cause:
The acceleration is too fast; Grid voltage too low; VFD power too low; Load transients/abnormal; Grounding short circuit or output phase loss; Strong external interference; Overvoltage stall protection not open.



Remedy:

  • Increase the ACC time.

  • Check the input power.

  • Select VFD with larger power.

  • Check if load is short circuited (grounding or wire) or rotation is not smooth.

  • Check output configuration.

  • Check if there is strong interference.

  • Check the setting of relative function codes.


OC2
[5] Overcurrent during deceleration

Cause:
The deceleration is too fast; Grid voltage too low; VFD power too low; Load transients/abnormal; Grounding short circuit or output phase loss; Strong external interference; Overvoltage stall protection not open.



Remedy:

  • Increase the deceleration time.

  • Check the input power.

  • Select VFD with larger power.

  • Check if load is short circuited (grounding or wire) or rotation is not smooth.

  • Check output configuration.

  • Check if there is strong interference.

  • Check the setting of relative function codes.


OC3
[6] Overcurrent during constant speed running

Cause:
Grid voltage too low; VFD power too low; Load transients/abnormal; Grounding short circuit or output phase loss; Strong external interference.



Remedy:

  • Check the input power.

  • Select VFD with larger power.

  • Check if load is short circuited (grounding or wire) or rotation is not smooth.

  • Check output configuration.

  • Check if there is strong interference.


OV1
[7] Overvoltage during acceleration

Cause:
Input voltage is abnormal; Large energy feedback; No braking components; Braking energy is not open.



Remedy:

  • Check the input power.

  • Check if DEC time is too short.

  • Check if VFD starts during motor rotation.

  • Increase energy consumption components.

  • Install braking components.

  • Check the setting of relative function codes.


OV2
[8] Overvoltage during deceleration

Cause:
Input voltage is abnormal; Large energy feedback; No braking components; Braking energy is not open.



Remedy:

  • Check the input power.

  • Check if DEC time is too short.

  • Check if VFD starts during motor rotation.

  • Increase energy consumption components.

  • Install braking components.

  • Check the setting of relative function codes.


OV3
[9] Overvoltage during constant speed running

Cause:
Input voltage is abnormal; Large energy feedback; No braking components; Braking energy is not open.



Remedy:

  • Check the input power.

  • Install braking components.

  • Check the setting of relative function codes.


UV
[10] Bus undervoltage

Cause:
The voltage of the power supply is too low; The overvoltage stall protection is not open.



Remedy:

  • Check the input power of the supply line.

  • Check the setting of relative function codes.


OL1
[11] Motor overload

Cause:
Power supply voltage too low; Motor rated current setting incorrect; Motor stall or load transients too strong.



Remedy:

  • Check the power of the supply line.

  • Reset the rated current of the motor.

  • Check the load and adjust the torque lift.


OL2
[12] VFD overload

Cause:
Acceleration too fast; Resetting rotating motor; Power supply voltage too low; Load too heavy; Close loop vector control reverse direction/long low-speed operation.



Remedy:

  • Increase the ACC time.

  • Avoid restarting after stopping.

  • Check the power of the supply line.

  • Select a VFD with bigger power.

  • Select a proper motor.


SPI
[13] Phase loss on input side

Cause:
Phase loss or fluctuation of input R,S,T.



Remedy:

  • Check input power.

  • Check installation distribution.


SPO
[14] Phase loss on output side

Cause:
U,V,W phase loss input (or serious asymmetrical three phase of the load).



Remedy:

  • Check the output distribution.

  • Check the motor and cable.


OH1
[15] Rectifier module overheat

Cause:
Air duct jam or fan damage; Ambient temperature is too high; The time of overload running is too long.



Remedy:

  • Dredge the vent duct or replace the fan.

  • Lower the ambient temperature.


OH2
[16] Inverter module overheat

Cause:
Air duct jam or fan damage; Ambient temperature is too high; The time of overload running is too long.



Remedy:

  • Dredge the vent duct or replace the fan.

  • Lower the ambient temperature.


EF
[17] External fault

Cause:
SI external fault input terminals action.



Remedy:

  • Check the external device input.


CE
[18] 485 communication fault

Cause:
Baud rate setting incorrect; Fault in communication wiring; Communication address wrong; Strong interference.



Remedy:

  • Set proper baud rate.

  • Check the communication connection distribution.

  • Set proper communication address.

  • Change or replace the connection distribution or improve anti-interference capability.


ItE
[19] Current detection fault

Cause:
Control panel connector poor contact; Exception on the magnifying circuit.



Remedy:

  • Check the connector and re-plug.

  • Change the main control panel.


tE
[20] Motor autotuning fault

Cause:
Motor capacity not compatible with VFD; Rated parameter of motor not set correctly; Offset parameters huge; Autotune overtime.



Remedy:

  • Change the VFD mode.

  • Set the rated parameter according to the motor name plate.

  • Empty the motor load.

  • Check the motor connection.

  • Check if the upper limit frequency is above 2/3 of rated frequency.


EEP
[21] EEPROM operation fault

Cause:
Error of controlling the write and read of parameters; Damage to EEPROM.



Remedy:

  • Press STOP/RST to reset.

  • Change the main control panel.


PIDE
[22] PID feedback offline fault

Cause:
PID feedback offline; PID feedback source disappear.



Remedy:

  • Check the PID feedback signal.

  • Check the PID feedback source.


bCE
[23] Braking unit fault

Cause:
Braking circuit fault or damage to braking pipes; External braking resistor not sufficient.



Remedy:

  • Check the braking unit and change new braking pipe.

  • Increase the braking resistor.


END
[24] Running time reached

Cause:
The actual running time of the VFD is above the internal setting running time.



Remedy:

  • Ask for the supplier and adjust the setting running time.


OL3
[25] Electronic overload

Cause:
The VFD will report overload pre-alarm according to the set value.



Remedy:

  • Check the load and the overload pre-alarm point.


PCE
[26] Keypad communication error

Cause:
Keypad not in good connection or offline; Keypad cable too long or strong interference; Keypad/Main board circuit fault.



Remedy:

  • Check the keypad cable and ensure it is normal.

  • Check the environment and eliminate the interference source.

  • Change hardware and ask for maintenance service.


UPE
[27] Parameter upload error

Cause:
Keypad not in good connection or offline; Keypad cable too long or strong interference; Communication circuit fault.



Remedy:

  • Check the environment and eliminate the interference source.

  • Change hardware and ask for maintenance service.


DNE
[28] Parameter download error

Cause:
Keypad not in good connection or offline; Keypad cable too long/interference; Data storage error in keypad.



Remedy:

  • Check the environment and eliminate the interference source.

  • Change hardware and ask for maintenance service.

  • Backup data in the keypad again.


ETH1
[32] To-ground short-circuit fault 1

Cause:
Output of VFD is short circuited with ground; Fault in current detection circuit; Great difference between motor power setting and VFD power.



Remedy:

  • Check if the connection of the motor is normal or not.

  • Change the hall.

  • Change the main control panel.

  • Reset the correct motor parameter.


ETH2
[33] To-ground short-circuit fault 2

Cause:
Output of VFD is short circuited with ground; Fault in current detection circuit; Great difference between motor power setting and VFD power.



Remedy:

  • Check if the connection of the motor is normal or not.

  • Change the hall.

  • Change the main control panel.

  • Reset the correct motor parameter.


dEu
[34] Speed deviation fault

Cause:
Load is too heavy, or stall occurred.



Remedy:

  • Check the load to ensure it is proper, increase the detection time.

  • Check whether control parameters are set properly.


STo
[35] Mal-adjustment fault

Cause:
Control parameters of synchronous motor are set improperly; Autotuning parameter inaccurate; VFD not connected to motor.



Remedy:

  • Check the load to ensure it is proper.

  • Check whether control parameters are set correctly.

  • Increase maladjustment detection time.


LL
[36] Electronic underload fault

Cause:
The VFD will report the underload pre-alarm according to the set value.



Remedy:

  • Check the load and the underload pre-alarm point.


PoFF
System power off

Cause:
System power off or low DC voltage.



Remedy:

  • Check the grid.


How to Clear & Reset INVT GD20-UL Drive Faults

  1. Keypad Reset: Press the red STOP/RST key on the integrated membrane keypad or connected external LED keypad. During a fault trip, this key directly clears active trip codes.
  2. Digital Input Reset (DI): If assigned in parameter group P05 (P05.01–P05.04 set to Function 4: Fault Reset), momentarily short the designated digital terminal (S1–S4 to COM) to clear the fault.
  3. RS-485 Modbus RTU: Send a reset bit command to communication control register 2000H over the built-in serial communication interface (485+ / 485-).
  4. Power Cycle: Disconnect main AC line power, wait until the internal DC bus capacitor discharges completely (wait at least 5 minutes until the LED display and power indicator are fully unlit), and restore power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 36VDC across main terminals (+) and (-) [or PB and (-)] before touching any input/output power terminals (R, S, T / L, N and motor terminals U, V, W). Wait at least 5 minutes after cutting input power to allow internal capacitors to safely discharge.