INVT GD300-21 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the INVT Goodrive300-21 (GD300-21) dual-inverter integrated air compressor drive series. Search or filter through the complete fault code directory below.
Power Range
7.5 – 110 kW (10 – 150 HP)
Supply Voltage
3PH 380–440V / 3PH 220–240V AC
Control Modes
Dual SVC & V/F (AM & PM Motors)
Operator Interface
Compressor Touchscreen HMI / LED
Complete INVT GD300-21 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type OUt1, OC1, or OV2).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| OUT1 [1] Inverter unit U-phase protection | Cause: ACC is too fast. IGBT module is damaged. Misacts caused by interference. Drive wires are poorly connected. To-ground short circuit occurs. Remedy:
|
| OUT2 [2] Inverter unit V-phase protection | Cause: (See OUT1 causes). Remedy:
|
| OUT3 [3] Inverter unit W-phase protection | Cause: (See OUT1 causes). Remedy:
|
| OV1 [7] Overvoltage during acceleration | Cause: Exception occurred to input voltage. Large energy feedback. Remedy:
|
| OV2 [8] Overvoltage during deceleration | Cause: Exception occurred to input voltage. Large energy feedback. Remedy:
|
| OV3 [9] Overvoltage during constant speed running | Cause: Exception occurred to input voltage. Large energy feedback. Remedy:
|
| OC1 [4] Overcurrent during acceleration | Cause: ACC/DEC is too fast. The voltage of the grid is too low. Inverter power is too small. Load transient or exception occurred. To-ground short circuit or output phase loss occurred. Strong external interference sources. Remedy:
|
| OC2 [5] Overcurrent during deceleration | Cause: (See OC1 causes). Remedy:
|
| OC3 [6] Overcurrent during constant speed running | Cause: (See OC1 causes). Remedy:
|
| UV [10] Bus undervoltage fault | Cause: The voltage of the grid is too low. Remedy:
|
| OL1 [11] Motor overload | Cause: The grid voltage is too low. The motor rated current is set incorrectly. The motor stall occurs or the load transient is too large. Remedy:
|
| OL2 [12] Inverter overload | Cause: ACC is too fast. The motor in rotating is restarted. The voltage of the grid is too low. Load is too large. Remedy:
|
| SPI [13] Phase loss on input side | Cause: Phase loss or violent fluctuation occurred on input R, S, T. Remedy:
|
| SPO [14] Phase loss on output side | Cause: Phase loss occurred to U, V, W output (or the three phases of motor is asymmetrical). Remedy:
|
| OH1 [15] Rectifier module overheating | Cause: Air duct is blocked or fan is damaged. Ambient temperature is too high. Long-time overload running. Remedy:
|
| OH2 [16] Inverter module overheat | Cause: Air duct is blocked or fan is damaged. Ambient temperature is too high. Long-time overload running. Remedy:
|
| EF [17] External fault | Cause: S external faulty input terminal action. Remedy:
|
| CE [18] RS485 communication fault | Cause: Baud rate is set improperly. Communication line fault. Incorrect communication address. Communication suffers from strong interference. Remedy:
|
| ItE [19] Current detection fault | Cause: Poor contact of the connector of control board. Hall component is damaged. Exception occurred to amplification circuit. Remedy:
|
| tE [20] Motor autotuning fault | Cause: The motor capacity does not match the inverter capacity. Motor parameter is set improperly. The parameters gained from autotuning deviate sharply from the standard parameters. Autotuning timeout. Remedy:
|
| EEP [21] EEPROM operation fault | Cause: Error in reading or writing control parameters. The EEPROM is damaged. Remedy:
|
| PIDE [22] PID feedback offline fault | Cause: PID feedback offline. PID feedback source disappears. Remedy:
|
| END [24] Running time reached | Cause: The actual running time of the inverter is longer than the internal set running time. Remedy:
|
| OL3 [25] Electronic overload fault | Cause: The inverter reports overload pre-alarm according to the setting. Remedy:
|
| PCE [26] Keypad communication fault | Cause: Keypad cable connected improperly or disconnected. Keypad cable too long, causing strong interference. Keypad or mainboard communication circuit error. Remedy:
|
| UPE [27] Parameter upload error | Cause: Keypad cable connected improperly or disconnected. Keypad cable too long, causing strong interference. Keypad or mainboard communication circuit error. Remedy:
|
| DNE [28] Parameter download error | Cause: Keypad cable connected improperly or disconnected. Keypad cable too long, causing strong interference. Data storage error occurred to the keypad. Remedy:
|
| ETH1 [32] To-ground short-circuit fault 1 | Cause: Inverter output is short connected to the ground. There is a fault in the current detection circuit. Remedy:
|
| ETH2 [33] To-ground short-circuit fault 2 | Cause: Inverter output is short connected to the ground. There is a fault in the current detection circuit. Remedy:
|
| dEu [34] Speed deviation fault | Cause: The load is too heavy or stalled. Remedy:
|
| STo [35] Mal-adjustment fault | Cause: SM control parameters are set incorrectly. Autotuned parameters are not accurate. The inverter is not connected to the motor. Remedy:
|
| LL [36] Electronic underload fault | Cause: The inverter reports underload pre-alarm according to the setting. Remedy:
|
| E_FAN [37] Auxiliary fan fault | Cause: The fan inverter is in fault. Remedy:
|
| PSF [38] Phase sequence fault | Cause: The phase sequence on the input side of the power is negative. Remedy:
|
| Communication interruption | Cause: RS485 communication port is disconnected. Remedy:
|
| L-AUP [44] Low auxiliary pressure fault | Cause: Auxiliary pressure is too low at start-up. Remedy:
|
| HAnd [45] Handshake failure | Cause: The handshake process timeout. Remedy:
|
How to Clear & Reset INVT GD300-21 Drive Faults
- HMI / Keypad Reset: Press the Reset soft button on the air compressor touchscreen HMI or press the red STOP/RST button on the internal keypad unit after resolving the trip condition.
- Digital Input Reset (DI): If programmed on the multi-function digital input terminal (S1–S3) for function 4 (Fault reset) in parameter group P05, pulse the terminal to remotely clear active fault latches.
- RS485 Communication Reset: Send a reset control command over the RS485 communication line by writing command bit
0007Hto control address 2000H. - Dual-Stage Diagnostic Inspection: Check parameters P07.27 to P07.32 for the past 6 fault records and P07.33 to P07.56 to examine main motor vs. cooling fan motor current, DC bus voltage, and discharge temperature (PT100 feedback) logged at trip time.
- Power Cycle: Disconnect the incoming 3-phase AC power. Wait until the touchscreen HMI turns off and internal DC bus capacitors completely discharge (minimum 5 minutes) before restoring mains power.
⚠️ High-Voltage Electrical Safety Warning:
Always disconnect incoming 3-phase mains AC power and wait at least 5 minutes before inspecting terminal connections. Use a calibrated digital multimeter to verify intermediate DC bus voltage across terminals (+) and (-) [or (P+) and (-)] is below 36VDC before servicing power output terminals for both the main compressor motor (U1, V1, W1) and oil-cooling fan motor (U2, V2, W2).