INVT GD350-UL Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the INVT Goodrive350-UL (GD350-UL) high-performance multi-function VFD series. Search or filter through the complete fault code directory below.

UL & cUL Certified Multi-Function VFD Power: 0.75 to 500 kW (1 to 670 HP) Built-in Safe Torque Off (STO SIL2/SIL3)
Power Range 0.75 – 500 kW (1 – 670 HP)
Supply Voltage 230V / 460V / 575V AC (3-Phase)
Control Modes SVPWM, SVC & Closed-Loop VC
Operator Interface Standard LCD Keypad / Mobile App

Complete INVT GD350-UL Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OC1, OV2, ItE, or Overcurrent).

Fault Code and MeaningCause and Remedy
OUt1
VFD unit Phase-U protection

Cause:
Acceleration is too fast; IGBT module is damaged; Misacts caused by interference; drive wires are poorly connected; To-ground short circuit.



Remedy:

  • Increase acceleration time.

  • Replace the power unit.

  • Check drive wires.

  • Check whether there is strong interference surrounds the peripheral equipment.


OUt2
VFD unit Phase-V protection

Cause:
Acceleration is too fast; IGBT module is damaged; Misacts caused by interference; drive wires are poorly connected; To-ground short circuit.



Remedy:

  • Increase acceleration time.

  • Replace the power unit.

  • Check drive wires.

  • Check whether there is strong interference surrounds the peripheral equipment.


OUt3
VFD unit Phase-W protection

Cause:
Acceleration is too fast; IGBT module is damaged; Misacts caused by interference; drive wires are poorly connected; To-ground short circuit.



Remedy:

  • Increase acceleration time.

  • Replace the power unit.

  • Check drive wires.

  • Check whether there is strong interference surrounds the peripheral equipment.


OV1
Over-voltage during acceleration

Cause:
Exception occurred to input voltage; Large energy feedback; Lack of brake units; Dynamic brake is not enabled.



Remedy:

  • Check input power.

  • Check whether load deceleration time is too short.

  • Check if the motor starts during rotating.

  • Install dynamic brake units.

  • Check the setting of related function codes.


OV2
Over-voltage during deceleration

Cause:
Exception occurred to input voltage; Large energy feedback; Lack of brake units; Dynamic brake is not enabled.



Remedy:

  • Check input power.

  • Check whether load deceleration time is too short.

  • Check if the motor starts during rotating.

  • Install dynamic brake units.

  • Check the setting of related function codes.


OV3
Over-voltage during constant speed running

Cause:
Exception occurred to input voltage; Large energy feedback; Lack of brake units; Dynamic brake is not enabled.



Remedy:

  • Check input power.

  • Check whether load deceleration time is too short.

  • Check if the motor starts during rotating.

  • Install dynamic brake units.

  • Check the setting of related function codes.


OC1
Over-current during acceleration

Cause:
Acceleration is too fast; Grid voltage is too low; VFD power is too small; Load transient or exception occurred; To-ground short circuit or output phase loss occur; Strong external interference sources; Overvoltage stall protection is not enabled.



Remedy:

  • Increase acceleration/deceleration time.

  • Check input power.

  • Select the VFD with larger power.

  • Check if the load is short circuited (to-ground or line-to-line) or if rotation is not smooth.

  • Check the output wiring.

  • Check if there is strong interference.

  • Check the setting of related function codes.


OC2
Over-current during deceleration

Cause:
See OC1 causes (Accel too fast, Grid low, VFD power small, Load transient, Short circuit, Interference).



Remedy:

  • Increase acceleration/deceleration time.

  • Check input power.

  • Select the VFD with larger power.

  • Check if the load is short circuited (to-ground or line-to-line) or if rotation is not smooth.

  • Check the output wiring.

  • Check if there is strong interference.

  • Check the setting of related function codes.


OC3
Over-current during constant speed running

Cause:
See OC1 causes (Grid low, VFD power small, Load transient, Short circuit, Interference, Stall protection).



Remedy:

  • Check input power.

  • Select the VFD with larger power.

  • Check if the load is short circuited.

  • Check the output wiring.

  • Check if there is strong interference.

  • Check the setting of related function codes.


UV
Bus undervoltage fault

Cause:
Grid voltage is too low; Overvoltage stall protection is not enabled.



Remedy:

  • Check grid input power.

  • Check the setting of related function codes.


OL1
Motor overload

Cause:
Grid voltage is too low; Rated motor current is set improperly; Motor stall or load jumps violently.



Remedy:

  • Check grid voltage.

  • Reset rated motor current.

  • Check the load and adjust torque boost.


OL2
VFD overload

Cause:
Acceleration is too fast; The motor in rotating is restarted; Grid voltage is too low; Load is too large; Power is too small.



Remedy:

  • Increase acceleration time.

  • Avoid restart after stop.

  • Check grid voltage.

  • Select the VFD with larger power.

  • Select proper motor.


SPI
Phase loss on input side

Cause:
Phase loss or violent fluctuation occurred to R, S and T input.



Remedy:

  • Check the input power.

  • Check installation wiring.


SPO
Phase loss on output side

Cause:
Phase loss occurred to U, V, W output (or the three phases of motor is asymmetrical).



Remedy:

  • Check the output wiring.

  • Check the motor and cable.


OH1
Overheat of rectifier module

Cause:
Air duct is blocked or fan is damaged; Ambient temperature is too high; Long-time overload running.



Remedy:

  • Ventilate the air duct or replace the fan.

  • Lower the ambient temperature.


OH2
Overheat of VFD module

Cause:
Air duct is blocked or fan is damaged; Ambient temperature is too high; Long-time overload running.



Remedy:

  • Ventilate the air duct or replace the fan.

  • Lower the ambient temperature.


EF
External fault

Cause:
SI external fault input terminal acts.



Remedy:

  • Check external device input.


CE
485 communication fault

Cause:
Baud rate is set improperly; Communication line fault; Communication address error; Communication suffers from strong interference.



Remedy:

  • Set proper baud rate.

  • Check the wiring of communication interfaces.

  • Set proper communication address.

  • Replace or change the wiring to enhance anti-interference capacity.


ItE
Current detection fault

Cause:
Poor contact of the connector of control board; Hall component is damaged; Exception occurred to amplification circuit.



Remedy:

  • Check the connector and re-plug.

  • Replace the hall component.

  • Replace the main control board.


tE
Motor autotuning fault

Cause:
Motor capacity does not match with the VFD capacity (diff exceeds 5 power classes); Motor parameter is set improperly; The parameters gained from autotuning deviate sharply from standard; Autotuning timeout.



Remedy:

  • Change the VFD model, or adopt V/F mode for control.

  • Set proper motor type and nameplate parameters.

  • Empty the motor load and carry out autotuning again.

  • Check motor wiring and parameter setting.

  • Check whether upper limit frequency is larger than 2/3 of the rated frequency.


EEP
EEPROM fault

Cause:
R/W error occurred to the control parameters; EEPROM is damaged.



Remedy:

  • Press STOP/RST to reset.

  • Replace the main control board.


PIDE
PID feedback offline fault

Cause:
PID feedback offline; PID feedback source disappears.



Remedy:

  • Check PID feedback signal wires.

  • Check PID feedback source.


bCE
Brake unit fault

Cause:
Brake circuit fault or brake tube is damaged; The resistance of external brake resistor is too small.



Remedy:

  • Check the brake unit, replace with new brake tubes.

  • Increase brake resistance.


END
Running time is up

Cause:
The actual running time of the VFD is larger than the set running time.



Remedy:

  • Ask help from the supplier, adjust the set running time.


OL3
Electronic overload fault

Cause:
The VFD releases overload pre-alarm based on the set value.



Remedy:

  • Check the load and overload pre-alarm threshold.


PCE
Keypad communication fault

Cause:
The keypad wire is poorly contacted or disconnected; The keypad wire is too long and suffers strong interference; Circuit fault occurred to the keypad or communication part of the main board.



Remedy:

  • Check the keypad wires to confirm whether fault exists.

  • Check the surroundings to rule out interference source.

  • Replace the hardware and ask for maintenance service.


UPE
Parameter upload error

Cause:
The keypad wire is poorly contacted or disconnected; The keypad wire is too long and suffers strong interference; Circuit fault occurred to the keypad.



Remedy:

  • Check the surroundings to rule out interference source.

  • Replace the hardware and ask for maintenance service.


DNE
Parameter download error

Cause:
The keypad wire is poorly contacted/disconnected; The keypad wire is too long/suffers interference; Data storage error occurred to the keypad.



Remedy:

  • Check the surroundings to rule out interference source.

  • Replace the hardware and ask for maintenance service.

  • Re-backup keypad data.


ETH1
To-ground short circuit fault 1

Cause:
VFD output is short connected to the ground; Current detection circuit is faulty; Actual motor power setting deviates sharply from the VFD power.



Remedy:

  • Check whether motor wiring is proper.

  • Replace the hall component.

  • Replace the main control board.

  • Reset the motor parameters properly.


ETH2
To-ground short circuit fault 2

Cause:
VFD output is short connected to ground; Current detection circuit is faulty; Actual motor power setting deviates sharply from the VFD power.



Remedy:

  • Check whether motor wiring is proper.

  • Replace the hall component.

  • Replace the main control board.

  • Reset the motor parameters properly.


dEu
Speed deviation fault

Cause:
Load is too heavy, or stall occurred.



Remedy:

  • Check the load to ensure it is proper, increase the detection time.

  • Check whether control parameters are set properly.


STo
Maladjustment fault

Cause:
Control parameters of synchronous motor is set improperly; The parameter gained from autotuning is inaccurate; The VFD is not connected to motor.



Remedy:

  • Check the load to ensure it is proper.

  • Check whether control parameters are set correctly.

  • Increase maladjustment detection time.


LL
Electronic underload fault

Cause:
The VFD performs underload pre-alarm based on the set value.



Remedy:

  • Check the load and overload pre-alarm threshold.


ENC1O
Encoder offline fault

Cause:
Encoder line sequence is wrong, or signal wires are poorly connected.



Remedy:

  • Check the encoder wiring.


ENC1D
Encoder reversal fault

Cause:
The encoder speed signal is contrary to the motor running direction.



Remedy:

  • Reset encoder direction.


ENC1Z
Encoder Z pulse offline fault

Cause:
Z signal wires are disconnected.



Remedy:

  • Check the wiring of Z signal.


OT
Motor over-temperature

Cause:
Motor over-temperature input terminal is valid.



Remedy:

  • Check the wiring of motor over-temperature input terminal.


STO
Safe torque off

Cause: Safe torque off function is enabled by external forces.


Remedy:

  • / (System state, not necessarily a failure).


STL1
Exception occurred to safe circuit of channel H1

Cause:

  • The wiring of STO is improper.

  • Fault occurred to external switch of STO.

  • Hardware fault occurred to safety circuit of channel H1.




Remedy:

  • Check whether terminal wiring of STO is proper and firm enough.

  • Check whether external switch of STO can work properly.

  • Replace the control board.


STL2
Exception occurred to channel H2 safe circuit

Cause:

  • The wiring of STO is improper.

  • Fault occurred to external switch of STO.

  • Hardware fault occurred to safety circuit of channel H2.




Remedy:

  • Check whether terminal wiring of STO is proper and firm enough.

  • Check whether external switch of STO can work properly.

  • Replace the control board.


STL3
Exception occurred to channel H1 and channel H2

Cause: Hardware fault occurred to STO circuit.


Remedy:

  • Replace the control board.


CrCE
Safety code FLASH CRC check fault

Cause: Control board is faulty.


Remedy:

  • Replace the control board.


E-Err
Repetitive extension card type

Cause: The two inserted extension cards are of the same type.


Remedy:

  • Users should not insert two cards with the same type.

  • Check the type of extension card, and remove one card after power down.


ENCUV
Encoder UVW loss fault

Cause: No electric level variation occurred to UVW signal.


Remedy:

  • Check the wiring of UVW.

  • Encoder is damaged.


F1-Er
Failed to identify the extension card in card slot 1

Cause: There is data transmission in interfaces of card slot 1, however, it cannot read the card type.


Remedy:

  • Confirm whether the extension card inserted can be supported.

  • Stabilize the extension card interfaces after power down, and confirm whether fault still occurs at next power-on.

  • Check whether the insertion port is damaged, if yes, replace the insertion port after power down.


F2-Er
Failed to identify the extension card in card slot 2

Cause: There is data transmission in interfaces of card slot 2, however, it cannot read the card type.


Remedy:

  • Confirm whether the extension card inserted can be supported.

  • Stabilize the extension card interfaces after power down, and confirm whether fault still occurs at next power-on.

  • Check whether the insertion port is damaged, if yes, replace the insertion port after power down.


F3-Er
Failed to identify the extension card in card slot 3

Cause: There is data transmission in interfaces of card slot 3, however, it cannot read the card type.


Remedy:

  • Confirm whether the extension card inserted can be supported.

  • Stabilize the extension card interfaces after power down, and confirm whether fault still occurs at next power-on.

  • Check whether the insertion port is damaged, if yes, replace the insertion port after power down.


C1-Er
Communication timeout occurred to the extension card in card slot 1

Cause: There is no data transmission in interfaces of card slot 1.


Remedy:

  • Confirm whether the extension card inserted can be supported.

  • Stabilize the extension card interfaces after power down, and confirm whether fault still occurs at next power-on.

  • Check whether the insertion port is damaged, if yes, replace the insertion port after power down.


C2-Er
Communication timeout occurred to the extension card in card slot 2

Cause: There is no data transmission in interfaces of card slot 2.


Remedy:

  • Confirm whether the extension card inserted can be supported.

  • Stabilize the extension card interfaces after power down, and confirm whether fault still occurs at next power-on.

  • Check whether the insertion port is damaged, if yes, replace the insertion port after power down.


C3-Er
Communication timeout occurred to the extension card in card slot 3

Cause: There is no data transmission in interfaces of card slot 3.


Remedy:

  • Confirm whether the extension card inserted can be supported.

  • Stabilize the extension card interfaces after power down, and confirm whether fault still occurs at next power-on.

  • Check whether the insertion port is damaged, if yes, replace the insertion port after power down.


E-DP
Profibus card communication timeout fault

Cause: There is no data transmission between the communication card and the host computer (or PLC).


Remedy:

  • Check whether the communication card wiring is loose or dropped.


E-NET
Ethernet card communication timeout fault

Cause: There is no data transmission between the communication card and the host computer.


Remedy:

  • Check whether the communication card wiring is loose or dropped.


E-CAN
CANopen card communication timeout fault

Cause: There is no data transmission between the communication card and the host computer (or PLC).


Remedy:

  • Check whether the communication card wiring is loose or dropped.


E-PN
PROFINET card communication timeout fault

Cause: There is no data transmission between the communication card and the host computer (or PLC).


Remedy:

  • Check whether the communication card wiring is loose or dropped.


E-CAT
EtherCAT card communication timeout fault

Cause: There is no data transmission between the communication card and the host computer (or PLC).


Remedy:

  • Check whether the communication card wiring is loose or dropped.


E-BAC
BACNet card communication timeout fault

Cause: There is no data transmission between the communication card and the host computer (or PLC).


Remedy:

  • Check whether the communication card wiring is loose or dropped.


E-DEV
DeviceNET card communication timeout fault

Cause: There is no data transmission between the communication card and the host computer (or PLC).


Remedy:

  • Check whether the communication card wiring is loose or dropped.


ESCAN
Can master/slave communication card communication timeout fault

Cause: There is no data transmission between the CAN master and slave communication cards.


Remedy:

  • Check whether the communication card wiring is loose or dropped.


S-Err
Master-slave synchronous CAN slave fault

Cause: Fault occurred to one of the CAN slave VFDs.


Remedy:

  • Detect the CAN slave VFD and analyze the corresponding fault cause of the VFD.


PoFF
System power failure

Cause: The system is powered off or the bus voltage is too low.


Remedy:

  • Check the grid conditions.


How to Clear & Reset INVT GD350-UL Drive Faults

  1. Keypad Reset: Press the red STOP/RST key directly on the LCD control panel. In any fault trip state, the STOP/RST key serves as an immediate fault clear command across all control locations.
  2. Digital Input Reset (DI): If assigned in parameter group P05 (P05.01–P05.08 set to Function 4: Fault Reset), pulse the designated digital input terminal (S1–S8 to COM) to clear the active alarm.
  3. INVT-Workshop / Studio PC Tool: Connect your PC via the USB or RS-485 interface, open INVT Studio or INVT-Workshop, and click “Fault Reset” in the online drive status monitor.
  4. Fieldbus Control Word: Write a reset bit pulse to communication register 2000H via Modbus RTU or through optional Profinet, EtherCAT, Ethernet/IP, or CANopen expansion cards.
  5. Power Cycle: Disconnect main AC line power, wait until the internal DC bus capacitor discharges completely (wait 5 to 25 minutes depending on kilowatt frame size until the POWER LED extinguishes), and restore line power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that the internal DC bus voltage has dropped strictly below 36VDC across main circuit terminals (+) and (-) [or UDC+ and UDC-] before opening enclosures, servicing terminal strips, or touching motor terminals U, V, and W on the INVT GD350-UL inverter. Wait at least 5 minutes (for units ≤110 kW), 15 minutes (132–315 kW), or 25 minutes (≥355 kW) after disconnecting input power.