INVT GD800 Pro Series drive

Home / INVT / INVT GD800 Pro Series drive

INVT GD800 Pro Series Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the INVT Goodrive800 Pro (GD800 Pro) modular engineering variable frequency drive series. Search or filter through the complete fault code directory below.

Modular Engineering Multi-Drive Power: 4 kW to 3000 kW (up to 3 MW) Embedded Functional Safety (STO SIL3 / PL e)
Power Range 4 kW – 3000 kW (5 – 4000+ HP)
Supply Voltage 380V / 500V / 690V AC & Common DC Bus
Control Modes Closed-Loop Vector (FVC), SVC & V/F
Operator Interface Multi-Language LCD Keypad / PC Studio

Complete INVT GD800 Pro Series Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OUt1, OC1, or TE).

Fault Code and MeaningCause and Remedy
ov1
Overvoltage during acceleration

Cause: Exception occurred to input voltage; Large energy feedback.



Remedy:

  • Check the input power.

  • Check whether load DEC time is too short.

  • Check if the motor starts during rotating.

  • Check if additional dynamic brake components are required.


ov2
Overvoltage during deceleration

Cause: Exception occurred to input voltage; Large energy feedback.



Remedy:

  • Check the input power.

  • Check whether load DEC time is too short.

  • Check if the motor starts during rotating.

  • Check if additional dynamic brake components are required.


ov3
Overvoltage during constant speed running

Cause: Exception occurred to input voltage; Large energy feedback.



Remedy:

  • Check the input power.

  • Check whether load DEC time is too short.

  • Check if the motor starts during rotating.

  • Check if additional dynamic brake components are required.


oC1
Overcurrent during acceleration

Cause: ACC/DEC is too fast; The voltage of the grid is too low; VFD power is too small; Load transient or exception occurred; To-ground short circuit or output phase loss occurred; Strong external interference sources.



Remedy:

  • Increase ACC/DEC time.

  • Check the input power.

  • Select the VFD with larger power.

  • Check whether the load is short circuited (to-ground short circuit or line-to-line short circuit) or the rotation is not smooth.

  • Check the output wiring.

  • Check if there is strong interference.


oC2
Overcurrent during deceleration

Cause: ACC/DEC is too fast; The voltage of the grid is too low; VFD power is too small; Load transient or exception occurred; To-ground short circuit or output phase loss occurred; Strong external interference sources.



Remedy:

  • Increase ACC/DEC time.

  • Check the input power.

  • Select the VFD with larger power.

  • Check whether the load is short circuited (to-ground short circuit or line-to-line short circuit) or the rotation is not smooth.

  • Check the output wiring.

  • Check if there is strong interference.


oC3
Overcurrent during constant speed running

Cause: ACC/DEC is too fast; The voltage of the grid is too low; VFD power is too small; Load transient or exception occurred; To-ground short circuit or output phase loss occurred; Strong external interference sources.



Remedy:

  • Increase ACC/DEC time.

  • Check the input power.

  • Select the VFD with larger power.

  • Check whether the load is short circuited (to-ground short circuit or line-to-line short circuit) or the rotation is not smooth.

  • Check the output wiring.

  • Check if there is strong interference.


Lv
Bus undervoltage fault

Cause: The voltage of the grid is too low.



Remedy:

  • Check the grid input power.


oL1
Motor overload

Cause: The grid voltage is too low; The motor rated current is set incorrectly; The motor stall occurs or the load transient is too large.



Remedy:

  • Check the grid voltage.

  • Reset the motor rated current.

  • Check the load and adjust the torque boost quantity.


oL2
VFD overload

Cause: ACC is too fast; The motor in rotating is restarted; The grid voltage is too low; Load is too large.



Remedy:

  • Increase ACC time.

  • Avoid restart after stop.

  • Check the grid voltage.

  • Select the VFD with larger power.

  • Select a proper motor.


SPI
Input phase loss

Cause: Phase loss or violent fluctuation occurred on input R, S, T.



Remedy:

  • Check the input power.

  • Check the installation wiring.


SPo
Phase loss on output side

Cause: Phase loss occurred to U, V, W output (or the three phases of motor is asymmetrical).



Remedy:

  • Check the output wiring.

  • Check the motor and cable.


EF
External fault

Cause: SI external faulty input terminal action.



Remedy:

  • Check external device input.


E_485
RS485 communication fault

Cause: Baud rate is set improperly; Communication line fault; Incorrect communication address; Communication suffers from strong interference.



Remedy:

  • Set proper baud rate.

  • Check the wiring of communication interfaces.

  • Set the communication address correctly.

  • Replace or change the wiring to enhance the anti-interference capacity.


ItE
Current detection fault

Cause: Poor contact of the connector of control board; Hall component is damaged; Exception occurred to amplification circuit.



Remedy:

  • Check the connector and re-plug.

  • Replace the hall component.

  • Replace the main control board.


tE
Motor-autotuning fault

Cause: The motor capacity does not match the VFD capacity; Motor parameter is set improperly; The parameters gained from autotuning deviate sharply from the standard parameters; Autotuning timeout.



Remedy:

  • Change the VFD model.

  • Set proper motor type and nameplate parameters.

  • Empty the motor load and carry out autotuning again.

  • Check the motor wiring and parameter setup.

  • Check whether the upper limit frequency is larger than 2/3 of the rated frequency.


EEP
EEPROM operation error

Cause: Error in reading or writing control parameters; EEPROM is damaged.



Remedy:

  • Press STOP/RST for reset.

  • Change the main control board.


PIdE
PID feedback offline fault

Cause: PID feedback offline; PID feedback source disappears.



Remedy:

  • Check PID feedback signal wires.

  • Check PID feedback source.


bCE
Braking unit fault

Cause: Fault occurred to the brake circuit or the braking pipe is damaged; Resistance of the external braking resistor is small.



Remedy:

  • Check the braking unit, and replace with new braking pipe.

  • Increase the brake resistance.


ENd
Running time reached

Cause: The actual running time of the VFD is longer than the internal set running time.



Remedy:

  • Ask for the supplier and adjust the set running time.


oL3
Electronic overload fault

Cause: The VFD reports overload pre-alarm according to the setting.



Remedy:

  • Check the load and the overload pre-alarm points.


PCE
Keypad communication fault

Cause: Keypad cable connected improperly or disconnected; Keypad cable too long, causing strong interference; Keypad or mainboard communication circuit error.



Remedy:

  • Check the keypad cable to determine whether a fault occurs.

  • Check for and remove the external interference source.

  • Replace the hardware and seek maintenance services.


UPE
Parameter upload error

Cause: Keypad cable connected improperly or disconnected; Keypad cable too long, causing strong interference; Keypad or mainboard communication circuit error.



Remedy:

  • Check for and remove the external interference source.

  • Replace the hardware and seek maintenance services.


dNE
Parameter download error

Cause: Keypad cable connected improperly or disconnected; Keypad cable too long, causing strong interference; Data storage error occurred to the keypad.



Remedy:

  • Check for and remove the external interference source.

  • Replace the hardware and seek maintenance services.

  • Re-back up the data on the keypad.


E_dP
PROFIBUS communication fault

Cause: Communication address is not correct; The matching resistance is not set well; The master GSD file is not set up; The peripheral interference is too large.



Remedy:

  • Check the related settings.

  • Check the surrounding environment, and eliminate interference effects.


E_NEt
Ethernet communication fault

Cause: The address of Ethernet is set improperly; The communication mode is set improperly; The peripheral interference is too large.



Remedy:

  • Check the related settings.

  • Check the communication mode selection.

  • Check the surrounding environment, and eliminate interference effects.


E_CAN
CANopen communication fault

Cause: Line contact is poor; The matching resistor is not switched on; Communication baud rates do not match; The peripheral interference is too large.



Remedy:

  • Check the line: switch on the matching resistor.

  • Set the same baud rate.

  • Check the surrounding environment, and eliminate interference effects.


EtH1
To-ground short-circuit fault 1

Cause: The output of the VFD is short circuited to the ground; There is a fault in the current detection circuit.



Remedy:

  • Check whether the motor wiring is normal.

  • Replace the hall component.

  • Replace the main control board.


dEU
Speed deviation fault

Cause: The load is too heavy or stalled.



Remedy:

  • Check the load to ensure it is proper, and increase the detection time.

  • Check whether the control parameters are set properly.


STE
Mal-adjustment fault

Cause: SM control parameters are set incorrectly; Autotuned parameters are not accurate; The VFD is not connected to the motor.



Remedy:

  • Check the load and ensure the load is normal.

  • Check whether control parameters are set correctly.

  • Increase the mal-adjustment detection time.


LL
Underload fault

Cause: The VFD reports underload pre-alarm according to the setting.



Remedy:

  • Check the load and the underload pre-alarm points.


ENCIo
Encoder offline fault

Cause: In closed-loop vector control, the encoder signal cables is disconnected; Encoder is damaged.



Remedy:

  • Check the encoder wiring and re-connect the cables.

  • Check for encoder output.


ENCId
Encoder reversal fault

Cause: In closed-loop vector control, the encoder is disconnected or damaged; VFD wiring is improper.



Remedy:

  • Check the encoder wiring and adjust the wiring.


E_STo
STO fault

Cause: STO terminal is disconnected.



Remedy:

  • Check the external controller.


FAE
Brake action fault

Cause: Brake feedback action error.



Remedy:

  • Check the external contactor.


E_ASC
Master/slave communication fault

Cause: The address is set improperly; The communication mode is set improperly; The communication cable is not connected properly.



Remedy:

  • Check the related settings.

  • Check the communication mode selection.

  • Check the wiring and adjust the wiring.


E_SLE
Slave fault

Cause: Fault occurring to the slave.



Remedy:

  • Check slave settings and ambient environment.


dF_CE
DSP-FPGA communication fault

Cause: DSP-FPGA communication fault occurred; Control board is faulty.



Remedy:

  • Ask for service.


CPoE
Control power fault

Cause: The working voltage of switch power is too low.



Remedy:

  • Check whether the switch power is normal.

  • Check whether the power board is normal.


oH
Motor overtemperature fault

Cause: Long-time overload running or exception occurred; The temperature detection resistance is abnormal; Motor overtemperature protection threshold is set improperly.



Remedy:

  • Check the motor, and perform maintenance on the motor.

  • Check whether the temperature sensor is proper.

  • Reset the motor overtemperature protection threshold.


tCE
Torque verification fault

Cause: The motor load is disconnected with the VFD.



Remedy:

  • Ensure the wiring between the motor and the VFD is in good conditions.

  • Decrease the torque verification point for light motor load.


P.oFF
VFD power-off status

Cause: Bus voltage is lower than the undervoltage point.



Remedy:

  • Check that the main power is disconnected.


m.oUt1
Unit phase-U Vce check fault

Cause: The corresponding IGBT inside the unit is damaged; Strong interference; External short circuit.



Remedy:

  • Ask for technical support.

  • Check for and remove the external interference source.

  • Check the external circuit and eliminate the load fault.


m.oUt2
Unit phase-V Vce check fault

Cause: The corresponding IGBT inside the unit is damaged; Strong interference; External short circuit.



Remedy:

  • Ask for technical support.

  • Check for and remove the external interference source.

  • Check the external circuit and eliminate the load fault.


m.oUt3
Unit phase-W Vce check fault

Cause: The corresponding IGBT inside the unit is damaged; Strong interference; External short circuit.



Remedy:

  • Ask for technical support.

  • Check for and remove the external interference source.

  • Check the external circuit and eliminate the load fault.


m.oC
Unit hardware overcurrent fault

Cause: The IGBT inside the unit is damaged; The inverter acceleration is too fast; Short circuit occurred to the output side of the unit.



Remedy:

  • Ask for technical support.

  • Update the parameter settings and restart.

  • Check the external circuit of the unit and eliminate the fault.


m.ItE
Unit current detection fault

Cause: The unit current detection parts is damaged; Interference exists.



Remedy:

  • Ask for technical support.

  • Check for and remove the external interference source.


m.IbC
Unit current imbalance fault

Cause: The three phase current amplitude difference of the power unit is too large and severely affect the system operating performance.



Remedy:

  • Check the input power.

  • Check the installation wiring.


m.oH1
Unit rectifier bridge overheating fault

Cause: Instantaneous overcurrent occurred to the rectifier; Three-phase output have interphase or the grounding is short circuited; Air duct is blocked or fan is damaged; Ambient temperature is too high; Control board cables or plugs are loose.



Remedy:

  • See solutions for overcurrent.

  • Re-wiring.

  • Dredge the vent duct or replace the fan.

  • Lower the ambient temperature.

  • Check and reconnect the control board.

  • Ask for technical support.


m.oH2
Unit IGBT overheating fault

Cause: Auxiliary power supply is damaged, and undervoltage occurred for drive voltage; The short through of bridge arm of power modules occurred; Control board is abnormal.



Remedy:

  • Check and reconnect the control board.

  • Ask for technical support.


m.EF1
Unit fan overheating fault

Cause: Fan is not powered on; Fan is overheated.



Remedy:

  • Check the power supply.

  • Clean the air duct of the inverter.


m.EF2
Unit filter module overheating fault

Cause: The unit is continuously running in overload; The air duct is blocked by foreign objects.



Remedy:

  • Check the inverter load and reduce the load power.

  • Clean the air duct of the inverter.


m.EF3
Unit input phase loss

Cause: SI external faulty input terminal action.



Remedy:

  • Check external device input.


m.ov
Unit bus overvoltage fault

Cause: The grid voltage is too high.



Remedy:

  • Check the input power.


m.Lv
Unit bus undervoltage fault

Cause: The grid voltage is too low.



Remedy:

  • Check the input power.


m.dn_C
Unit downstream communication fault

Cause: The address settings between the master and the slave is not consistent; The communication mode is set improperly for the slave; The communication cable is not connected properly.



Remedy:

  • Check the related settings.

  • Check the communication mode selection.

  • Check the wiring and adjust the wiring.


m.UP_C
Unit upstream communication fault

Cause: The address settings between the master and the slave is not consistent; The communication mode is set improperly for the master; The communication cable is not connected properly.



Remedy:

  • Check the related settings.

  • Check the communication mode selection.

  • Check the wiring and adjust the wiring.


m.PEr
Unit power supply detection fault

Cause: The working voltage of switch power is too low.



Remedy:

  • Ask for technical support.


m.CoFF
Unit optical-fiber communication fault

Cause: The optical fiber is not connected properly or the optical fiber is damaged.



Remedy:

  • Check the optical fiber or replace a new optical fiber.


PoFF
Power on failure

Cause: The optical fiber is normal but the bus voltage is too low.



Remedy:

  • Check the grid conditions.


(No Code)
Communication failure between keypad and main control board

Cause: The keypad is not connected properly.



Remedy:

  • Check the installation environment of the keypad.


How to Clear & Reset INVT GD800 Pro Series Drive Faults

  1. Keypad Reset: Press the red STOP/RST key on the cabinet-door LCD control panel once the root fault condition on the active rectifier or inverter unit has been resolved.
  2. Digital Input Reset (DI): If configured in parameter group P05 (P05.01–P05.09) on the CU (Control Unit) terminal block, pulse the designated digital input assigned to function 4 (Fault reset).
  3. Fieldbus Communication Command: Transmit a fault reset control word (write command bit 0007H to control address 2000H) via PROFINET, Profibus-DP, Modbus RTU/TCP, CANopen, or Ethernet/IP communication cards.
  4. Engineering PC Workshop Tool: Connect an engineering PC via optical fiber, USB, or Ethernet to the INVT Drive Workshop software, open the active unit status window, and click “Fault Reset” to clear latching unit alarms.
  5. System Power Cycle & DC Isolation: Switch off the main AC incoming circuit breaker or open the DC bus isolation switch. Allow high-capacity DC bus capacitor banks to bleed down completely (minimum 15 minutes) before re-closing the supply.
⚠️ High-Power Engineering DC Bus Electrical Safety Warning: The INVT GD800 Pro system incorporates high-power multi-drive inverter modules operating on intermediate DC bus voltages up to 1250VDC. Always disconnect main incoming supply breakers and wait at least 15 minutes. Use a calibrated high-voltage multimeter to verify that DC bus terminals (+) and (-) have dropped strictly below 36VDC before withdrawing drive modules, opening cabinet doors, or touching UVW output busbars.