INVT GD800 Pro Series Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the INVT Goodrive800 Pro (GD800 Pro) modular engineering variable frequency drive series. Search or filter through the complete fault code directory below.
Power Range
4 kW – 3000 kW (5 – 4000+ HP)
Supply Voltage
380V / 500V / 690V AC & Common DC Bus
Control Modes
Closed-Loop Vector (FVC), SVC & V/F
Operator Interface
Multi-Language LCD Keypad / PC Studio
Complete INVT GD800 Pro Series Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type OUt1, OC1, or TE).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| ov1 Overvoltage during acceleration | Cause: Exception occurred to input voltage; Large energy feedback. Remedy:
|
| ov2 Overvoltage during deceleration | Cause: Exception occurred to input voltage; Large energy feedback. Remedy:
|
| ov3 Overvoltage during constant speed running | Cause: Exception occurred to input voltage; Large energy feedback. Remedy:
|
| oC1 Overcurrent during acceleration | Cause: ACC/DEC is too fast; The voltage of the grid is too low; VFD power is too small; Load transient or exception occurred; To-ground short circuit or output phase loss occurred; Strong external interference sources. Remedy:
|
| oC2 Overcurrent during deceleration | Cause: ACC/DEC is too fast; The voltage of the grid is too low; VFD power is too small; Load transient or exception occurred; To-ground short circuit or output phase loss occurred; Strong external interference sources. Remedy:
|
| oC3 Overcurrent during constant speed running | Cause: ACC/DEC is too fast; The voltage of the grid is too low; VFD power is too small; Load transient or exception occurred; To-ground short circuit or output phase loss occurred; Strong external interference sources. Remedy:
|
| Lv Bus undervoltage fault | Cause: The voltage of the grid is too low. Remedy:
|
| oL1 Motor overload | Cause: The grid voltage is too low; The motor rated current is set incorrectly; The motor stall occurs or the load transient is too large. Remedy:
|
| oL2 VFD overload | Cause: ACC is too fast; The motor in rotating is restarted; The grid voltage is too low; Load is too large. Remedy:
|
| SPI Input phase loss | Cause: Phase loss or violent fluctuation occurred on input R, S, T. Remedy:
|
| SPo Phase loss on output side | Cause: Phase loss occurred to U, V, W output (or the three phases of motor is asymmetrical). Remedy:
|
| EF External fault | Cause: SI external faulty input terminal action. Remedy:
|
| E_485 RS485 communication fault | Cause: Baud rate is set improperly; Communication line fault; Incorrect communication address; Communication suffers from strong interference. Remedy:
|
| ItE Current detection fault | Cause: Poor contact of the connector of control board; Hall component is damaged; Exception occurred to amplification circuit. Remedy:
|
| tE Motor-autotuning fault | Cause: The motor capacity does not match the VFD capacity; Motor parameter is set improperly; The parameters gained from autotuning deviate sharply from the standard parameters; Autotuning timeout. Remedy:
|
| EEP EEPROM operation error | Cause: Error in reading or writing control parameters; EEPROM is damaged. Remedy:
|
| PIdE PID feedback offline fault | Cause: PID feedback offline; PID feedback source disappears. Remedy:
|
| bCE Braking unit fault | Cause: Fault occurred to the brake circuit or the braking pipe is damaged; Resistance of the external braking resistor is small. Remedy:
|
| ENd Running time reached | Cause: The actual running time of the VFD is longer than the internal set running time. Remedy:
|
| oL3 Electronic overload fault | Cause: The VFD reports overload pre-alarm according to the setting. Remedy:
|
| PCE Keypad communication fault | Cause: Keypad cable connected improperly or disconnected; Keypad cable too long, causing strong interference; Keypad or mainboard communication circuit error. Remedy:
|
| UPE Parameter upload error | Cause: Keypad cable connected improperly or disconnected; Keypad cable too long, causing strong interference; Keypad or mainboard communication circuit error. Remedy:
|
| dNE Parameter download error | Cause: Keypad cable connected improperly or disconnected; Keypad cable too long, causing strong interference; Data storage error occurred to the keypad. Remedy:
|
| E_dP PROFIBUS communication fault | Cause: Communication address is not correct; The matching resistance is not set well; The master GSD file is not set up; The peripheral interference is too large. Remedy:
|
| E_NEt Ethernet communication fault | Cause: The address of Ethernet is set improperly; The communication mode is set improperly; The peripheral interference is too large. Remedy:
|
| E_CAN CANopen communication fault | Cause: Line contact is poor; The matching resistor is not switched on; Communication baud rates do not match; The peripheral interference is too large. Remedy:
|
| EtH1 To-ground short-circuit fault 1 | Cause: The output of the VFD is short circuited to the ground; There is a fault in the current detection circuit. Remedy:
|
| dEU Speed deviation fault | Cause: The load is too heavy or stalled. Remedy:
|
| STE Mal-adjustment fault | Cause: SM control parameters are set incorrectly; Autotuned parameters are not accurate; The VFD is not connected to the motor. Remedy:
|
| LL Underload fault | Cause: The VFD reports underload pre-alarm according to the setting. Remedy:
|
| ENCIo Encoder offline fault | Cause: In closed-loop vector control, the encoder signal cables is disconnected; Encoder is damaged. Remedy:
|
| ENCId Encoder reversal fault | Cause: In closed-loop vector control, the encoder is disconnected or damaged; VFD wiring is improper. Remedy:
|
| E_STo STO fault | Cause: STO terminal is disconnected. Remedy:
|
| FAE Brake action fault | Cause: Brake feedback action error. Remedy:
|
| E_ASC Master/slave communication fault | Cause: The address is set improperly; The communication mode is set improperly; The communication cable is not connected properly. Remedy:
|
| E_SLE Slave fault | Cause: Fault occurring to the slave. Remedy:
|
| dF_CE DSP-FPGA communication fault | Cause: DSP-FPGA communication fault occurred; Control board is faulty. Remedy:
|
| CPoE Control power fault | Cause: The working voltage of switch power is too low. Remedy:
|
| oH Motor overtemperature fault | Cause: Long-time overload running or exception occurred; The temperature detection resistance is abnormal; Motor overtemperature protection threshold is set improperly. Remedy:
|
| tCE Torque verification fault | Cause: The motor load is disconnected with the VFD. Remedy:
|
| P.oFF VFD power-off status | Cause: Bus voltage is lower than the undervoltage point. Remedy:
|
| m.oUt1 Unit phase-U Vce check fault | Cause: The corresponding IGBT inside the unit is damaged; Strong interference; External short circuit. Remedy:
|
| m.oUt2 Unit phase-V Vce check fault | Cause: The corresponding IGBT inside the unit is damaged; Strong interference; External short circuit. Remedy:
|
| m.oUt3 Unit phase-W Vce check fault | Cause: The corresponding IGBT inside the unit is damaged; Strong interference; External short circuit. Remedy:
|
| m.oC Unit hardware overcurrent fault | Cause: The IGBT inside the unit is damaged; The inverter acceleration is too fast; Short circuit occurred to the output side of the unit. Remedy:
|
| m.ItE Unit current detection fault | Cause: The unit current detection parts is damaged; Interference exists. Remedy:
|
| m.IbC Unit current imbalance fault | Cause: The three phase current amplitude difference of the power unit is too large and severely affect the system operating performance. Remedy:
|
| m.oH1 Unit rectifier bridge overheating fault | Cause: Instantaneous overcurrent occurred to the rectifier; Three-phase output have interphase or the grounding is short circuited; Air duct is blocked or fan is damaged; Ambient temperature is too high; Control board cables or plugs are loose. Remedy:
|
| m.oH2 Unit IGBT overheating fault | Cause: Auxiliary power supply is damaged, and undervoltage occurred for drive voltage; The short through of bridge arm of power modules occurred; Control board is abnormal. Remedy:
|
| m.EF1 Unit fan overheating fault | Cause: Fan is not powered on; Fan is overheated. Remedy:
|
| m.EF2 Unit filter module overheating fault | Cause: The unit is continuously running in overload; The air duct is blocked by foreign objects. Remedy:
|
| m.EF3 Unit input phase loss | Cause: SI external faulty input terminal action. Remedy:
|
| m.ov Unit bus overvoltage fault | Cause: The grid voltage is too high. Remedy:
|
| m.Lv Unit bus undervoltage fault | Cause: The grid voltage is too low. Remedy:
|
| m.dn_C Unit downstream communication fault | Cause: The address settings between the master and the slave is not consistent; The communication mode is set improperly for the slave; The communication cable is not connected properly. Remedy:
|
| m.UP_C Unit upstream communication fault | Cause: The address settings between the master and the slave is not consistent; The communication mode is set improperly for the master; The communication cable is not connected properly. Remedy:
|
| m.PEr Unit power supply detection fault | Cause: The working voltage of switch power is too low. Remedy:
|
| m.CoFF Unit optical-fiber communication fault | Cause: The optical fiber is not connected properly or the optical fiber is damaged. Remedy:
|
| PoFF Power on failure | Cause: The optical fiber is normal but the bus voltage is too low. Remedy:
|
| (No Code) Communication failure between keypad and main control board | Cause: The keypad is not connected properly. Remedy:
|
How to Clear & Reset INVT GD800 Pro Series Drive Faults
- Keypad Reset: Press the red STOP/RST key on the cabinet-door LCD control panel once the root fault condition on the active rectifier or inverter unit has been resolved.
- Digital Input Reset (DI): If configured in parameter group P05 (P05.01–P05.09) on the CU (Control Unit) terminal block, pulse the designated digital input assigned to function 4 (Fault reset).
- Fieldbus Communication Command: Transmit a fault reset control word (write command bit
0007Hto control address 2000H) via PROFINET, Profibus-DP, Modbus RTU/TCP, CANopen, or Ethernet/IP communication cards. - Engineering PC Workshop Tool: Connect an engineering PC via optical fiber, USB, or Ethernet to the INVT Drive Workshop software, open the active unit status window, and click “Fault Reset” to clear latching unit alarms.
- System Power Cycle & DC Isolation: Switch off the main AC incoming circuit breaker or open the DC bus isolation switch. Allow high-capacity DC bus capacitor banks to bleed down completely (minimum 15 minutes) before re-closing the supply.
⚠️ High-Power Engineering DC Bus Electrical Safety Warning:
The INVT GD800 Pro system incorporates high-power multi-drive inverter modules operating on intermediate DC bus voltages up to 1250VDC. Always disconnect main incoming supply breakers and wait at least 15 minutes. Use a calibrated high-voltage multimeter to verify that DC bus terminals (+) and (-) have dropped strictly below 36VDC before withdrawing drive modules, opening cabinet doors, or touching UVW output busbars.