LS Electric iX7NH drive

Home / LS Electric / LS Electric iX7NH drive

LS Electric iX7NH Servo Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, AL-xx alarm trip causes, and step-by-step troubleshooting procedures for the high-performance LS Electric iX7NH EtherCAT & Modbus TCP AC servo drive series. Search or filter through the complete fault code directory below.

High-Speed EtherCAT & Modbus TCP Power: 0.1 to 3.5 kW (100W to 3500W) Embedded Web Server & STO
Power Range 0.1 – 3.5 kW (100W – 3500W)
Supply Voltage 1-Ph 100~120V / 1/3-Ph 200~240V
Control Modes Position, Speed & Torque (CiA402)
Operator Interface Built-in Web Server / DriveCM

Complete LS Electric iX7NH Servo Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type AL-11, AL-14, Overcurrent, or Encoder).

Fault Code and MeaningCause and Remedy
AL-10

IPM fault
(Overcurrent H/W)

Cause:

  • Motor cable abnormality.

  • Encoder cable abnormality.

  • Parameter setting abnormality.




Remedy:

  • Check for abnormal wiring or short circuit. Replace the motor cable.

  • Check for abnormal wiring or short circuit. Replace the encoder cable.

  • Make sure settings for Motor ID [0x2000], Encoder Type [0x2001], and Format [0x2002] match the motor label. Modify parameters if necessary.


AL-11

IPM temperature
(IPM Overheat)

Cause:

  • Ambient temperature is too high.

  • Continual overload alarm.

  • Highly frequent or continual regenerative operation.

  • Drive installation direction issue.

  • Drive abnormality.




Remedy:

  • Check if ambient temperature exceeds 50°C. Lower temperature around the drive.

  • Check accumulated operation overload ratio [0x2603]. Change capacity of drive/motor or adjust gain.

  • Check accumulated regeneration overload ratio [0x2606]. Adjust regeneration brake resistor [0x2009] or use an external resistor.

  • Refer to "Wiring and Connection" section for installation status.

  • If alarm persists after power cycling, replace the drive.


AL-14

Over current
(Overcurrent S/W)

Cause:

  • Motor phase resistance issue.

  • Apparatus abnormality.




Remedy:

  • Inspect resistance between motor lines (U-V, V-W, W-U should be below several Ω). Replace motor if needed.

  • Inspect apparatus for conflicts or binding.


AL-15

Current offset
(Current offset abnormality)

Cause:

  • Motor U, V phase current offset set excessively.

  • Drive abnormality.




Remedy:

  • Check U/V/W-phase current offsets [0x2015]~[0x2017]. If 5% or higher of rated current, adjust again.

  • If alarms occur continually after adjustment, replace the drive.


AL-16

Current limit exceeded
(Overcurrent H/W)

Cause:

  • Drive abnormality.

  • Noise-related abnormalities.




Remedy:

  • If alarm occurs continually after power cycling, replace the drive.

  • Resolve noise by checking wiring/installation. Check PE wiring. Adjust PE wiring size to match drive main circuit wiring.


AL-21

Continuous overload

Cause:

  • Continuous operation with load exceeding rated value.

  • Motor brake abnormality.

  • Parameter setting abnormality.

  • Apparatus or Cable abnormality.




Remedy:

  • Check load rate [0x2603]. Change motor/drive capacity or adjust gain.

  • Check opening of motor brake during SVON. Supply power to brake.

  • Verify Motor ID, Encoder Type/Format settings match label. Check overload check base [0x200F].

  • Inspect apparatus for binding. Check motor/encoder cables for shorts/wiring issues.


AL-22

Drive temperature 1
(Drive overheat 1)

Cause:

  • Ambient temperature too high.

  • Drive abnormality.




Remedy:

  • Check if ambient temp > 50°C. Lower temperature.

  • Check if displayed temp [0x260B] differs greatly from ambient. Replace drive if sensor is faulty.


AL-23

Regenerative overload

Cause:

  • Capacity exceeded due to frequent operation or continual regeneration.

  • Parameter setting abnormality.

  • Main power input voltage too high (544 Vac or higher).

  • Drive abnormality (Resistor generating heat when not in operation).




Remedy:

  • Check accumulated regeneration rate [0x2606]. Adjust resistor config [0x2009] or use external resistor.

  • Re-inspect main power source voltage.

  • Replace the drive if resistor heats up unexpectedly.


AL-24

Motor cable open
(Motor disconnection)

Cause:

  • Parameter setting abnormality (Current offsets).

  • Motor cable abnormality (Disconnection).

  • Motor abnormality (Internal short).

  • Drive abnormality.




Remedy:

  • Check settings at [0x2015]-[0x2017]. Execute command for current offset adjustment.

  • Check for cable disconnection. Replace motor cable.

  • Check for U, V, W short inside motor. Replace motor.

  • If alarm occurs continuously after SV-ON, replace the drive.


AL-25

Drive temperature 2
(Drive overheat 2)

Cause:

  • Ambient temperature.

  • Drive abnormality.




Remedy:

  • Lower temperature around the drive if > 50°C.

  • Check displayed temp 2 value [0x260C]. Replace drive if faulty.


AL-26

Encoder temperature
(Encoder Overheat)

Cause: Reserved.


Remedy: -
AL-28

Fan trip
(DC cooling fan abnormality)

Cause: DC cooling fan abnormality (Disconnection, short, abnormal connection).


Remedy: Connect DC cooling fan. If alarm persists after power cycle, replace the DC cooling fan.
AL-29

Regeneration brake fault

Cause: Regeneration resistor abnormality (Disconnection or short).


Remedy: Connect regeneration brake resistor. If alarm persists, replace the regenerative resistor.
AL-30

Encoder communication
(Serial Encoder Error)

Cause:

  • Encoder cable abnormality.

  • Parameter setting abnormality.

  • Encoder abnormality.

  • Drive abnormality.




Remedy:

  • Check for disconnection/short. Replace encoder cable.

  • Match Encoder Type [0x2001] and Resolution [0x2002] to label.

  • If alarm persists, replace motor or drive.


AL-31

Encoder cable open
(Disconnection)

Cause: Encoder abnormality.


Remedy: If alarm occurs continually, replace the motor (internal encoder issue).
AL-32

Encoder data
(Encoder Data Error)

Cause: Drive abnormality.


Remedy: If alarm occurs continually after power cycling, replace the drive.
AL-33

Motor setting
(Motor ID Setting Error)

Cause:

  • Motor ID setting mismatch.

  • Drive abnormality.




Remedy:

  • Ensure Motor ID [0x2000] matches motor label. Alarm clears after param modification and power cycle.

  • If alarm persists, replace the drive.


AL-34

Z Phase open
(Encoder Z-phase Loss)

Cause:

  • Parameter setting abnormality.

  • Encoder cable abnormality.

  • Encoder or Drive abnormality.




Remedy:

  • If using step motor (no Z phase), set 14th bit in warning mask [0x2014] to mask AL-34.

  • Check wiring/shorts. Replace encoder cable.

  • Replace motor or drive if hardware is faulty.


AL-35

Low battery
(Encoder battery low)

Cause:

  • Parameter setting abnormality.

  • Defective battery connection.

  • Low battery voltage (< 3.3V).




Remedy:

  • For incremental usage of absolute encoder, set Absolute Encoder Config [0x2005] to 1.

  • Connect battery accurately.

  • Replace the battery.


AL-36

Sinusoidal ENC amplitude

Cause:

  • Encoder cable abnormality (Shield/PE).

  • Drive abnormality.




Remedy:

  • Check for disconnection, shield, and PE connection. Replace cable.

  • Replace drive if alarm persists.


AL-37

Sinusoidal ENC frequency

Cause:

  • Parameter setting abnormality.

  • Converter failure.

  • Encoder abnormality.




Remedy:

  • Check Encoder Type [0x2001] and Speed Command (Max 250kHz).

  • Replace converter or encoder if hardware is faulty.


AL-38

Encoder setting error

Cause:

  • Abnormal combination of drive and motor.

  • Encoder cable abnormality.

  • Encoder/Drive abnormality.




Remedy:

  • Use a drive and motor with the same brand label.

  • Check wiring. Replace encoder cable.

  • Replace motor or drive if alarm persists.


AL-3b

Encoder position error
(Position loss)

Cause:

  • Defective battery connection.

  • Low battery voltage.




Remedy:

  • Check connection, then execute GB preset procedure.

  • Replace battery (> 3.3V), then execute GB preset procedure.


AL-40

Under voltage
(Low Voltage)

Cause:

  • Main power input voltage abnormality (< 134 Vac).

  • DC link voltage low (< 190 Vdc).

  • Lowered power voltage during operation.




Remedy:

  • Re-inspect main power source.

  • Check DC link voltage [0x2605]. Replace drive if internal reading is wrong.

  • Use 3-phase voltage supply.


AL-41

Over voltage

Cause:

  • Main power input voltage too high (> 286 Vac).

  • DC link voltage high (> 405 Vdc).

  • Too large external regeneration resistor.

  • Rapid acceleration/deceleration.




Remedy:

  • Re-inspect main power source.

  • Recheck regeneration resistor value.

  • Set a higher value for acceleration/deceleration time.


AL-42

Main power fail

Cause:

  • Main power input voltage abnormality (L1, L2, L3).

  • Parameter setting abnormality (Check mode).

  • Momentary power outage.




Remedy:

  • Re-check power (200-240 Vac).

  • Use 3-phase input if possible and adjust [0x2006].

  • Increase monitoring interval [0x2007] or check power supply.


AL-43

Control power fail

Cause: Voltage failure between C1 and C2 phases.


Remedy: Re-inspect control power (should be 200-240 Vac). Replace drive if alarm persists.
AL-50

Over speed limit

Cause:

  • Motor/Encoder cable abnormality.

  • Parameter setting abnormality.

  • Gear ratio or Gain settings.




Remedy:

  • Replace motor/encoder cable.

  • Match Motor ID/Encoder settings to label.

  • Lower electric gear ratio [0x6091]. Re-adjust gain [0x2100]~[0x211F].


AL-51

POS following
(Excessive Position Error)

Cause:

  • Parameter setting abnormality (Gear ratio, Error window).

  • Apparatus binding.

  • Drive abnormality.




Remedy:

  • Lower electric gear ratio [0x6091]. Adjust error window [0x6065] and timeout [0x6066].

  • Inspect apparatus for binding.

  • Replace drive if alarm persists.


AL-53

Excessive SPD deviation

Cause:

  • Motor/Encoder cable abnormality.

  • Parameter setting abnormality.

  • Apparatus binding or Limit contact sensor.




Remedy:

  • Replace motor/encoder cables.

  • Match Motor ID/Encoder settings to label. Lower gear ratio.

  • Inspect apparatus.


AL-56

Excessive position command

Cause:

  • Motor/Encoder cable abnormality.

  • Parameter setting abnormality.




Remedy:

  • Replace motor/encoder cables.

  • Match Motor ID/Encoder settings to label. Lower gear ratio.


AL-57

Excessive pulse output speed

Cause: Parameter setting abnormality.


Remedy:

  • Lower encoder output pulse [0x2422] setting.

  • Lower electric gear ratio [0x6091].


AL-63

Parameter checksum

Cause: O/S replacement (Variable parameters set to maximum).


Remedy: Restore default parameters (0x1011). Initialize and re-set parameters before operation.
AL-71

Factory setting

Cause: Parameter setting abnormality.


Remedy: Contact service center. Check drive capacity at [0x1008]. Reset drive capacity and download OS again.
W01

PWR_FAIL
(Main Power Phase Loss)

Cause:

  • Main power input voltage failure (L1, L2, L3).

  • Parameter setting abnormality.

  • Momentary power outage.




Remedy:

  • Re-inspect main power source (200-240 Vac).

  • Adjust main power fail check mode [0x2006].

  • Increase main power fail check time [0x2007].


W02

LOW_BATT
(Low Voltage of Encoder Battery)

Cause:

  • Parameter setting abnormality.

  • Defective battery connection.

  • Low battery voltage.




Remedy:

  • For incremental encoder usage, set [0x2005] to 1.

  • Connect battery accurately.

  • Replace battery if < 3.3V.


W03

SW_POS_LMT
(Software Position Limit)

Cause: Parameter setting abnormality.


Remedy: Change settings of software position limit function select [0x2400] or limit values [0x607D].
W10

OV_LOAD
(Operation Overload)

Cause:

  • Continuous operation with load exceeding rated value.

  • Motor brake abnormality.

  • Parameter setting abnormality.

  • Apparatus or Cable abnormality.




Remedy:

  • Check overload rate [0x2603]. Change motor/drive capacity or adjust gain.

  • Check motor brake.

  • Match Motor ID/Encoder settings.

  • Inspect apparatus and cables.


W20

SETUP
(Setting abnormality)

Cause:

  • Abnormal combination of drive and motor.

  • IO setting abnormality (Signal overlap).




Remedy:

  • Lower torque limit or replace motor/drive to match capacities.

  • Set IO parameters [0x2200]-[0x2212] correctly.


W40

UD_VTG
(Low Voltage)

Cause:

  • Main power input voltage abnormality (< 134 Vac).

  • DC link voltage low (< 190 Vdc).

  • Lowered power voltage during operation.




Remedy:

  • Re-inspect main power.

  • Replace drive if DC link voltage reading is incorrect.

  • Use 3-phase voltage supply.


W80

EMG
(Emergency Signal Input)

Cause: EMG contact abnormality.


Remedy: This represents emergency pause state. Check wiring and parameters [0x211F], [0x2200], [0x2205]. Set wiring and parameters for operation conditions.

How to Clear & Reset LS Electric iX7NH Servo Drive Faults

  1. Built-in Web Server: Connect to the drive’s Ethernet port using any standard web browser, open the embedded management console, and click “Alarm Clear / Reset” under the diagnostic status view.
  2. EtherCAT / Modbus TCP Controlword: In your PLC or motion master, transition Bit 7 (Fault Reset) from `0` to `1` in CiA402 Controlword object `0x6040` (or issue the Modbus TCP clear alarm command) while the servo is disabled.
  3. Digital Input Reset (CN1 ALRST): With the servo disabled (SV-OFF), apply a momentary pulse (minimum 120 ms) to the designated digital input pin assigned to ALRST (Alarm Reset) on the CN1 I/O interface.
  4. DriveCM PC Software / USB OTG: Connect your PC via the USB port using DriveCM configuration software, open the live monitoring status tab, and click “Fault Reset”. You can also view historical alarm trace files via the USB OTG memory port.
  5. Power Cycle: Disconnect both main AC line power and control power, wait at least 15 minutes until the charge lamp extinguishes completely, and re-energize the servo drive.
⚠️ High-Voltage Electrical Safety Warning: Always wait at least 15 minutes after disconnecting power until the internal charge lamp is completely unlit, and verify with a calibrated digital multimeter that the DC bus voltage measures strictly below 30VDC before inspecting servo motor cables, disconnecting encoder connectors, or touching power terminals on the LS Electric iX7NH drive.