LS Electric iE5 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the LS Electric iE5 (Starvert SV-iE5) micro industrial drive series. Search or filter through the complete fault code directory below.

Compact Micro VFD Power: 0.1 to 0.4 kW (0.125 to 0.5 HP) V/f Control & Built-in Potentiometer
Power Range 0.1 – 0.4 kW (0.125 – 0.5 HP)
Supply Voltage 200–230V AC (1-Ph / 3-Ph)
Control Modes V/F Control (Linear & Pattern)
Operator Interface Integrated LED Keypad & Potentiometer

Complete LS Electric iE5 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OCt, OVt, or GFt).

Fault Code and MeaningCause and Remedy
OCt

Overcurrent

Cause:

  • Accel/Decel time is too short compared to the inertia of the load (GD²).

  • Load is greater than the inverter rating.

  • Inverter output is issued when the motor is free running.

  • Output short circuit or ground fault has occurred.

  • Mechanical brake of the motor is operating too fast.




Remedy:

  • Increase the Accel/Decel time.

  • Replace the inverter with appropriate capacity.

  • Resume operation after stopping the motor or use P36 (Speed search).

  • Check output wiring.

  • Check the mechanical brake.


GFt / GCt

Ground fault current

Cause:

  • Ground fault has occurred at the output wiring of the inverter.

  • The insulation of the motor is damaged due to heat.




Remedy:

  • Check the wiring of the output terminal.

  • Replace the motor.


IOL / OLt

Inverter overload / Overload trip

Cause:

  • Load is greater than the inverter rating.

  • Torque boost scale is set too large.




Remedy:

  • Upgrade the capacity of motor and inverter or reduce the load weight.

  • Reduce torque boost scale.


OHt

Inverter overheat

Cause:

  • Cooling system has faults.

  • Ambient temperature is too high.




Remedy:

  • Check for alien substances clogged in the heat sink.

  • Keep ambient temperature under 40°C.


COL

Condenser overload

Cause:

  • 3-Phase product may have one phase lost.

  • Internal condenser was outworn.




Remedy:

  • Check whether wiring of input power or inter-phase voltage is abnormal.

  • It’s almost time to replace or it may happen when it is used in hot temperature for a long while. Contact after-sales service.


POt

Output Phase loss

Cause:

  • Faulty contact of magnetic switch at output.

  • Faulty output wiring.




Remedy:

  • Make connection of magnetic switch at output of the inverter securely.

  • Check output wiring.


OUt

Over voltage

Cause:

  • Decel time is too short compared to the inertia of the load (GD²).

  • Regenerative load is at the inverter output.

  • Line voltage is too high.




Remedy:

  • Increase the Decel time.

  • Check whether line voltage exceeds its rating.


LUt

Low voltage

Cause:

  • Line voltage is low.

  • Load larger than line capacity is connected to line (ex: welding machine, motor’s direct input).

  • Faulty magnetic switch at the input side of the inverter.




Remedy:

  • Check whether line voltage is below its rating.

  • Check the incoming AC line. Adjust the line capacity corresponding to the load.

  • Change a magnetic switch.


EtA / EtB

External fault A / B contact input

Cause:

  • The multi function terminals (P66 ~ P70) set to “18 (External fault-A)” or “19 (External trip signal input : fault-B)” in P66~P70 in PG Group is ON.




Remedy:

  • Eliminate the cause of fault at circuit connected to external fault terminal or cause of external fault input.


_ _ _ L

Lost Command

Cause:

  • No frequency command is applied to AI terminal.

  • Communication command is cut off.




Remedy:

  • Check the wiring of AI and frequency reference level.

  • In case of a program set to periodically update frequency, check the communication line or operation of master device.


EEP / HUt

Parameter save error / Hardware fault

Cause:

  • Hardware fault or First power-on after software upgrade.




Remedy:

  • Contact your local LSIS sales representative.

  • EEP message occurs when first allowing power after upgrading software due to A/S service. At the moment, turn it off and retry.


How to Clear & Reset LS Electric iE5 Drive Faults

  1. Keypad Reset: Press the red [STOP/RESET] key on the integrated front keypad when the fault code is flashing on the 4-digit 7-segment display.
  2. Multi-Function Input Reset (P1–P3): Pulse the external control terminal programmed for “Reset” (configurable via input parameters I17, I18, or I19 set to 3 / Reset).
  3. DriveView Software: On communication-equipped models, connect via RS-485 Modbus, launch LS DriveView software, and click “Fault Reset” on the main control panel.
  4. Modbus RTU Communication: Write a reset bit command over RS-485 serial communication registers to clear the active inverter trip condition remotely.
  5. Power Cycle: Disconnect incoming AC mains supply power, wait at least 5 minutes until the 7-segment display goes completely blank and internal capacitors discharge, then restore mains power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus voltage has dropped safely below 30VDC across terminals [P/+] and [N/-] (or motor output terminals U, V, and W) before inspecting wiring, removing terminal covers, or touching terminals on the LS Electric iE5 drive.