LS Electric iG5A Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the LS Electric Starvert iG5A compact industrial drive series. Search or filter through the complete fault code directory below.
Power Range
0.4 – 22 kW (0.5 – 30 HP)
Supply Voltage
1-Ph 200V / 3-Ph 200–230V & 380–480V
Control Modes
V/F & Sensorless Vector Control
Operator Interface
Integrated 7-Segment LED Keypad
Complete LS Electric iG5A Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type OC, OV, GF, or Overheat).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
OC1 Overcurrent The inverter turns off its output when the output current of the inverter flows more than the inverter rated current. | Cause:
Remedy:
|
OC2 Overcurrent 2 When IGBT’s Arm is short and output short occurs, the inverter turns off its output. | Cause:
Remedy:
|
GFT Ground fault current The inverter turns off its output when a ground fault occurs and the ground fault current is more than the internal setting value. | Cause:
Remedy:
|
IOL Inverter Overload The inverter turns off its output when the output current of the inverter flows more than the rated level (150% for 1 minute). | Cause:
Remedy:
|
OLT Overload trip The inverter turns off its output if the output current flows at 150% of rated current for more than the current limit time. | Cause:
Remedy:
|
OHT Inverter overheat The inverter turns off its output if the heat sink overheats due to a damaged cooling fan or an alien substance. | Cause:
Remedy:
|
POT Output Phase loss The inverter turns off its output when one or more of the output (U, V, W) phases are open. | Cause:
Remedy:
|
FAn Cooling fan fault Displayed when a fault condition occurs in the inverter cooling fan. | Cause:
Remedy:
|
OVT Over voltage DC voltage increases higher than 400V during deceleration or due to surge voltage. | Cause:
Remedy:
|
LVT Low voltage The inverter turns off its output if the DC voltage is below 180V. | Cause:
Remedy:
|
ETH Electronic Thermal The internal electronic thermal determines motor overheating. | Cause:
Remedy:
|
EtA External fault A contact input Inverter turns off output when external fault signal A (Normal Open) is received. | Cause:
Remedy:
|
EtB External fault B contact input Inverter turns off output when external fault signal B (Normal Close) is received. | Cause:
Remedy:
|
_ _ L Operating method lost Frequency command lost when set via Analog input or Communication. | Cause:
Remedy:
|
rErr Remote keypad communication error Inverter and remote keypad do not communicate with each other. | Cause:
Remedy:
|
nbr Brake control error Rating current flows below set value during break control. | Cause:
Remedy:
|
EEP / HWT / Err / COM / ntc System/Hardware Errors EEP: Parameter save error HWT: Hardware fault Err: Communication error COM: Keypad error ntc: NTC open | Cause:
Remedy:
|
How to Clear & Reset LS Electric iG5A Drive Faults
- Keypad Reset: Press the red STOP/RESET key on the front 7-segment loader keypad while the fault trip code is flashing.
- Digital Input Reset (RST): Configure any multi-function input terminal (P1 to P8 via parameters I17 to I24) to setting
3 (RST). Close the circuit between the assigned terminal and the CM common terminal to trigger a reset. - DriveView PC Software: Connect your PC via an RS-485 serial converter to the drive communication terminals, launch LS DriveView software, and execute a software trip reset directly from the monitor screen.
- RS-485 Modbus / LS Bus Network: Set Bit 3 (
Fault reset) from0to1in the inverter communication command register (address0x0006) over the built-in serial link. - Power Cycle: Disconnect AC input mains power, wait until the 7-segment display and internal charge LED turn off completely (allow at least 5–10 minutes for capacitor discharge), then restore power.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 30VDC across terminals [P] (or [P1]) and [N(-)] before opening wiring covers, checking connections, or servicing terminals U, V, and W on the LS Electric iG5A inverter.