LS Electric iP5A Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the LS Electric iP5A dedicated fan and pump inverter series. Search or filter through the complete fault code directory below.
Power Range
5.5 – 450 kW (7.5 – 600 HP)
Supply Voltage
3-Phase 200–230V / 380–480V
Control Modes
V/f Control & Sensorless Vector
Operator Interface
32-Character LCD Keypad / Loader
Complete LS Electric iP5A Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type Over Current, Over Voltage, or Low Voltage).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
Over Current 1 The inverter turns off its output when the output current of the inverter flows more than 200% of the inverter rated current. | Cause:
Remedy:
(Caution) Operating inverter prior to correcting fault may damage the IGBT. |
Ground Fault The inverter turns off its output when a ground fault occurs and the ground fault current is more than the internal setting value. | Cause:
Remedy:
|
Over Voltage The inverter turns off its output if the DC voltage of the main circuit increases higher than the rated value (during deceleration or regen). | Cause:
Remedy:
|
Over Load (Current Limit Protection). The inverter turns off its output if the output current flows at 120% of the rated current. | Cause:
Remedy:
|
Over Heat The inverter turns off its output if the heat sink is over heated. | Cause:
Remedy:
|
E-Thermal (Electronic Thermal). Internal calculation determines motor overheating. Overload capacity: 130% for 1 min. | Cause:
Remedy:
|
Ext. Trip User triggered external trip signal to stop output. | Cause: External Trip has occurred. Remedy:
|
Low Voltage DC voltage is below the detection level (insufficient torque or potential motor overheating). | Cause:
Remedy:
|
Over Current 2 IGBT Short or Output Short. | Cause:
Remedy:
|
Output Phase Open One or more of the output (U, V, W) phases is open. | Cause:
Remedy:
|
BX (Instant Cut Off). Used for emergency stop. | Cause: The BX terminal is turned ON. Remedy:
|
HW-Diag Inverter Hardware Fault (Control circuitry error). | Cause:
Remedy:
|
COM Error / CPU Error Inverter cannot communicate with the keypad. | Cause:
Remedy:
|
Inv. OLT Inverter Overload. Output current flows more than rated level (110% for 1 min, 130% for 4 sec). | Cause:
Remedy:
|
NTC open Inverter internal NTC is opened. | Cause: Inverter internal NTC circuit is open/damaged. Remedy:
|
LOP / LOR / LOV / LOI / LOX Operating Method when the Speed Reference is Lost. | Cause:
Remedy:
|
How to Clear & Reset LS Electric iP5A Drive Faults
- Keypad Reset: Press the red [STOP/RESET] key on the 32-character LCD loader keypad once the fault condition has been resolved.
- Terminal Reset (Multi-Function Input): Momentarily trigger any multi-function control input (M1 to M8) defined as 14 (RST / Fault Reset) in parameters I17 through I24.
- DriveView Software: Connect a PC using LS Electric DriveView monitoring software via RS-485 communication lines and trigger a software reset from the diagnostics window.
- Fieldbus Network: Write the fault reset bit in the drive command word via Modbus RTU, BACnet, LonWorks, or CC-Link communication interface cards.
- Power Cycle: Switch off the incoming 3-phase mains AC line power, wait until the LCD display turns off and the internal charge indicator lamp extinguishes completely (approx. 5 to 10 minutes), then restore power.
⚠️ High-Voltage Electrical Safety Warning:
Lethal residual charge remains in the DC link capacitors after main AC supply disconnection. Wait at least 5 to 10 minutes and verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 30VDC across terminals [P+] and [N-] before inspecting terminal connections or motor leads U, V, and W on the LS Electric iP5A drive.