LS Electric iP5A Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the LS Electric iP5A dedicated fan and pump inverter series. Search or filter through the complete fault code directory below.

Dedicated Fan & Pump Inverter Power: 5.5 to 450 kW (7.5 to 600 HP) Advanced Multi-Motor Control (MMC)
Power Range 5.5 – 450 kW (7.5 – 600 HP)
Supply Voltage 3-Phase 200–230V / 380–480V
Control Modes V/f Control & Sensorless Vector
Operator Interface 32-Character LCD Keypad / Loader

Complete LS Electric iP5A Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type Over Current, Over Voltage, or Low Voltage).

Fault Code and MeaningCause and Remedy

Over Current 1



The inverter turns off its output when the output current of the inverter flows more than 200% of the inverter rated current.

Cause:


  • Acceleration/Deceleration time is too short compared to the GD² of the load.

  • Load is larger than the inverter rating.

  • Inverter turns output on when the motor is free running.

  • Output short or ground fault has occurred.

  • Mechanical brake of the motor is operating too fast.

  • Components of the main circuit have overheated due to a faulty cooling fan.




Remedy:

  • Increase Accel/Decel time.

  • Increase inverter capacity.

  • Operate after motor has stopped.

  • Check output wiring.

  • Check mechanical brake operation.

  • Check cooling fan.


(Caution) Operating inverter prior to correcting fault may damage the IGBT.

Ground Fault



The inverter turns off its output when a ground fault occurs and the ground fault current is more than the internal setting value.

Cause:


  • Ground fault has occurred at the output wiring of inverter.

  • The insulation of the motor is damaged due to heat.




Remedy:

  • Investigate the output wiring of inverter.

  • Exchange motor.



Over Voltage



The inverter turns off its output if the DC voltage of the main circuit increases higher than the rated value (during deceleration or regen).

Cause:


  • Deceleration time is too short compared to the GD² of load.

  • Regenerative load at the output.

  • Line voltage high.




Remedy:

  • Increase deceleration time.

  • Use regenerative resistor option.

  • Check line voltage.



Over Load



(Current Limit Protection). The inverter turns off its output if the output current flows at 120% of the rated current.

Cause:


  • Load is larger than the inverter rating.

  • Incorrect inverter capacity selected.

  • Set incorrect V/F pattern.




Remedy:

  • Increase capacity of motor and inverter.

  • Select correct inverter capacity.

  • Select correct V/F pattern.



Over Heat



The inverter turns off its output if the heat sink is over heated.

Cause:


  • Cooling fan damaged or an alien substance inserted.

  • Cooling system has faults.

  • Ambient temperature high.




Remedy:

  • Exchange cooling fans and/or eliminate alien substance.

  • Check for alien substances in the heat sink.

  • Keep ambient temperature under 40°C.



E-Thermal



(Electronic Thermal). Internal calculation determines motor overheating. Overload capacity: 130% for 1 min.

Cause:


  • Motor has overheated.

  • Load is larger than inverter rating.

  • ETH level too low.

  • Incorrect inverter capacity selected.

  • Set incorrect V/F pattern.

  • Operated too long at low speeds.




Remedy:

  • Reduce load and/or running duty.

  • Increase inverter capacity.

  • Adjust ETH level to an appropriate level.

  • Select correct inverter capacity.

  • Select correct V/F pattern.

  • Install a cooling fan with a separate power supply.



Ext. Trip



User triggered external trip signal to stop output.

Cause:

External Trip has occurred.



Remedy:

  • Eliminate Trip at circuit connected to external trip terminal.

  • Remove external trip input.



Low Voltage



DC voltage is below the detection level (insufficient torque or potential motor overheating).

Cause:


  • Line voltage low.

  • Load larger than line capacity is connected to line (e.g., welding machine, large motor starting).

  • Faulty magnetic switch at the input side of the inverter.




Remedy:

  • Check line voltage.

  • Increase line capacity.

  • Exchange magnetic switch.



Over Current 2



IGBT Short or Output Short.

Cause:


  • Short has occurred between the upper and lower IGBT.

  • Short has occurred at the output of the inverter.

  • Acceleration/Deceleration time is too short compared to the GD² of load.




Remedy:

  • Check IGBT.

  • Check output wiring of inverter.

  • Increase acceleration time.



Output Phase Open



One or more of the output (U, V, W) phases is open.

Cause:


  • Faulty contact of magnetic switch at output.

  • Faulty output wiring.




Remedy:

  • Check magnetic switch at output of inverter.

  • Check output wiring.



BX



(Instant Cut Off). Used for emergency stop.

Cause:

The BX terminal is turned ON.



Remedy:

  • Turn the BX terminal OFF to return to regular operation.

  • Take caution when using this function.



HW-Diag



Inverter Hardware Fault (Control circuitry error).

Cause:


  • Wdog error (CPU fault).

  • EEP error (memory fault).

  • ADC Offset (current feedback circuit fault).

  • Input phase open.

  • NTC open.




Remedy:

  • Exchange inverter.



COM Error / CPU Error



Inverter cannot communicate with the keypad.

Cause:


  • Faulty connection between inverter and keypad.

  • Inverter CPU malfunction.




Remedy:

  • Check connector.

  • Exchange inverter.



Inv. OLT



Inverter Overload. Output current flows more than rated level (110% for 1 min, 130% for 4 sec).

Cause:


  • Load is larger than inverter rating.

  • Incorrect inverter capacity selected.




Remedy:

  • Increase motor and/or inverter capacity.

  • Select correct inverter capacity.



NTC open



Inverter internal NTC is opened.

Cause:

Inverter internal NTC circuit is open/damaged.



Remedy:

  • Contact the factory or your local distributor.



LOP / LOR / LOV / LOI / LOX



Operating Method when the Speed Reference is Lost.

Cause:


  • LOP: Loss of reference from the Option (DPRAM time out).

  • LOR: Remote communication network fault.

  • LOV: 'V1' analog frequency reference lost.

  • LOI: 'I' analog frequency reference lost.

  • LOX: Sub-board (V2, ENC) analog frequency reference lost.




Remedy:

  • Eliminate cause of fault (check connections/signals).


How to Clear & Reset LS Electric iP5A Drive Faults

  1. Keypad Reset: Press the red [STOP/RESET] key on the 32-character LCD loader keypad once the fault condition has been resolved.
  2. Terminal Reset (Multi-Function Input): Momentarily trigger any multi-function control input (M1 to M8) defined as 14 (RST / Fault Reset) in parameters I17 through I24.
  3. DriveView Software: Connect a PC using LS Electric DriveView monitoring software via RS-485 communication lines and trigger a software reset from the diagnostics window.
  4. Fieldbus Network: Write the fault reset bit in the drive command word via Modbus RTU, BACnet, LonWorks, or CC-Link communication interface cards.
  5. Power Cycle: Switch off the incoming 3-phase mains AC line power, wait until the LCD display turns off and the internal charge indicator lamp extinguishes completely (approx. 5 to 10 minutes), then restore power.
⚠️ High-Voltage Electrical Safety Warning: Lethal residual charge remains in the DC link capacitors after main AC supply disconnection. Wait at least 5 to 10 minutes and verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 30VDC across terminals [P+] and [N-] before inspecting terminal connections or motor leads U, V, and W on the LS Electric iP5A drive.