LS Electric iS7 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the LS Electric iS7 (Starvert SV-iS7) high-performance drive series. Search or filter through the complete fault code directory below.
Power Range
0.75 – 375 kW (1.0 – 500 HP)
Supply Voltage
200–230V / 380–480V (3-Phase)
Control Modes
V/F, Sensorless & Sensored Vector, PM
Operator Interface
Graphic LCD Keypad / 7-Segment
Complete LS Electric iS7 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type Over Current1, Over Voltage, or Ground Trip).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| Over Load Warning Message | Cause: Motor is overloaded (Operates when PRT-17 is set to "1"). Remedy:
|
| Under Load Warning Message | Cause: Motor is underloaded (Operates when PRT-25 is set to "1"). Remedy:
|
| Inv Over Load Warning Message | Cause: Accumulated overload time is equivalent to 60% of the inverter overheat protection (inverter IOLT) level. Remedy:
|
| Lost Command Warning Message | Cause: Lost Command warning alarm occurred based on condition set at PRT-13-15 (occurs even when PRT-12 is "0"). Remedy:
|
| Fan Warning Warning Message | Cause: Error detected from the cooling fan while PRT-79 is set to "1". Remedy:
|
| DB Warn %ED Warning Message | Cause: DB resistor usage rate exceeds the set value. Remedy:
|
| Enc Conn Check Warning Message | Cause: "3 (Enc Test)" is set at BAS-20 (Auto Tuning) and no signal is input during the encoder test. Remedy:
|
| Enc Dir Check Warning Message | Cause: "3 (Enc Test)" is set at BAS-20 and settings for A and B encoder phases are changed or opposite during test. Remedy:
|
| Lost Keypad Warning Message | Cause: Operating commands come from keypad or communication problem in Keypad JOG mode after setting PRT-11 to "0". Remedy:
|
| Check Line PLZ Warning Message | Cause: Problem with communication between the keypad and the iS7 Control CPU (control connection cables). Remedy:
|
| Fire Mode Warning Message | Cause: Fire function is activated. Remedy:
|
| PID Sleep Warning Message | Cause: Displayed in PID Sleep mode to distinguish from a stopped state. Remedy:
|
| AUX Power On Warning Message | Cause: Control power is supplied with the auxiliary power module (replaces Low Voltage trip when main power is off). Remedy:
|
| Over Load Fault Trip | Cause: The load is greater than the motor's rated capacity. Remedy:
Cause: The set value for the overload trip level (PRT-21) is too low. Remedy:
|
| Under Load Fault Trip | Cause: There is a motor-load connection problem. Remedy:
Cause: The set value for the underload level (PRT-29 and PRT-30) is less than the system's minimum load. Remedy:
|
| Over Current1 Fault Trip | Cause: Acc/dec time is too short compared to load inertia (GD2). Remedy:
Cause: The inverter load is greater than the rated capacity. Remedy:
Cause: The inverter supplied an output while the motor was idling. Remedy:
Cause: The mechanical brake of the motor is operating too fast. Remedy:
|
| Over Voltage Fault Trip | Cause: The deceleration time is too short for the load inertia (GD2). Remedy:
Cause: A generative load occurs at the inverter output. Remedy:
Cause: The input voltage is too high. Remedy:
|
| Low Voltage / Low Voltage2 Fault Trip | Cause: The input voltage is too low. Remedy:
Cause: A load greater than the power capacity is connected to the system (e.g. a welder, direct motor connection). Remedy:
Cause: The magnetic contactor connected to the power source has a faulty connection. Remedy:
|
| Ground Trip Fault Trip | Cause: A ground fault has occurred in the inverter output wiring. Remedy:
|
| E-Thermal Fault Trip | Cause: The set value for electronic thermal protection is too low. Remedy:
Cause: The inverter has been operated at a low speed for an extended period. Remedy:
Cause: The motor insulation is damaged. Remedy:
Cause: The motor has overheated. Remedy:
Cause: The inverter load is greater than the rated capacity. Remedy:
|
| Out Phase Open Fault Trip | Cause: The magnetic contactor on the output side has a connection fault. Remedy:
Cause: The output wiring is faulty. Remedy:
|
| In Phase Open Fault Trip | Cause: The magnetic contactor on the input side has a connection fault. Remedy:
Cause: The input wiring is faulty. Remedy:
Cause: The DC link capacitor needs to be replaced. Remedy:
|
| Inverter OLT Fault Trip | Cause: The load is greater than the rated motor capacity. Remedy:
Cause: The torque boost level is too high. Remedy:
|
| Over Heat Fault Trip | Cause: There is a problem with the cooling system. Remedy:
Cause: The inverter cooling fan has been operating for an extended period. Remedy:
Cause: The ambient temperature is too high. Remedy:
|
| Over Current2 Fault Trip | Cause: The output wiring has short-circuited. Remedy:
Cause: There is a fault with the electronic semiconductor (IGBT). Remedy:
|
| NTC Open Fault Trip | Cause: The ambient temperature is too low. Remedy:
Cause: There is a fault with the internal temperature sensor. Remedy:
|
| FAN Trip Fault Trip | Cause: There is a foreign object in the inverter vent where the fan is located. Remedy:
Cause: The cooling fan needs to be replaced. Remedy:
|
| IP54 FAN Trip Fault Trip | Cause: The fan connector is not connected. Remedy:
Cause: The power connector for the internal fan PCB board is not connected. Remedy:
Cause: The cooling fan needs to be replaced. Remedy:
|
| No Motor Trip Fault Trip | Cause: The motor is not connected to the inverter output. Remedy:
Cause: The current level for trip detection is not set properly. Remedy:
|
How to Clear & Reset LS Electric iS7 Drive Faults
- Keypad Reset: Press the red [STOP/RESET] key on the graphic LCD keypad or standard console display while the active fault information is shown.
- Multi-Function Input Reset (P1–P8): Trigger the terminal assigned to the “Reset” function (programmable via input parameters IN-65 through IN-72 set to 4 / Reset).
- DriveView Software: Connect your PC via the RS-485 Modbus terminal or loader interface, launch DriveView 7 / 9, and click “Fault Reset” in the main monitor window.
- Fieldbus / Network Reset: Write a reset command bit across your network protocol (Profibus-DP, Ethernet/IP, Modbus-TCP, or CANopen) via the communication control word.
- Power Cycle: Disconnect the incoming 3-phase AC supply line, wait at least 10 minutes until the charging indicator lamp turns off completely and the internal DC bus discharges, then reapply power.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that the DC bus intermediate circuit voltage measures strictly below 30VDC across terminals [P1/+] and [N/-] (or motor output terminals U, V, and W) before inspecting motor leads, opening terminal covers, or touching wiring terminals on the LS Electric iS7 drive.