LS Electric L7P Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, alarm causes, and step-by-step troubleshooting procedures for the LS Electric L7P pulse & indexing AC servo drive series. Search or filter through the complete fault code directory below.

AC Servo Drive (Pulse / Indexing) Power: 0.1 to 7.5 kW (100W to 7.5kW) Position, Speed & Torque Control
Power Range 0.1 – 7.5 kW (100W – 7.5kW)
Supply Voltage 200–230V / 380–480V AC
Control Modes Position (Pulse/Index), Speed, Torque
Operator Interface Integrated 7-Segment LED / Drive CM

Complete LS Electric L7P Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type AL-14, AL-21, or Overload).

Fault Code and MeaningCause and Remedy
AL-10

IPM fault
(Over current H/W)

Cause:

  • Motor cable error or short.

  • Encoder cable error or short.

  • Parameter setting error (Motor ID/Encoder type).




Remedy:

  • Check if wiring is incorrect or shorted; replace motor cable.

  • Check encoder wiring; replace encoder cable.

  • Verify Motor ID [0x2000] and Encoder type [0x2001] match motor label.


AL-14

Over current
(Over current S/W)

Cause:

  • Check motor phase resistor.

  • Machine part problem (conflict or binding).

  • Drive error.

  • Error by noise.




Remedy:

  • Perform Motor line resistance test (U-V, V-W, W-U should be several Ω or less); replace motor.

  • Check if there is binding in the equipment.

  • If alarm continues after servo on, replace drive.

  • Check FG wiring condition; match FG wire size with main circuit wire size.


AL-16

Current limit exceeded
(Over current H/W)

Cause:

  • Drive error.

  • Error by noise.




Remedy:

  • If alarm continues after servo on, replace drive.

  • Check method to improve noise of wiring/installation. check FG wiring.


AL-11

IPM temperature
(IPM overheating)

Cause:

  • Ambient temperature too high.

  • Continuous Overload alarm.

  • High-frequency operation of regenerative drive.

  • Drive setting direction error.

  • Drive error.




Remedy:

  • Check if surrounding temperature is over 50°C; lower temperature.

  • Check accumulated operate overload percentage [0x2603]; change drive/motor capacity or tune gain.

  • Check regenerative overload [0x2606]; adjust regeneration resistor setting [0x2009] or use external resistor.

  • Refer to wiring and connection manual.

  • If alarm continues, replace drive.


AL-15

Current offset

Cause:

  • Motor U/V/W phase current offset oversetting.

  • Drive error.




Remedy:

  • Check if U/V/W phase current offset [0x2015~0x2017] are 5% of rated current or higher; rerun adjusting phase current offset.

  • If alarm occurs continually after adjusting offset, replace drive.


AL-21

Continuous overload

Cause:

  • Sequent operating that exceeds rated load.

  • Motor brake error.




Remedy:

  • Check if driving load rate [0x2603] is below 100%; change drive/motor capacity or tune gain.

  • Check if motor brake is holding; provide supply power to motor brake.


AL-22

Drive temperature 1

Cause:

  • Ambient temperature.

  • Drive error.




Remedy:

  • Check if surrounding temperature is over 50°C.

  • Check if displayed value [0x260B] differs significantly from surrounding temp; replace drive.


AL-23

Regeneration overload

Cause:

  • Capacity excess by high frequency or continuous regenerative operation.

  • Parameter setting error.

  • Main power input voltage error.

  • Drive error.




Remedy:

  • Check overload rate [0x2606]; Adjust value on 0x2009 or use braking resistor.

  • Check setting value [0x2009] ~ [0x200E].

  • Check if main power voltage is over 544V; recheck power supply.

  • Check temperature of regenerative resistance; replace drive if faulty.


AL-24

Motor cable open

Cause:

  • Parameter setting error.

  • Motor cable error (disconnected).

  • Motor error (short circuit).

  • Drive error.




Remedy:

  • Check [0x2015] offset current; process phase current offset control.

  • Check if cable is disconnected; replace motor cable.

  • Check short circuit (U,V,W); replace motor.

  • If alarm persists, replace servo drive.


AL-25

Drive temperature 2

Cause:

  • Ambient temperature.

  • Drive error.




Remedy:

  • Check if surrounding temperature is over 50°C.

  • Check if displayed value 2 [0x260C] is correct; replace drive.


AL-30

Encoder communication

Cause:

  • Encoder cable error.

  • Parameter setting Error.




Remedy:

  • Check for disconnection/short; replace encoder cable.

  • Ensure [0x2001], [0x2002] matches motor label information.


AL-31

Encoder cable open

Cause:

  • Encoder error.




Remedy:

  • If alarm continues after servo on, replace drive or servo motor.


AL-32

Encoder data

Cause:

  • Drive error.




Remedy:

  • If alarm continues after servo on, replace drive.


AL-33

Motor setting
(Motor ID setting error)

Cause:

  • Setting Motor ID error.

  • Drive error.




Remedy:

  • Ensure value of [0x2000] is same as application motor label; power off/on after adjusting.

  • If alarm continues after servo on, replace drive.


AL-34

Z Phase open

Cause:

  • Parameter setting error (Mask settings).

  • Encoder cable error.

  • Encoder error.

  • Drive error.




Remedy:

  • For motors without phase Z, mask AL-34 by setting 14th bit of [0x2014].

  • Wiring incorrect or short; replace encoder cable.

  • If alarm continues, replace drive.


AL-35

Low battery

Cause:

  • Parameter setting Error (Absolute vs Incremental).

  • Poor battery contact or not connected.

  • Battery voltage is low (< 3.3V).




Remedy:

  • Check absolute value encoder [0x2005] setting.

  • Connect battery rightly.

  • Replace battery.


AL-36

Sinusoidal ENC frequency

Cause:

  • Encoder cable error (wiring/shield).

  • Parameter setting error.

  • Drive error.




Remedy:

  • Check shield and FG disconnect; replace encoder cable.

  • Check encoder type [0x2001]; Check speed command up to 250kHz.

  • If alarm continues, replace drive.


AL-37

Sinusoidal ENC frequency
(Converter error)

Cause:

  • Converter error.

  • Encoder error.




Remedy:

  • If alarm continues after servo on, replace drive.


AL-38

Encoder setting error

Cause:

  • Drive / Motor combination error.

  • Encoder cable error.

  • Encoder error.

  • Drive error.




Remedy:

  • Check brand label code; use motor and drive of same brand.

  • Wiring incorrect or short; replace encoder cable.

  • If alarm continues, replace drive.


AL-39

Preset Error

Cause:

  • Parameter setting Error (Abs encoder value).

  • Poor battery contact.

  • Initial encoder power supply.




Remedy:

  • Check [0x2005] setting.

  • Connect battery correctly, reset alarm, reapply power. Check mechanical home.

  • Occurs when power applied after first connection; reset alarm and check home.


AL-40

Under voltage

Cause:

  • Main power input voltage error (Low).

  • Running when power voltage is low.




Remedy:

  • Check if main power is over 134[Vac].

  • Check [0x2605] is over 190 [Vdc].

  • Use 3 phase as supply voltage.


AL-41

Over voltage

Cause:

  • Main power input voltage error (High).

  • When braking resistor is high.

  • Setting value of acceleration/deceleration.

  • Drive error.




Remedy:

  • Check if main power is below 286[Vac]. Check [0x2605] below 405[Vdc].

  • Review regenerative resistance condition.

  • Set longer acceleration / deceleration time.

  • If alarm continues, replace drive.


AL-42

Main power fail

Cause:

  • Main power input voltage error (Phase loss).

  • Parameter setting Error (Input mode).

  • Momentary power failure.

  • Drive error.




Remedy:

  • Check voltage between phases (200-230V).

  • Wire or set parameter [0x2006] for correct input power (possibly 3 phase).

  • Check [0x2007] setting.

  • If alarm continues, replace drive.


AL-43

Control power fail

Cause:

  • Voltage between phase of C1, C2 error.

  • Drive error.




Remedy:

  • Check voltage between phases C1, C2 is within 200-230[Vac].

  • If alarm continues, replace drive.


AL-50

Over speed limit

Cause:

  • Motor or Encoder cable error.

  • Parameter setting Error (Motor label/Gain).

  • Encoder error.




Remedy:

  • Check wiring; replace cable.

  • Modify parameter [0x2000], [0x2001] to match label.

  • Set Electronic gear ratio low [0x6091] or readjust gain [0x2100].

  • If alarm continues, replace drive.


AL-51

POS following

Cause:

  • Parameter setting Error.

  • Machine part has problem.

  • Drive error.




Remedy:

  • Check [0x6091] gear ratio. Check [0x6066] position error excess time.

  • Check if machine was forced by drive part.

  • If alarm continues, replace drive.


AL-53

Excessive SPD deviation

Cause:

  • Motor or Encoder cable error.

  • Parameter setting Error.

  • Machine part has problem.

  • Encoder or Drive error.




Remedy:

  • Check wiring; replace cables.

  • Check [0x2000] matches motor label. Check gear ratio [0x6091].

  • Check operating condition of limit contact point sensor.

  • If alarm continues, replace drive.


AL-63

Parameter checksum

Cause:

  • When O/S is changed.

  • Drive error.




Remedy:

  • Restore initial parameter (0x1011). Set up parameter before operating.

  • If alarm continues, replace drive.


AL-71

Factory setting

Cause:

  • Parameter setting error.




Remedy:

  • Contact service center. Check [0x1008] DeviceName.

  • Download OS or set capacity of drive again.


W01

PWR_FAIL
(Main power source loss)

Cause:

  • Main power input Voltage error.

  • Parameter setting error.

  • Momentary power failure.




Remedy:

  • Check voltage between phase 200-230[Vac] of L1, L2, L3.

  • Check main power input mode [0x2006].

  • Check actual main power or increase value of checking time.


W02

LOW_BATT
(Low voltage of encoder battery)

Cause:

  • Parameter setting error (Absolute encoder).

  • Bad connection of battery.

  • Battery voltage low.




Remedy:

  • Set [0x2005] to "1" if using ABS encoder as incremental.

  • Connect battery rightly.

  • Replace battery (> 3.3V).


W04

SW_POS_LMT
(Software Position Limit)

Cause:

  • Parameter setting error (Software restriction).




Remedy:

  • Change value of software position limit [0x2400] or limit value [0x607D].


W10

OV_LOAD
(Operation overload)

Cause:

  • Sequent operating that exceed rated load.

  • Motor brake error.




Remedy:

  • Check overload warning level [0x2010] and accumulated rate [0x2603]. Tune gain or change capacity.

  • Check if motor brake is holding.


W20

SETUP
(Drive/Motor Combination error)

Cause:

  • Parameter setting error (Motor ID/Encoder type).

  • Machine part status Error.

  • Motor/Encoder cable error.




Remedy:

  • Modify parameter [0x2000], [0x2001], [0x2002] to match label.

  • Check machine part.

  • Replace motor/encoder cable.


W40

UD_VTG
(Low Voltage)

Cause:

  • Main power input voltage error (Low).

  • Running when power voltage is low.




Remedy:

  • Check if main power > 134[Vac]. DC link [0x2605] between 190~405[Vdc].

  • Use 3 phase as supply voltage.


W80

EMG
(Emergency signal input)

Cause:

  • EMG contact error.




Remedy:

  • Emergency stop by EMG contact. Check [0x211F], [0x2200].


How to Clear & Reset LS Electric L7P Drive Faults

  1. Front Panel Reset: Use the front operator pushbuttons (Mode/Set) to navigate to the alarm reset parameter or clear alarm status directly from the 7-segment display.
  2. Digital Input Reset (Alarm Reset): Assert the external digital input terminal assigned to the AL_RST (Alarm Reset) function on the CN1 I/O connector.
  3. Drive CM PC Software: Connect via the USB mini-B interface or RS-422/485 serial port, launch the Drive CM software, and click the “Alarm Reset” button in the status monitor.
  4. RS-422 / Modbus RTU Communication: Send an alarm reset command bit over serial communication using standard Modbus RTU or object dictionary commands via the CN3/CN4 communication ports.
  5. Power Cycle: Shut off both main AC power (L1, L2, L3) and control power (C1, C2), wait at least 15 minutes until the charge lamp turns completely off and intermediate capacitors discharge, then restore power.
⚠️ High-Voltage Electrical Safety Warning: Always ensure both main power (L1, L2, L3) and control power (C1, C2) are disconnected, and wait at least 15 minutes until the internal charge lamp extinguishes completely. Verify that residual DC bus voltage has dropped below 30VDC using a calibrated multimeter before touching power terminals (U, V, W or B+, B, BI) or servicing the LS Electric L7P drive.