LS Electric M100 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the LS Electric LSLV-M100 micro inverter series. Search or filter through the complete fault code directory below.
Power Range
0.1 – 2.2 kW (0.125 – 3.0 HP)
Supply Voltage
1-Ph 100–120V & 200–240V AC
Control Modes
V/F Control with Slip Compensation
Operator Interface
Built-in LED Keypad & Potentiometer
Complete LS Electric M100 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type OC, OV, LU, or Overheat).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
OLt Over Load (Latch Trip) Displayed when the motor overload trip is activated and the actual load level exceeds the set level. Operates when Pr20 is set to a value other than 0. | Cause:
Remedy:
|
OCt Over Current (Latch Trip) Displayed when inverter output current exceeds 200% of the rated current. | Cause:
Remedy:
|
Ovt Over Voltage (Latch Trip) Displayed when internal DC circuit voltage exceeds the specified value. | Cause:
Remedy:
|
Lvt Low Voltage (Level Trip) Displayed when internal DC circuit voltage is less than the specified value. | Cause:
Remedy:
|
GFt Ground Trip (Latch Trip) Displayed when a ground fault trip occurs on the output side of the inverter. | Cause:
Remedy:
|
EtH E-Thermal (Latch Trip) Displayed based on inverse time-limit thermal characteristics to prevent motor overheating. | Cause:
Remedy:
|
OPO Out Phase Open (Latch Trip) Displayed when a 3-phase inverter output has one or more phases in an open circuit condition. | Cause:
Remedy:
|
IOL Inverter OLT (Latch Trip) Displayed when the inverter has been protected from overload and resultant overheating. | Cause:
Remedy:
|
OHt Over Heat (Latch Trip) Displayed when the temperature of the inverter heat sink exceeds the specified value. | Cause:
Remedy:
|
ntC NTC Open (Latch Trip) Displayed when an error is detected in the temperature sensor of the IGBT. | Cause:
Remedy:
|
FAn Fan Trip (Latch Trip) Displayed when an error is detected in the cooling fan. | Cause:
Remedy:
|
rOt Relay Open Trip (Fatal Trip) Displayed when the input power is unstable or an initial charging circuit trip occurs. | Cause:
Remedy:
|
How to Clear & Reset LS Electric M100 Drive Faults
- Keypad Reset: Press the red STOP/RESET key on the integrated front keypad while the trip code is flashing on the 7-segment display.
- Multi-Function Terminal Reset (RST): On Advanced I/O models, terminal P4 is configured by default as
RESET(or assign any input P1–P5 via parameters In.65–In.69 to setting3: RST). Close the contact between the assigned terminal and the CM terminal to reset the trip. - DriveView PC Software: Connect your PC via an RJ45-to-RS-485 interface to the drive, open the LS DriveView commissioning software, and click “Reset” in the inverter monitoring window.
- Modbus RTU / LS INV Communication: Set Bit 3 (
Fault reset) from0to1in the inverter command register (address0x0006) across the integrated RS-485 communication link. - Power Cycle: Disconnect AC line input power, wait at least 5 minutes until the LED keypad display and power indicators are completely dark, then reapply power to clear non-persistent trips.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 30VDC across terminals [B1/P+] and [N(-)] before inspecting terminal connections, wiring motor leads, or touching terminals U, V, and W on the LS Electric LSLV-M100 inverter.