Mitsubishi FR-B-750 drive

Home / Mitsubishi / Mitsubishi FR-B-750 drive

Mitsubishi FR-B-750 Drive Fault Codes & Diagnostic Guide

Complete fault code directory, protective trip definitions, cause analysis, and step-by-step troubleshooting procedures for the Mitsubishi Electric FR-B-750 explosion-proof motor driving inverter.

Explosion-Proof Motor Inverter Power Rating: 0.75 kW (1.0 HP) Variable Torque / Soft-PWM Control
Motor Capacity 0.75 kW (1.0 HP)
Supply Voltage 3-Ph 200–240V / 380–480V AC
Control Modes Soft-PWM / V/F Variable Torque
Operator Interface FR-DU04/07 Panel & FR-PU04/07

Complete Mitsubishi FR-B-750 Drive Fault Code Directory

Use the search box in the table below to quickly find your alarm code (e.g., type E.OC1, E.OV1, E.THT, or Overcurrent).

Fault Code and MeaningCause and Remedy

E.OC1

Overcurrent shut-off during acceleration

Cause: When the inverter output current reaches or exceeds approximately 200% of the rated current during acceleration.


Check points: Check for sudden acceleration, output short circuit, or if main circuit power (R, S, T) is supplied.

Remedy:

  • Increase the acceleration time.

  • If "E.OC1" is always lit at a start, disconnect the motor once and then start the inverter. If "E.OC1" is still lit, contact your sales representative.

  • Supply main circuit power (R, S, T).



E.OC2

Overcurrent shut-off during constant speed

Cause: When the inverter output current reaches or exceeds approximately 200% of the rated current during constant speed.


Check points: Check for sudden load change or output short circuit.

Remedy:

  • Keep load stable.



E.OC3

Overcurrent shut-off during deceleration

Cause: When the inverter output current reaches or exceeds approximately 200% of the rated current during deceleration.


Check points: Check for sudden speed reduction, output short circuit, or too fast operation of motor's mechanical brake.

Remedy:

  • Increase the deceleration time.

  • Check mechanical brake operation.



E.OV1

Regenerative overvoltage shut-off during acceleration

Cause: Regenerative energy causes the inverter's internal main circuit DC voltage to reach or exceed the specified value. It may also be activated by a surge voltage generated in the power supply system.


Check points: Check for too slow acceleration.

Remedy:

  • Decrease the acceleration time.



E.OV2

Regenerative overvoltage shut-off during constant speed

Cause: Regenerative energy causes internal main circuit DC voltage to exceed specified value (or surge voltage).


Check points: Check for sudden load change.

Remedy:

  • Keep load stable.

  • Use the brake unit or power return converter (FR-RC) as required.



E.OV3

Regenerative overvoltage shut-off during deceleration or stop

Cause: Regenerative energy causes internal main circuit DC voltage to exceed specified value (or surge voltage).


Check points: Check for sudden speed reduction.

Remedy:

  • Increase the deceleration time. (Set the deceleration time which meets load GD²).

  • Decrease the braking duty.

  • Use the brake unit or power return converter (FR-RC) as required.



E.THM

Motor overload shut-off (electronic overcurrent protection)

Cause: Motor overheat due to overload or reduced cooling capability during constant-speed operation. (Pre-alarm occurs at 85% of preset value).


Check points: Check the motor for use under overload.

Remedy:

  • Reduce the load weight.

  • For a constant-torque motor, change the Pr. 71 setting to the constant-torque motor setting.



E.THT

Inverter overload shut-off (electronic overcurrent protection)

Cause: Current of more than 150% of the rated output current flows. Inverse-time characteristics activate protection to protect output transistors.


Check points: Check the motor for use under overload.

Remedy:

  • Reduce the load weight.



E.IPF

Instantaneous power failure protection

Cause: A power failure occurred for longer than 15ms.


Check points: Find the cause of instantaneous power failure occurrence.

Remedy:

  • Remedy the instantaneous power failure.

  • Prepare a backup power supply for instantaneous power failure.

  • Set the function of automatic restart after instantaneous power failure.


E.UVT

Undervoltage protection

Cause:

Power supply voltage reduces below 150V (about 300V for the 400V class). Large-capacity motor start causing voltage dip. Jumper not connected across P-P1.


Remedy:


  • Check the power supply system equipment.

  • Connect a jumper or DC reactor across terminals P-P1.


E.FIN

Fin overheat

Cause:

Cooling fin overheats (sensor actuated). Too high ambient temperature or cooling fin clogging.


Remedy:


  • Set the ambient temperature to within the specifications.

  • Clean the cooling fins.


E.GF

Output side ground fault overcurrent protection

Cause:

Ground fault overcurrent flows due to a ground fault in the inverter's output side (load side). Check for ground fault in motor or connection cable.


Remedy:


  • Remedy the ground fault portion.


E.OHT

OH Fault (External thermal relay operation)

Cause:

External thermal relay or internal motor temperature relay switched on (contacts open). Motor overheating. Incorrect setting of Pr. 180 to Pr. 186.


Remedy:


  • Reduce the load and operating duty.

  • Check Pr. 180 to Pr. 186 settings.


E.BE

Br. Cct. Fault (Brake transistor alarm detection)

Cause:

Brake circuit fault due to damaged brake transistors. Load GD² is too high or improper braking usage frequency.


Remedy:


  • Change the inverter.

  • Reduce load GD².


E.OLT

Stall prevention (Still Prev STP)

Cause:

Running frequency fell to 0 because stall prevention was activated. Motor used under overload.


Remedy:


  • Reduce the load weight.


E.OPT

Option Fault

Cause:

Dedicated option setting error or connection fault. High power factor converter connection set but AC power supplied to R, S, T. Loose connector.


Remedy:


  • Connect the plugged-in option securely.

  • Contact your sales representative.


E.OP1 to OP3

Option slot alarm 1 to 3

Cause:

Functional alarm in the plug-in option (e.g. communication alarm). Wrong option function setting or operation.


Remedy:


  • Confirm the option function setting, etc.


E.PE

Corrupt Memory (Parameter storage device alarm)

Cause:

Fault in the E²PROM device. Too many parameter write times.


Remedy:


  • Contact your sales representative.


E.PUE

PU Leave Out (Parameter unit disconnection)

Cause:

Communication between inverter and PU suspended/disconnected. Loose fitting of DU or PU. Pr. 75 setting issue.


Remedy:


  • Fit the DU and PU securely.


E.RET

Retry No Over (Retry count exceeded)

Cause:

Operation could not be resumed within the set number of retries.


Remedy:


  • Eliminate the cause of the error preceding this indication.


E.LF

Output phase failure protection

Cause:

One of the three phases (U, V, W) on the output side is open. Rated motor current is extremely lower than rated inverter current. Loose wiring.


Remedy:


  • Check the cables properly.

  • Check the setting of Pr. 251.


E.CPU

CPU Fault

Cause:

Arithmetic operation of the built-in CPU does not end within a predetermined period.


Remedy:


  • Make connection securely.

  • Contact your sales representative.


E.6 / E.7

Fault 6 / Fault 7 (CPU error)

Cause:

Arithmetic operation of peripheral circuit failed or receive data error in built-in CPU. Loose connector.


Remedy:


  • Make connection securely.

  • Contact your sales representative.


E.P24
24VDC power output short circuit

Cause: Check for a short circuit in the PC terminal output.



Remedy:


Remedy the short circuit portion.
E.CTE
Operation panel power supply short circuit

Cause: Check for a short circuit in the PU connector cable.



Remedy:


Check the PU and cable.
E.MB1 to 7
Brake sequence error

Cause: Find the cause of alarm occurrence.



Remedy:


Perform parameter setting check and wiring properly.
FN
Fan fault

Cause: Check the cooling fan for a fault.



Remedy:


Change the fan.
OL
Stall prevention (Over current)

Cause: Check the motor for use under overload.



Remedy:


The acceleration time may change. Increase the stall prevention operation level using Pr. 22 "stall prevention operation level" or make the stall prevention inoperative using Pr. 156 "stall prevention operation selection".
oL
Stall prevention (overvoltage)

Cause: Check for sudden speed reduction.



Remedy:


The deceleration time may change. Increase the deceleration time using Pr. 8 "deceleration time".
PS
PU stop

Cause: Check for a stop made by pressing the STOP key of the operation panel.



Remedy:


Refer to page 98.
Err.
Operation Error

Cause: This alarm appears if:

  • The RES signal is on.

  • You attempted to set any parameter value in the external operation mode.

  • You attempted to change the operation mode during operation.

  • You attempted to set any parameter value outside its setting range.

  • Normal communication cannot be made between the PU and inverter.

  • You attempted to make parameter setting when Pr. 77 "parameter write disable selection" has been set to disable parameter write.




Remedy:


Perform operation correctly.

How to Clear & Reset Mitsubishi FR-B-750 Drive Faults

  1. Keypad Reset: Press the red STOP / RESET key directly on the operation panel (FR-DU04/07) or parameter unit (FR-PU04/07) while the inverter is in a trip condition. Parameter Pr. 75 (Reset selection / PU stop selection) dictates reset behavior in external or communication modes.
  2. Terminal Input Reset (RES): Turn ON external control terminal RES by connecting it to terminal SD (Sink logic) or PC (Source logic) for at least 0.1 seconds, then disconnect/reopen the contact.
  3. Serial Communication (RS-485): Send an inverter fault reset command bit over the PU connector or serial communication interface using the Mitsubishi computer link protocol.
  4. PC Diagnostics: When safe communication wiring is routed to the safe area, use Mitsubishi FR Configurator via the serial communication port to execute an inverter soft reset.
  5. Power Cycle: Disconnect the primary AC input power, wait until the red front-panel CHARGE LED and operation panel display turn off completely (approx. 10 minutes), then restore AC mains power.
⚠️ Hazardous Area & High-Voltage Electrical Safety Warning: The FR-B-750 inverter is designed specifically to drive pressure-resistant explosion-proof motors, but the inverter unit itself does not have an explosion-proof construction and must strictly be installed in a non-hazardous, safe area outside explosive atmospheres. Always disconnect mains power and wait at least 10 minutes until the CHARGE lamp is completely unlit. Confirm that intermediate DC voltage across terminals [P/+] and [N/-] is strictly below 30 VDC before inspecting wiring or touching motor leads U, V, and W.