Mitsubishi FR-CS80 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, protective trip explanations, root causes, and step-by-step troubleshooting procedures for the Mitsubishi Electric FR-CS80 compact micro inverter series.
Power Range
0.1 – 15 kW (1/8 – 20 HP)
Supply Voltage
1-Ph 200V / 3-Ph 200–240V / 380–480V
Control Modes
V/F & Adv. Magnetic Flux Vector
Operator Interface
Integrated 4-Digit Display & M Dial
Complete Mitsubishi FR-CS80 Drive Fault Code Directory
Use the search box in the table below to quickly find your alarm code (e.g., type E.OC1, E.OV1, E.THT, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| HOLD Operation panel lock | Cause: Operation lock is set. Operation other than STOP/RESET is invalid. Remedy:
|
| LOCD Parameter locked | Cause: Password function is active. Display and setting of parameters are restricted. Remedy:
|
| Er1 Write disable error | Cause: Parameter setting was attempted while Pr.77 is set to disable write, or overlapping ranges set for frequency jump/adjustable 5 points V/F. The PU and inverter may not be communicating normally. Remedy:
|
| Er2 Write error during operation | Cause: Parameter write was attempted while Pr.77 Parameter write selection = "0". Remedy:
|
| Er3 Calibration error | Cause: Analog input bias and gain calibration values are set too close. Remedy:
|
| Er4 Mode designation error | Cause: Parameter setting is attempted in the External or NET operation mode when Pr.77 = "1", or when the command source is not at the operation panel. Remedy:
|
| Err. (Error) | Cause: The RES signal is turned ON, or voltage at the input side of the inverter has dropped. Remedy:
|
| OLC (FR-LU08: OL) Stall prevention (overcurrent) | Cause: When the output current of the inverter increases, the stall prevention function is activated. This stops the increase (during accel) or decreases frequency (during constant speed/decel) to prevent an overcurrent trip. Remedy:
|
| OLV (FR-LU08: oL) Stall prevention (overvoltage) | Cause: When the output voltage increases, the stall prevention function is activated. The regeneration avoidance function may be activated due to excessive regenerative power. Remedy:
|
| TH Electronic thermal O/L relay pre-alarm | Cause: Appears if the cumulative value of the electronic thermal O/L relay reaches 85% of the preset level of Pr.9. Remedy:
|
| PS PU stop | Cause: The motor is stopped using STOP/RESET under a mode other than PU operation mode (if Pr.75 is set to allow this), or by the emergency stop function. Remedy:
|
| UV Undervoltage | Cause: Power supply voltage of the inverter decreased to about 115 VAC (200V class) or 230 VAC (400V class) or below. Remedy:
|
| IH Inrush current limit resistor overheat | Cause: The inrush current limit resistor (PTC thermistor) is overheated due to frequent power ON/OFF cycling. Remedy:
|
| ED Emergency drive in operation | Cause: Emergency drive operation is performed by turning ON the X84 signal. Remedy: The display is cleared when the emergency drive operation ends. |
| E.OC1 Overcurrent trip during acceleration | Cause:
Remedy:
|
| E.OC2 Overcurrent trip during constant speed | Cause:
Remedy:
|
| E.OC3 Overcurrent trip during deceleration or stop | Cause:
Remedy:
|
| E.OV1 Regenerative overvoltage trip during acceleration | Cause:
Remedy:
|
| E.OV2 Regenerative overvoltage trip during constant speed | Cause:
Remedy:
|
| E.OV3 Regenerative overvoltage trip during deceleration or stop | Cause:
Remedy:
|
| E.THT Inverter overload trip (electronic thermal O/L relay function) | Cause:
Remedy:
|
| E.THM Motor overload trip (electronic thermal O/L relay function) | Cause:
Remedy:
|
| E.FIN Heatsink overheat | Cause:
Remedy:
|
| E.UVT Undervoltage | Cause:
Remedy:
|
| E.ILF Input phase loss | Cause:
Remedy:
|
| E.OLT Stall prevention stop | Cause: Output frequency has fallen to 1 Hz by stall prevention operation and remains for 3 seconds. Check if the motor is not used under overload. Remedy:
|
| E.GF Output side earth (ground) fault overcurrent | Cause: Earth (ground) fault overcurrent flows due to an earth fault on the inverter's output side. Check for a ground fault in the motor and connection cable. Remedy:
|
| E.LF Output phase loss | Cause: One of the three phases (U, V, W) on the inverter's output side is lost. Check wiring and that motor capacity is not smaller than inverter. Remedy:
|
| E.OHT External thermal relay operation | Cause: External or internal thermal relay switches ON (contacts open). Check for motor overheating. Check Pr.178 to Pr.182 settings. Remedy:
|
| E.PE6 Internal storage device fault | Cause: Writing data failed due to power-OFF or data fault during parameter operations. Check if power was turned OFF during operations. Remedy:
|
| E.PE / E.PE2 Parameter storage device fault (Corrupt Memory) | Cause: A fault occurred in the stored parameters (EEPROM failure). Check for too many parameter write times. Remedy:
|
| E.PUE PU disconnection | Cause: Communication between inverter and PU is suspended/disconnected. Check that PU is connected properly and Check Pr.75. Remedy:
|
| E.RET Retry count excess | Cause: Operation cannot be resumed properly within the number of retries set in Pr.67. Find the cause of the fault occurrence. Remedy:
|
| E.CPU / E.5 CPU fault | Cause: Communication fault of the built-in CPU. Check for devices producing excess electrical noises around the inverter. Remedy:
|
| E.CDO Abnormal output current detection | Cause: Output current exceeds Pr.150 level. Check settings of Pr.150, Pr.151, and Pr.167. Remedy:
|
| E.IOH Inrush current limit circuit fault | Cause: Resistor of inrush current limit circuit is overheated or faulty. Check that frequent power ON/OFF is not repeated. Remedy:
|
| E.ICF Input monitoring fault | Cause: Input signal does not turn ON/OFF within time set in Pr.242. Check for input signal loss or device failure. Remedy:
|
| E.LCI 4 mA input fault | Cause: Analog input current is 2 mA or less. Check for break in wiring or Pr.778 setting. Remedy:
|
| E.E10 Inverter output fault | Cause: Fault on inverter output side while Pr.631 is active. Check for ground fault in motor/cable. Remedy:
|
| E.0 No fault history | Cause: Appears when no fault records are stored. Remedy:
|
How to Clear & Reset Mitsubishi FR-CS80 Drive Faults
- Keypad Reset: Press the red STOP / RESET key directly on the integrated front operation panel while the drive is faulted. Parameter Pr. 75 (Reset selection / PU stop selection) configures reset permissibility under different control modes.
- Terminal Input Reset (RES): Turn ON the external terminal RES by closing contact to terminal SD (Sink logic) for at least 0.1 seconds, then reopen the connection.
- FR Configurator2 PC Software: Connect via the RS-485 communication terminal block using an RS-485 to USB converter, launch Mitsubishi FR Configurator2, and trigger the “Fault Reset” instruction.
- Serial Communication (Modbus RTU): Write a fault reset bit command (Bit 1 or Bit 7 depending on communication mode settings) across the built-in RS-485 Modbus RTU interface.
- Power Cycle: Disconnect AC input mains power, wait until the LED display and internal charge light completely turn off (allow at least 10 minutes for full capacitor discharge), and restore mains power.
⚠️ High-Voltage Electrical Safety Warning:
Lethal residual voltage remains inside intermediate DC bus capacitors after main AC power removal. Wait at least 10 minutes after turning OFF mains supply, verify that the operation panel LED display is completely dark, and measure DC voltage across terminals [P/+] and [N/-] with a multimeter to ensure it reads below 30 VDC before inspecting wiring or touching terminal terminals U, V, and W.