Mitsubishi FR-D700 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Mitsubishi FR-D700 compact micro-inverter series. Search or filter through the complete fault code directory below.

Compact Micro Drive Series Power: 0.1 to 15 kW (0.125 to 20 HP) Advanced Magnetic Flux Vector Control
Power Range 0.1 – 15 kW (0.125 – 20 HP)
Supply Voltage 1-Ph 100/200V, 3-Ph 200/400V
Control Modes Advanced Magnetic Flux Vector, V/F
Operator Interface Integrated Dial Panel / FR-PU07

Complete Mitsubishi FR-D700 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type E.OC1, E.OV1, or E.THM).

Fault Code and MeaningCause and Remedy
HOLD

Operation panel lock

Cause: Operation has been attempted during the operation panel lock.


Remedy:

Press MODE for 2s to release the lock.
LOCd

Password locked

Cause: Reading/writing of a password-restricted parameter has been attempted.


Remedy:

Enter the password in Pr. 297 (Password lock/unlock) to unlock the password function before operating.
Er1

Write disable error

Cause:

  • Parameter setting has been attempted although parameter writing is set to be disabled.

  • Overlapping range has been set for the frequency jump.

  • PU and the inverter cannot make normal communication.




Remedy:


  • Check the setting of Pr. 77 (Parameter write selection).

  • Check the settings of Pr. 31 to Pr. 36 (frequency jump).

  • Check the connection of PU and the inverter.


Er2

Write error during operation

Cause: Parameter writing has been attempted while a value other than "2" is set in Pr. 77 and the STF (STR) is ON.


Remedy:


  • Set "2" in Pr. 77 (Parameter write selection).

  • After stopping the operation, set parameters.


Er3

Calibration error

Cause: Analog input bias and gain calibration values have been set too close.


Remedy:

Check the settings of calibration parameters C3, C4, C6 and C7.
Er4

Mode designation error

Cause:

  • Parameter setting attempted in External/NET mode when Pr. 77 is not "2".

  • Parameter writing attempted when command source is not operation panel.




Remedy:


  • Set operation mode to "PU operation mode".

  • Set "2" in Pr. 77.

  • Disconnect PU, set Pr. 551 = "9999".

  • Set Pr. 551 = "4".


Err.

Inverter reset

Cause: The reset signal (RES signal) is ON (Inverter output is shutoff).


Remedy:

Turn OFF the reset command.
OL

Stall prevention (overcurrent)

Cause: The overcurrent stall prevention has been activated.


Remedy:


  • Increase/decrease Pr. 0 Torque boost by 1%.

  • Set larger value in Pr. 7 Accel time and Pr. 8 Decel time.

  • Reduce load weight. Try General-purpose magnetic flux vector control.

  • Adjust Pr. 13 Starting frequency. Change Pr. 14 Load pattern.

  • Adjust Pr. 22 Stall prevention level.


oL

Stall prevention (overvoltage)

Cause: The overvoltage stall prevention function has been activated.


Remedy:

Set the deceleration time longer.
rb

Regenerative brake pre-alarm

Cause: The regenerative brake duty has reached 85% of the Pr. 70 setting or higher.


Remedy:


  • Set the deceleration time longer.

  • Check Pr. 30 and Pr. 70 settings.


TH

Electronic thermal relay pre-alarm

Cause: The cumulative value of the electronic thermal O/L relay has reached 85% of the Pr. 9 setting.


Remedy:


  • Reduce the load and frequency of operation.

  • Set an appropriate value in Pr. 9.


PS

PU stop

Cause: STOP/RESET on the operation panel has been pressed during External operation.


Remedy:

Turn the start signal OFF and release with PU/EXT.
MT

Maintenance signal output

Cause: The cumulative energization time has exceeded the maintenance output timer set value.


Remedy:

Setting "0" in Pr. 503 Maintenance timer erases the signal.
Uu

Undervoltage

Cause: The voltage at the main circuit power has been lowered.


Remedy:

Investigate the devices on the power supply line such as the power supply itself.
SA

Safety stop

Cause: Safety stop function activating (Outputs are being shut off).


Remedy:


  • Short across terminals S1-SC and S2-SC if not using safety stop.

  • Check wiring of S1, S2, and SC.

  • Contact sales representative if wiring has no fault.


Fn

Fan alarm

Cause: The cooling fan is at a standstill although it is required to be operated.


Remedy:

Check for fan failure. Please contact your sales representative.
E.OC1

Overcurrent trip during acceleration

Cause: Overcurrent has occurred during acceleration.


Remedy:


  • Set acceleration time longer.

  • Disconnect motor and restart; if fault persists, inverter may be faulty.

  • Check wiring for short circuit/ground fault.

  • Set Pr. 3 Base frequency to 50Hz (if motor is 50Hz).

  • Lower stall prevention level.

  • Activate stall prevention (Pr. 156).


E.OC2

Overcurrent trip during constant speed

Cause: Overcurrent has occurred during constant speed operation.


Remedy:


  • Keep load stable.

  • Check wiring for shorts/ground faults.

  • Lower stall prevention level.


E.OC3

Overcurrent trip during deceleration or stop

Cause: Overcurrent has occurred during deceleration or at a stop.


Remedy:


  • Set deceleration time longer.

  • Check wiring for shorts/ground faults.

  • Check mechanical brake timing.

  • Lower stall prevention level.


E.OV1

Regenerative overvoltage trip during acceleration

Cause: Overvoltage has occurred during acceleration.


Remedy:


  • Set acceleration time shorter.

  • Use regeneration avoidance function (Pr. 882, etc).

  • Set Pr. 22 Stall prevention correctly.

  • Set Pr. 154 = "11".


E.OV2

Regenerative overvoltage trip during constant speed

Cause: Overvoltage has occurred during constant speed operation.


Remedy:


  • Keep load stable.

  • Use regeneration avoidance function.

  • Use brake resistor/unit/converter.

  • Set Pr. 154 = "11".


E.OV3

Regenerative overvoltage trip during deceleration

Cause: Overvoltage has occurred during deceleration or at a stop.


Remedy:


  • Set deceleration time longer.

  • Make brake cycle longer.

  • Use regeneration avoidance function.

  • Use brake resistor/unit.

  • Set Pr. 154 = "11".


E.THT

Inverter overload trip

Cause: The electronic thermal relay function for inverter element protection has been activated.


Remedy:


  • Set acceleration/deceleration time longer.

  • Adjust Pr. 0 Torque boost.

  • Adjust Pr. 14 Load pattern.

  • Reduce the load.


E.THM

Motor overload trip

Cause: The electronic thermal relay function for motor protection has been activated.


Remedy:


  • Reduce the load.

  • For constant-torque motor, set Pr. 71.

  • Set stall prevention level accordingly.


E.FIN

Heatsink overheat

Cause: The heatsink has overheated.


Remedy:


  • Set surrounding air temperature within specifications.

  • Clean the heatsink.

  • Replace cooling fan.


E.ILF

Input phase loss

Cause: One of the three phases on the inverter input side has been lost or largely unbalanced.


Remedy:


  • Wire cables properly.

  • Repair cable breaks.

  • Check Pr. 872 setting.


E.OLT

Stall prevention stop

Cause: The output frequency has dropped to 1Hz due to excess motor load deceleration.


Remedy:

Reduce the load. (Check Pr. 22).
E.BE

Brake transistor alarm detection

Cause: A fault has occurred in the brake circuit (e.g., transistor breakage).


Remedy:

Replace the inverter.
E.GF

Output side earth fault overcurrent at start

Cause: An earth (ground) fault occurred on the inverter's output side.


Remedy:

Remedy the ground fault portion.
E.LF

Output phase loss

Cause: One of the three phases (U, V, W) on the inverter's output side has been lost.


Remedy:


  • Wire cables properly.

  • Check if motor capacity matches inverter.


E.OHT

External thermal relay operation

Cause: The external thermal relay connected to the OH signal has been activated.


Remedy:


  • Reduce load and operate less frequently.

  • Reset the inverter.


E.PTC

PTC thermistor operation

Cause: Resistance of the PTC thermistor reached the protection level.


Remedy:

Reduce the load.
E.PE

Parameter storage device fault

Cause: Operation of the component where parameters are stored has become abnormal.


Remedy:


  • Contact sales representative.

  • If writing frequently, set Pr. 342 = "1" (RAM write).


E.PUE

PU disconnection

Cause: Communication error between PU and inverter, or interval exceeded.


Remedy:


  • Connect PU cable securely.

  • Check communication settings.

  • Increase Pr. 122 interval or set to "9999".


E.RET

Retry count excess

Cause: Operation restart within the set number of retries has failed.


Remedy:

Eliminate the cause of the error preceding this indication.
E.CPU

CPU fault

Cause: An error has occurred in the CPU and in the peripheral circuits.


Remedy:


  • Take measures against electrical noise.

  • If persists, contact sales representative.


E.CDO

Output current detection value exceeded

Cause: Output current has exceeded the output current detection level.


Remedy:

Check settings of Pr. 150, Pr. 151, Pr. 166, Pr. 167.
E.IOH

Inrush current limit circuit fault

Cause: The resistor of the inrush current limit circuit has overheated.


Remedy:

Configure a circuit where frequent power ON/OFF is not repeated.
E.AIE

Analog input fault

Cause: Voltage/Current input mismatch on Terminal 4 vs Pr. 267 setting.


Remedy:

Give frequency command by current input OR set Pr. 267 and switch to voltage correctly.
E.SAF

Safety circuit fault

Cause: While safety circuit fault is occurring, terminals across S1/PC or S2/PC are opened.


Remedy:


  • Short terminals S1-SC and S2-SC if not using safety stop.

  • Check wiring of S1, S2, SC and safety relay module.


How to Clear & Reset Mitsubishi FR-D700 Drive Faults

  1. Keypad Reset: Press the STOP / RESET key on the integrated operation panel. Keypad reset is active only when the inverter is in a trip state.
  2. Digital Input Reset (RES Terminal): Turn ON the reset signal between terminal RES and terminal SD (for sink logic) or terminal PC (for source logic) for at least 0.1 seconds, then turn it OFF. Note: Resetting while the drive is operating will cause the motor to coast to stop.
  3. FR Configurator PC Software: Connect a PC using an RS-485 cable to the RJ-45 PU connector on the front panel, launch FR Configurator, open the Diagnostics/Monitor window, and execute “Fault Clear” or “Inverter Reset”.
  4. RS-485 / Modbus RTU Communication: Send an inverter reset command or set the reset bit over the RS-485 communication line via Modbus RTU protocol (Pr. 117–Pr. 124 configuration).
  5. Power Cycle: Switch OFF the main circuit power supply breaker (terminals R/L1, S/L2, T/L3). Wait until the red CHARGE lamp turns off completely (approx. 10 minutes), then switch power back ON.
⚠️ High-Voltage Electrical Safety Warning: Always verify that the red CHARGE lamp on the front unit is completely extinguished, and use a calibrated digital multimeter to confirm that the intermediate DC bus voltage measured across terminals [P/+] and [N/-] is strictly below 30V DC before touching motor leads, terminal screws, or wiring terminals U, V, and W.