Mitsubishi FR-F500J Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, protective trip definitions, cause analysis, and step-by-step troubleshooting procedures for the Mitsubishi Electric FR-F500J compact fan and pump inverter series.

Compact Fan & Pump Inverter Power: 0.4 to 15 kW (0.5 to 20 HP) Automatic Torque Boost & Soft-PWM
Power Range 0.4 – 15 kW (0.5 – 20 HP)
Supply Voltage 3-Ph 200–240V / 380–480V AC
Control Modes V/F & Automatic Torque Boost
Operator Interface Integrated Panel & Dial / FR-PU04

Complete Mitsubishi FR-F500J Drive Fault Code Directory

Use the search box in the table below to quickly find your alarm code (e.g., type E.OC1, E.OV1, E.THT, or Overcurrent).

Fault Code and MeaningCause and Remedy

OC1



Overcurrent shut-off during acceleration

Cause:



When the inverter output current reaches or exceeds approximately 150% of the rated inverter current during acceleration, the protective circuit is activated to stop the inverter output.

Check points: Sudden acceleration, long downward acceleration time in vertical lift applications, or output short-circuit/ground fault.



Remedy:




  • Increase the acceleration time.

  • Shorten the downward acceleration time in vertical lift application.



OC2



Overcurrent shut-off during constant speed

Cause:



When the inverter output current reaches or exceeds approximately 150% of the rated inverter current during constant speed operation.

Check points: Sudden load change or output short-circuit/ground fault.



Remedy:




  • Keep load stable.



OC3



Overcurrent shut-off during deceleration

Cause:



When the inverter output current reaches or exceeds approximately 150% of the rated inverter current during deceleration.

Check points: Sudden speed reduction, output short-circuit/ground fault, or too fast operation of the motor's mechanical brake.



Remedy:




  • Increase the deceleration time.

  • Adjust brake operation.



OV1



Regenerative overvoltage shut-off during acceleration

Cause:



Main circuit DC voltage rises to specified value due to excessive regenerative energy or surge voltage during acceleration.

Check points: Too slow acceleration (e.g. during downward acceleration in vertical lift load).



Remedy:




  • Decrease the acceleration time.

  • Install a power factor improving reactor.



OV2



Regenerative overvoltage shut-off during constant speed

Cause:



Main circuit DC voltage rises to specified value due to excessive regenerative energy or surge voltage during constant speed.

Check points: Sudden load change.



Remedy:




  • Keep load stable.

  • Install a power factor improving reactor.



OV3



Regenerative overvoltage shut-off during deceleration or stop

Cause:



Main circuit DC voltage rises to specified value due to excessive regenerative energy or surge voltage during deceleration or stop.

Check points: Sudden speed reduction.



Remedy:




  • Increase the deceleration time (match moment of inertia of load).

  • Decrease the braking duty.

  • Install a power factor improving reactor.



THM



Motor overload shut-off (electronic thermal relay function)

Cause:



Motor overheat due to overload or reduced cooling capability during low speed operation. (Note: If using multi-pole or multiple motors, use an external thermal relay).

Check points: Check the motor for use under overload.



Remedy:




  • Reduce the load weight.

  • For a constant-torque motor, set the constant-torque motor in Pr. 71 "applied motor".



THT



Inverter overload shut-off (electronic thermal relay function)

Cause:



Current of more than 120% of rated output flows (but less than 150%) causing inverse time characteristics to activate to protect output transistors.

Check points: Check the motor for use under overload.



Remedy:




  • Reduce the load weight.



FIN



Fin overheat

Cause:



Heatsink overheats and temperature sensor actuates.

Check points: Too high ambient temperature or heatsink clogging.



Remedy:




  • Set the ambient temperature to within the specifications.

  • Clean heatsink if clogged.



GF



Start-time output side earth (ground) fault overcurrent

Cause:



Earth (ground) fault current flows at start due to a fault on the output (load) side. Valid when Pr. 40 is set to "1".

Check points: Earth (ground) fault in the motor or connection cable.



Remedy:




  • Remedy the earth (ground) fault portion.



LF



Output phase failure protection

Cause:



One of the three phases (U, V, W) on the output side opens at motor start.

Check points: Check wiring (ensure motor is normal). Check if motor used is smaller (two ranks or less) than inverter capacity.



Remedy:




  • Wire the cables properly.

  • Set "0" (without output phase failure protection) in H8 if using a smaller motor.



OHT



External thermal relay / OH Fault

Cause:



External thermal relay or internally mounted motor temperature relay switches on (contacts open).

Check points: Motor overheating. Check if Pr. 60 to Pr. 63 is set correctly to 7 (OH signal).



Remedy:




  • Reduce the load and operating duty.



OLT



Stall prevention (overload)

Cause:



Running frequency has fallen to 0 by stall prevention operation activated (OL appears).

Check points: Check the motor for use under overload.



Remedy:




  • Reduce the load weight.



OPT



Option Fault / Communication error

Cause:



Setting error or connection fault during use of RS-485 communication function.

Check points: Check that the connector is plugged securely.



Remedy:




  • Make connection securely.

  • Please contact your sales representative.


PE (FR-PU04: Corrupt Memory)

Parameter storage device alarm

Cause:


A fault occurred in parameters stored (example: EEPROM fault). Check for too many number of parameter write times.



Remedy:


Please contact your sales representative.
PUE (FR-PU04: PU Leave Out)

Parameter Unit disconnection

Cause:


Stops the inverter output if communication between inverter and PU is suspended (e.g. if PU is disconnected with "1" set in parameter n17).



Remedy:


Fit the FR-PU04 securely.
RET (FR-PU04: Retry No Over)

Retry count over

Cause:


If operation cannot be resumed properly within the number of retries set, this function stops the inverter output.



Remedy:


Eliminate the cause of the error preceding this error indication.
CPU (FR-PU04: CPU Fault)

CPU error

Cause:


If the arithmetic operation of the built-in CPU does not end within a predetermined period, the inverter self-determines it as an alarm and stops output.



Remedy:


Please contact your sales representative.
FN

Fan trouble

Cause:


For the inverter which contains a cooling fan, this appears when the cooling fan stops due to a fault.



Remedy:


Replace the fan.
OL

Stall prevention (overcurrent)

Cause:


Current more than 120% of rated inverter current flows in the motor.

  • During acceleration: Stops frequency increase.

  • During constant speed: Lowers frequency.

  • During deceleration: Stops frequency decrease.

  • Check the motor for use under overload.




Remedy:



  • The acceleration/deceleration time may change.

  • Increase the stall prevention operation level with Pr. 22.

  • Disable stall prevention with Pr. 21.

  • Check that the torque boost (Pr. 0) setting is not higher than required.


oL

Stall prevention (overvoltage)

Cause:


If the regenerative energy of the motor increases too much to exceed the brake capability, this function stops the decrease in frequency to prevent overvoltage shut-off. Check for sudden speed reduction.



Remedy:


The deceleration time may change. Increase the deceleration time using Pr. 8 "deceleration time".
PS

PU stop

Cause:


Pr. 75 "reset selection/PU stop selection" had been set and a stop was made by pressing the STOP/RESET of the operation panel or parameter unit during external operation mode.



Remedy:


Refer to the manual page 116.
UV / F5J

Undervoltage

Cause:


Power supply voltage decreases (below about 150VAC for 200V class / 300VAC for 400V class).

  • Check for a start of large-capacity motor.

  • Check that the power supply capacity is sufficient.




Remedy:


Check the power supply system equipment such as the power supply.
Er1 (FR-PU04: Control Mode)

Write disable error

Cause:



  • Write was performed with "1" (write disable) set in Pr. 77.

  • Frequency jump setting range overlapped.

  • Parameter write was performed though the operation panel does not have the write precedence.




Remedy:



  • Check the setting of Pr. 77 "parameter write disable selection".

  • Check the settings of Pr. 31 to 36 (frequency jump).

  • Check communication connector settings.


Er2 (FR-PU04: OPERATOR ERR)

Write-while-running error / mode designation error

Cause:



  • Write was performed during operation.

  • An attempt was made to change Pr. 79 setting while run command is input.

  • Write was performed in the external operation mode.




Remedy:



  • After stopping operation, make parameter setting.

  • After setting the operation mode to the "PU operation mode", make parameter setting.


Er3 (FR-PU04: Incr I/P)

Calibration error

Cause:


Analog input bias and gain calibration values are too close.



Remedy:


Check the settings of C3, C4, C6 and C7 (calibration functions).

How to Clear & Reset Mitsubishi FR-F500J Drive Faults

  1. Keypad Reset: Press the red STOP / RESET key directly on the front panel or the attached parameter unit (FR-PU04) while an alarm code is shown. Verify that parameter Pr. 75 (Reset selection / PU stop selection) allows keypad reset under your current operating mode.
  2. Terminal Input Reset (RES): Close an external contact between terminal RES and terminal SD for at least 0.1 seconds, then disconnect/open the contact to clear the trip condition.
  3. Serial Communication (RS-485): Issue a fault reset command bit via the PU connector using the Mitsubishi computer link / inverter communication protocol.
  4. PC Software Reset: Connect via the serial PU communication interface using an approved RS-485 converter, launch Mitsubishi setup software, and trigger an inverter software reset.
  5. Power Cycle: Switch off the main AC line power, wait until the red front-panel CHARGE LED is completely unlit (allow at least 10 minutes for intermediate bus capacitors to discharge), and turn the power back on.
⚠️ High-Voltage Electrical Safety Warning: Hazardous residual electrical charge remains in the DC bus capacitors even after the AC power is disconnected. Wait at least 10 minutes after turning off the power supply, ensure the CHARGE indicator lamp is completely off, and verify with a calibrated DC voltmeter that intermediate voltage across terminals [P/+] and [N/-] is strictly below 30 VDC before inspecting terminals or touching output motor leads U, V, and W.