Mitsubishi FR-F500J Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, protective trip definitions, cause analysis, and step-by-step troubleshooting procedures for the Mitsubishi Electric FR-F500J compact fan and pump inverter series.
Power Range
0.4 – 15 kW (0.5 – 20 HP)
Supply Voltage
3-Ph 200–240V / 380–480V AC
Control Modes
V/F & Automatic Torque Boost
Operator Interface
Integrated Panel & Dial / FR-PU04
Complete Mitsubishi FR-F500J Drive Fault Code Directory
Use the search box in the table below to quickly find your alarm code (e.g., type E.OC1, E.OV1, E.THT, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
OC1 Overcurrent shut-off during acceleration | Cause: When the inverter output current reaches or exceeds approximately 150% of the rated inverter current during acceleration, the protective circuit is activated to stop the inverter output. Check points: Sudden acceleration, long downward acceleration time in vertical lift applications, or output short-circuit/ground fault. Remedy:
|
OC2 Overcurrent shut-off during constant speed | Cause: When the inverter output current reaches or exceeds approximately 150% of the rated inverter current during constant speed operation. Check points: Sudden load change or output short-circuit/ground fault. Remedy:
|
OC3 Overcurrent shut-off during deceleration | Cause: When the inverter output current reaches or exceeds approximately 150% of the rated inverter current during deceleration. Check points: Sudden speed reduction, output short-circuit/ground fault, or too fast operation of the motor's mechanical brake. Remedy:
|
OV1 Regenerative overvoltage shut-off during acceleration | Cause: Main circuit DC voltage rises to specified value due to excessive regenerative energy or surge voltage during acceleration. Check points: Too slow acceleration (e.g. during downward acceleration in vertical lift load). Remedy:
|
OV2 Regenerative overvoltage shut-off during constant speed | Cause: Main circuit DC voltage rises to specified value due to excessive regenerative energy or surge voltage during constant speed. Check points: Sudden load change. Remedy:
|
OV3 Regenerative overvoltage shut-off during deceleration or stop | Cause: Main circuit DC voltage rises to specified value due to excessive regenerative energy or surge voltage during deceleration or stop. Check points: Sudden speed reduction. Remedy:
|
THM Motor overload shut-off (electronic thermal relay function) | Cause: Motor overheat due to overload or reduced cooling capability during low speed operation. (Note: If using multi-pole or multiple motors, use an external thermal relay). Check points: Check the motor for use under overload. Remedy:
|
THT Inverter overload shut-off (electronic thermal relay function) | Cause: Current of more than 120% of rated output flows (but less than 150%) causing inverse time characteristics to activate to protect output transistors. Check points: Check the motor for use under overload. Remedy:
|
FIN Fin overheat | Cause: Heatsink overheats and temperature sensor actuates. Check points: Too high ambient temperature or heatsink clogging. Remedy:
|
GF Start-time output side earth (ground) fault overcurrent | Cause: Earth (ground) fault current flows at start due to a fault on the output (load) side. Valid when Pr. 40 is set to "1". Check points: Earth (ground) fault in the motor or connection cable. Remedy:
|
LF Output phase failure protection | Cause: One of the three phases (U, V, W) on the output side opens at motor start. Check points: Check wiring (ensure motor is normal). Check if motor used is smaller (two ranks or less) than inverter capacity. Remedy:
|
OHT External thermal relay / OH Fault | Cause: External thermal relay or internally mounted motor temperature relay switches on (contacts open). Check points: Motor overheating. Check if Pr. 60 to Pr. 63 is set correctly to 7 (OH signal). Remedy:
|
OLT Stall prevention (overload) | Cause: Running frequency has fallen to 0 by stall prevention operation activated (OL appears). Check points: Check the motor for use under overload. Remedy:
|
OPT Option Fault / Communication error | Cause: Setting error or connection fault during use of RS-485 communication function. Check points: Check that the connector is plugged securely. Remedy:
|
| PE (FR-PU04: Corrupt Memory) Parameter storage device alarm | Cause: A fault occurred in parameters stored (example: EEPROM fault). Check for too many number of parameter write times. Remedy: Please contact your sales representative. |
| PUE (FR-PU04: PU Leave Out) Parameter Unit disconnection | Cause: Stops the inverter output if communication between inverter and PU is suspended (e.g. if PU is disconnected with "1" set in parameter n17). Remedy: Fit the FR-PU04 securely. |
| RET (FR-PU04: Retry No Over) Retry count over | Cause: If operation cannot be resumed properly within the number of retries set, this function stops the inverter output. Remedy: Eliminate the cause of the error preceding this error indication. |
| CPU (FR-PU04: CPU Fault) CPU error | Cause: If the arithmetic operation of the built-in CPU does not end within a predetermined period, the inverter self-determines it as an alarm and stops output. Remedy: Please contact your sales representative. |
| FN Fan trouble | Cause: For the inverter which contains a cooling fan, this appears when the cooling fan stops due to a fault. Remedy: Replace the fan. |
| OL Stall prevention (overcurrent) | Cause: Current more than 120% of rated inverter current flows in the motor.
Remedy:
|
| oL Stall prevention (overvoltage) | Cause: If the regenerative energy of the motor increases too much to exceed the brake capability, this function stops the decrease in frequency to prevent overvoltage shut-off. Check for sudden speed reduction. Remedy: The deceleration time may change. Increase the deceleration time using Pr. 8 "deceleration time". |
| PS PU stop | Cause: Pr. 75 "reset selection/PU stop selection" had been set and a stop was made by pressing the STOP/RESET of the operation panel or parameter unit during external operation mode. Remedy: Refer to the manual page 116. |
| UV / F5J Undervoltage | Cause: Power supply voltage decreases (below about 150VAC for 200V class / 300VAC for 400V class).
Remedy: Check the power supply system equipment such as the power supply. |
| Er1 (FR-PU04: Control Mode) Write disable error | Cause:
Remedy:
|
| Er2 (FR-PU04: OPERATOR ERR) Write-while-running error / mode designation error | Cause:
Remedy:
|
| Er3 (FR-PU04: Incr I/P) Calibration error | Cause: Analog input bias and gain calibration values are too close. Remedy: Check the settings of C3, C4, C6 and C7 (calibration functions). |
How to Clear & Reset Mitsubishi FR-F500J Drive Faults
- Keypad Reset: Press the red STOP / RESET key directly on the front panel or the attached parameter unit (FR-PU04) while an alarm code is shown. Verify that parameter Pr. 75 (Reset selection / PU stop selection) allows keypad reset under your current operating mode.
- Terminal Input Reset (RES): Close an external contact between terminal RES and terminal SD for at least 0.1 seconds, then disconnect/open the contact to clear the trip condition.
- Serial Communication (RS-485): Issue a fault reset command bit via the PU connector using the Mitsubishi computer link / inverter communication protocol.
- PC Software Reset: Connect via the serial PU communication interface using an approved RS-485 converter, launch Mitsubishi setup software, and trigger an inverter software reset.
- Power Cycle: Switch off the main AC line power, wait until the red front-panel CHARGE LED is completely unlit (allow at least 10 minutes for intermediate bus capacitors to discharge), and turn the power back on.
⚠️ High-Voltage Electrical Safety Warning:
Hazardous residual electrical charge remains in the DC bus capacitors even after the AC power is disconnected. Wait at least 10 minutes after turning off the power supply, ensure the CHARGE indicator lamp is completely off, and verify with a calibrated DC voltmeter that intermediate voltage across terminals [P/+] and [N/-] is strictly below 30 VDC before inspecting terminals or touching output motor leads U, V, and W.