Mitsubishi FR-F500L Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Mitsubishi FR-F500L large-capacity fan and pump inverter series. Search or filter through the complete fault code directory below.
Power Range
75 – 530 kW (100 – 700 HP)
Supply Voltage
200–220V / 380–480V (3-Phase)
Control Modes
Optimum Excitation, Flux Vector, V/F
Operator Interface
FR-DU04 / FR-PU04 Operation Panel
Complete Mitsubishi FR-F500L Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type E.OC1, E.OV1, or E.THM).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| E.OC1 Overcurrent shut-off during acceleration | Cause: When inverter output current exceeds approx 150% during acceleration.
Remedy:
|
| E.OC2 Overcurrent shut-off during constant speed | Cause: When inverter output current exceeds approx 150% during constant speed.
Remedy:
|
| E.OC3 Overcurrent shut-off during deceleration | Cause: When inverter output current exceeds approx 150% during deceleration.
Remedy:
|
| E.OV1 Regenerative overvoltage shut-off during acceleration | Cause: Regenerative energy or surge voltage caused internal DC voltage to exceed specified value.
Remedy:
|
| E.OV2 Regenerative overvoltage shut-off during constant speed | Cause: Regenerative energy or surge voltage caused internal DC voltage to exceed specified value.
Remedy:
|
| E.OV3 Regenerative overvoltage shut-off during deceleration or stop | Cause: Regenerative energy or surge voltage caused internal DC voltage to exceed specified value.
Remedy:
|
| E.THM Motor overload shut-off (electronic overcurrent protection) | Cause: Motor overheat due to overload or reduced cooling capability.
Remedy:
|
| E.THT Inverter overload shut-off (electronic overcurrent protection) | Cause: Current >120% rating flows (inverse-time characteristics activated).
Remedy:
|
| E.IPF Instantaneous power failure protection | Cause: Power failure occurred for longer than 15ms.
Remedy:
|
| E.UVT Undervoltage protection | Cause: Start of large-capacity motor. Jumper or DC reactor is not connected across terminals P-P1. Remedy: Check the power supply system equipment such as power supply. Connect a jumper or DC reactor across terminals P-P1. |
| E.FIN Fin overheat | Cause: Too high ambient temperature. Heatsink clogging. Remedy: Set the ambient temperature to within the specifications. |
| E.GF Output side earth (ground) fault overcurrent protection | Cause: Earth (ground) fault in the motor and connection cable. Remedy: Remedy the earth (ground) fault portion. |
| E.OHT External thermal relay operation | Cause: Motor overheating. Value of 7 (OH signal) is set incorrectly in any of Pr. 180 to Pr. 186. Remedy: Reduce the load and operating duty. |
| E.OLT Stall prevention (Stll Prev STP) | Cause: Motor used under overload conditions. Remedy: Reduce the load weight. |
| E.OPT Option alarm | Cause: Number of communication options fitted is more than one. AC power supply connected to R, S, T terminals when high power factor converter is connected. Remedy: Reduce the communication options used to one. Check the parameter (Pr. 30) setting and wiring. Contact sales representative if inverter is damaged by AC power connection. |
| E.OP1 to E.OP3 Option slot alarm 1 to 3 | Cause: Wrong option function setting and operation. Plug-in option not connected securely. Communication cable wire breakage. Termination resistor not fitted properly. Remedy: Confirm the option function setting, etc. Connect the plug-in option securely. |
| E.PE Parameter storage device alarm (Corrupt Memry) | Cause: Too many parameter write times (E2PROM fault). Remedy: Change the inverter. |
| E.PUE Parameter unit disconnection (PU Leave Out) | Cause: Loose fitting of the DU or PU. Incorrect Pr. 75 setting. Remedy: Fit the DU and PU securely. |
| E.RET Retry count exceeded (Retry No Over) | Cause: Operation could not be resumed within the set number of retries. Remedy: Eliminate the cause of the error preceding this error indication. |
| E.CPU CPU error (CPU Fault) | Cause: Arithmetic operation of built-in CPU did not end within predetermined period. Remedy: Make connection securely. |
| E. 3 Option fault (Fault 3) | Cause: Communication option not plugged in securely. Excess noises around the inverter. Remedy: Take measures against noises if there are devices producing excess noises. Contact your sales representative. |
| E.6 / E.7 CPU error | Cause: Check for excess electrical noises around the inverter. Remedy:
|
| E.P24 24VDC power output short circuit | Cause: Check for a short circuit in the PC terminal output. Remedy: Remedy the short circuit portion. |
| E.CTE Operation panel power supply short circuit | Cause: Check for a short circuit in the PU connector cable. Remedy: Check the PU and cable. |
| E.LF Output phase failure protection | Cause:
Remedy:
|
| FN Fan fault | Cause: Check the cooling fan for a fault. Remedy: Change the fan. |
| OL Stall prevention (Over current) | Cause: Check the motor for use under overload. Remedy: The acceleration/deceleration time may change. Increase the stall prevention operation level with Pr. 22 "stall prevention operation level" or disable stall prevention with Pr. 156 "stall prevention operation selection". |
| oL Stall prevention (overvoltage) | Cause: Check for sudden speed reduction. Remedy: The deceleration time may change. Increase the deceleration time with Pr. 8 "deceleration time". |
| PS PU stop | Cause: Check for a stop made by pressing the STOP/RESET key of the operation panel. Remedy: Refer to page 102 (release the PU stop mode). |
| TH Electronic overcurrent protection prealarm | Cause: Check for large load or sudden acceleration. Remedy: Reduce the load volume or the frequency of operation. |
| Err. Error (Operation Error) | Cause: This alarm appears if:
Remedy: Perform operation correctly. |
How to Clear & Reset Mitsubishi FR-F500L Drive Faults
- Keypad Reset: Press the STOP / RESET key on the operation panel (FR-DU04) or parameter unit (FR-PU04). Keypad reset is active only while the inverter is in a fault trip condition.
- Digital Input Reset (RES Terminal): Turn ON the reset signal across control terminal RES and common terminal SD (for sink logic) or PC (for source logic) for at least 0.1 seconds, then turn it OFF. Note: Resetting while running will coast the motor to stop.
- PU / RS-485 Communication: Connect a PC using an RS-485 conversion cable to the RJ-45 PU port on the inverter, and issue an Inverter Reset / Fault Clear command via software or computer link protocol.
- Fieldbus Option Card: Assert the Inverter Reset Bit or write command code
H9696across CC-Link (FR-A5NC), Profibus-DP (FR-A5NP), or DeviceNet (FR-A5ND) networks. - Power Cycle: Switch OFF the main circuit power supply breaker (terminals R/L1, S/L2, T/L3). Wait until the red CHARGE lamp turns off completely (at least 10 minutes for capacitor bank discharge), then restore power.
⚠️ High-Voltage Electrical Safety Warning:
Always verify that the red CHARGE lamp on the front unit is completely extinguished, and use a calibrated digital multimeter to confirm that the intermediate DC bus voltage measured across terminals [P/+] and [N/-] is strictly below 30V DC before touching motor leads, terminal screws, or wiring terminals U, V, and W.