Mitsubishi FR-F700P Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, protective trip definitions, cause analysis, and step-by-step troubleshooting procedures for the Mitsubishi Electric FR-F700P premium fan and pump inverter series.
Power Range
0.75 – 560 kW (1 – 750 HP)
Supply Voltage
3-Ph 200–240V / 380–480V AC
Control Modes
V/F, Adv. Magnetic Flux, OEC
Operator Interface
FR-DU07 Panel / FR-PU07 Keypad
Complete Mitsubishi FR-F700P Drive Fault Code Directory
Use the search box in the table below to quickly find your alarm code (e.g., type E.OC1, E.OV1, E.THT, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| HOLD Operation panel lock | Cause: Operation lock mode is set. Operation other than STOP/RESET is invalid. Remedy:
|
| LOCd Password locked | Cause: Password function is active. Display and setting of parameter is restricted. Remedy:
|
| Er1 Write disable error | Cause:
Remedy:
|
| Er2 Write error during operation | Cause: Parameter writing was performed during operation while Pr. 77 is not set to "2" and STF (STR) is ON. Remedy:
|
| Er3 Calibration error | Cause: Analog input bias and gain calibration values are too close. Remedy:
|
| Er4 Mode designation error | Cause:
Remedy:
|
| rE1 Parameter read error | Cause: An error occurred in the EEPROM on the operation panel side during parameter copy reading. Remedy:
|
| rE2 Parameter write error | Cause:
Remedy:
|
| rE3 Parameter verification error | Cause:
Remedy:
|
| rE4 Model error | Cause:
Remedy:
|
| Err. Error / Reset Signal | Cause:
Remedy:
|
| OL Stall prevention (overcurrent) | Cause: The output current of the inverter exceeded the stall prevention operation level (Pr. 22). This stops frequency increase (accel) or decreases frequency (decel/constant speed) to prevent overcurrent trip. Remedy:
|
| oL Stall prevention (overvoltage) | Cause: Regenerative energy of the motor became excessive (during deceleration). The inverter stops frequency decrease to prevent overvoltage trip. Remedy:
|
| PS PU stop | Cause: Stop with [STOP/RESET] key of PU is set in Pr. 75. Remedy:
|
| RB Regenerative brake prealarm Appears if the regenerative brake duty reaches or exceeds 85% of the Pr. 70 setting. If it reaches 100%, a regenerative overvoltage (E.OV_) occurs. | Cause:
Remedy:
|
| TH Electronic thermal relay function prealarm Appears if the cumulative value of the Pr. 9 Electronic thermal O/L relay reaches or exceeds 85% of the preset level. | Cause:
Remedy:
|
| MT Maintenance signal output Indicates that the cumulative energization time of the inverter has reached a given time. | Cause:
Remedy:
|
| CP Parameter copy Appears when parameters are copied between models with capacities of 55K or lower and 75K or higher. | Cause:
Remedy:
|
| FN Fan alarm Appears on the operation panel when the cooling fan stops due to a fault or different operation from the setting of Pr. 244. | Cause:
Remedy:
|
| E.OC1 Overcurrent trip during acceleration When the inverter output current reaches or exceeds approximately 170% of the rated current during acceleration. | Cause:
Remedy:
|
| E.OC2 Overcurrent trip during constant speed When the inverter output current reaches or exceeds approximately 170% of the rated current during constant speed operation. | Cause:
Remedy:
|
| E.OC3 Overcurrent trip during deceleration or stop When the inverter output current reaches or exceeds approximately 170% of the rated current during deceleration or stop. | Cause:
Remedy:
|
| E.OV1 Regenerative overvoltage trip during acceleration If regenerative energy causes the inverter's internal main circuit DC voltage to reach or exceed the specified value. | Cause:
Remedy:
|
| E.OV2 Regenerative overvoltage trip during constant speed If regenerative energy causes the inverter's internal main circuit DC voltage to reach or exceed the specified value. | Cause:
Remedy:
|
| E.OV3 Regenerative overvoltage trip during deceleration or stop If regenerative energy causes the inverter's internal main circuit DC voltage to reach or exceed the specified value. | Cause:
Remedy:
|
| E.THT Inv. Overload | Cause: Inverter overload trip (electronic thermal relay function). If a current not less than 120% of the rated output current flows and overcurrent trip does not occur (170% or less), the electronic thermal relay activates to stop the inverter. Check points:
Remedy:
|
| E.THM Motor Overload | Cause: Motor overload trip (electronic thermal relay function). The electronic thermal relay detects motor overheat due to overload or reduced cooling capability during constant-speed operation. Check points:
Remedy:
|
| E.FIN H/Sink O/Temp | Cause: Heatsink overheat. If the heatsink overheats, the temperature sensor is actuated to stop the inverter output. Check points:
Remedy:
|
| E.IPF Inst. Pwr. Loss | Cause: Instantaneous power failure. If a power failure occurs for longer than 15ms, the instantaneous power failure protective function is activated. Check points:
Remedy:
|
| E.BE Br. Cct. Fault | Cause: Brake transistor alarm detection/internal circuit fault. Stops output if a fault occurs in the brake circuit (e.g., damaged brake transistors). Check points:
Remedy:
|
| E.UVT Under Voltage | Cause: If the power supply voltage decreases, the control circuit will not perform normal functions. Stops inverter if voltage drops below about 150V (200V class) or 300V (400V class). Also activates if jumper is missing across P/+ and P1. Check points:
Remedy:
|
| E.ILF Input phase loss | Cause: Input phase loss. Output when one phase of the three-phase power input is lost (valid when Pr. 872 = 1). Check points:
Remedy:
|
| E.OLT Stall Prev STP | Cause: Stall prevention stop. If frequency falls to 0.5Hz (1.5Hz under IPM) by stall prevention and remains for 3s, E.OLT appears. Check points:
Remedy:
|
| E.SOT Motor step out | Cause: Loss of synchronism detection. Stops output when operation is not synchronized (IPM motor control only). Check points:
Remedy:
|
| E.GF Ground Fault | Cause: Output side earth (ground) fault overcurrent. Stops inverter if earth fault occurs on output side. Check points:
Remedy:
|
| E.LF Output phase loss | Cause: Output phase loss. Stops inverter if one of the three phases (U, V, W) on the output side is lost. Check points:
Remedy:
|
| E.OHT OH Fault | Cause: External thermal relay operation. External or internal temperature relay switches ON (contacts open). Check points:
Remedy:
|
| E.PTC PTC activated | Cause: PTC thermistor operation. Motor overheat status detected for 10s or more by external PTC thermistor connected to terminal AU. Check points:
Remedy:
|
| E.OPT Option Fault | Cause: Option fault. AC power connected to wrong terminals, plug-in option switch changed, or communication option connected while password locked. Check points:
Remedy:
|
| E.OP1 Communication option fault | Cause: Stops the inverter output when a communication line fault occurs in the communication option.
Remedy:
|
| E.1 Option fault | Cause: Stops the inverter output if a contact fault or the like of the connector between the inverter and communication option occurs. Appears when the switch for the manufacturer setting of the plug-in option is changed.
Remedy:
|
| E.PE Parameter storage device fault (control circuit board) | Cause: Trips when a fault occurred in the parameter stored (EEPROM failure). Check for too many number of parameter write times. Remedy: Please contact your sales representative. When performing parameter write frequently for communication purposes, set "1" in Pr. 342 to enable RAM write. Note that powering OFF returns the inverter to the status before RAM write. |
| E.PE2 Parameter storage device fault (main circuit board) | Cause: Trips when a fault occurred in the parameter stored (EEPROM failure). Remedy: Please contact your sales representative. |
| E.PUE PU disconnection | Cause:
Remedy: Fit the FR-DU07 or parameter unit (FR-PU04/FR-PU07) securely. |
| E.RET Retry count excess | Cause: If operation cannot be resumed properly within the number of retries set, this function trips the inverter. Find the cause of fault occurrence. Remedy: Eliminate the cause of the fault preceding this error indication. |
| E.5 / E.6 / E.7 / E.CPU CPU fault | Cause: Stops the inverter output if the communication fault of the built-in CPU occurs. Check for devices producing excess electrical noises around the inverter. Remedy:
|
| E.CTE Operation panel / RS-485 power supply short circuit | Cause: When the operation panel power supply (PU connector) is shorted, or internal power supply for RS-485 terminals are shorted, this function shuts off the power output.
Remedy:
|
| E.P24 24VDC power output short circuit | Cause: When the 24VDC power output from the PC terminal is shorted, this function shuts off the power output. All external contact inputs switch OFF.
Remedy: Remedy the earth (ground) fault portion. Reset via operation panel or power cycle. |
| E.CDO Output current detection value exceeded | Cause: This function stops the inverter output when the output current exceeds the setting of Pr.150 or falls below Pr.152.
Remedy: Review and adjust parameter settings related to Output Current Detection (Refer to manual page 146). |
| E.IOH Inrush current limit circuit fault | Cause: Trips when the resistor of the inrush current limit circuit overheats.
Remedy: Configure a circuit where frequent power ON/OFF is not repeated. If the problem still persists after taking the above measure, please contact your sales representative. |
| E.SER Communication fault (inverter) | Cause: This function stops the inverter output when communication error occurs consecutively for more than permissible retry count (Pr. 335) or communication is broken for time set in Pr. 336. Check the RS-485 terminal wiring. Remedy: Perform wiring of the RS-485 terminals properly. |
| E.AIE Analog input fault | Cause: Stops the inverter output when a 30mA or higher current or a 7.5V or higher voltage is input to terminal 2 or terminal 4 while specific input selections are active.
Remedy: Either give a frequency command by current input or set Pr. 73 or Pr. 267 to voltage input. |
| E.PID PID signal fault | Cause: If any of PID upper limit (FUP), PID lower limit (FDN), and PID deviation limit (Y48) turns ON during PID control, inverter shuts off the output.
Remedy: Make correct settings for Pr.131, Pr.132, and Pr.553. |
| E.13 Internal circuit fault | Cause: Trips when an internal circuit error occurred. Remedy: Please contact your sales representative. |
How to Clear & Reset Mitsubishi FR-F700P Drive Faults
- Keypad Reset: Press the STOP / RESET key directly on the operation panel (FR-DU07) or parameter unit (FR-PU07) while the inverter is in an alarm state. Confirm that parameter Pr. 75 (Reset selection / PU stop selection) allows resetting under your active control mode.
- Terminal Input Reset (RES): Short-circuit external control terminal RES to terminal SD (for Sink logic) or PC (for Source logic) for at least 0.1 seconds, then disconnect/reopen the contact.
- FR Configurator Software: Connect a PC via the RS-485 / PU connector using an approved interface cable, open Mitsubishi FR Configurator, and click “Fault Reset” in the monitoring status window.
- Fieldbus Communication: Set the fault reset bit (such as Bit 1 or Bit 7 depending on communication protocol) across built-in RS-485 Modbus RTU or optional CC-Link, BACnet, or LonWorks communication modules.
- Power Cycle: Disconnect primary AC input power, wait until the red front-panel CHARGE LED is completely unlit (approx. 10 minutes to allow DC capacitors to fully discharge), and reapply input power.
⚠️ High-Voltage Electrical Safety Warning:
Hazardous residual voltage remains inside intermediate DC bus capacitors after main power is shut off. Wait at least 10 minutes after disconnecting mains supply, ensure the CHARGE indicator lamp is completely unlit, and verify with a calibrated DC voltmeter that the voltage between terminal [P/+] and terminal [N/-] is strictly below 30 VDC before inspecting wiring or touching terminals U, V, and W.