Mitsubishi FR-S500 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Mitsubishi Electric FR-S500 compact micro inverter series. Search or filter through the complete fault code directory below.
Power Range
0.1 – 3.7 kW (0.125 – 5 HP)
Supply Voltage
100–120V / 200–240V / 380–480V (1/3-Phase)
Control Modes
Soft-PWM / V/F & Flux Vector Control
Operator Interface
Integrated Setting Dial Panel / FR-PU04
Complete Mitsubishi FR-S500 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type E.OC1, E.OV1, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
OC1 (FR-PU04: OC During Acc) Overcurrent cut-off during acceleration | Cause: When the inverter output current reaches or exceeds approximately 200% of the rated inverter current during acceleration, the protective circuit is activated to stop the inverter output. Check points: Check for sudden acceleration. Check for output short-circuit/ground fault. Remedy:
|
OC2 (FR-PU04: Stedy Spd OC) Overcurrent cut-off during constant speed | Cause: When the inverter output current reaches or exceeds approximately 200% of the rated inverter current during constant-speed operation, the protective circuit is activated to stop the inverter output. Check points: Check for sudden load change. Check for output short-circuit/ground fault. Remedy:
|
OC3 (FR-PU04: OC During Dec) Overcurrent cut-off during deceleration | Cause: When the inverter output current reaches or exceeds approximately 200% of the rated inverter current during deceleration (other than acceleration or constant speed), the protective circuit is activated to stop the inverter output. Check points: Check for sudden speed reduction. Check for output short-circuit/ground fault. Check for too fast operation of motor's mechanical brake. Remedy:
|
OV1 (FR-PU04: OV During Acc) Regenerative overvoltage cut-off during acceleration | Cause: When the main circuit DC voltage in the inverter rises to or above the specified value due to excessive regenerative energy during acceleration. May also be activated by surge voltage in power supply. Check points: Check for too slow acceleration. Remedy:
|
OV2 (FR-PU04: Stedy Spd OV) Regenerative overvoltage cut-off during constant speed | Cause: When the main circuit DC voltage in the inverter rises to or above the specified value due to excessive regenerative energy during constant speed. May also be activated by surge voltage in power supply. Check points: Check for sudden load change. Remedy:
|
OV3 (FR-PU04: OV During Dec) Regenerative overvoltage cut-off during deceleration or stop | Cause: When the main circuit DC voltage in the inverter rises to or above the specified value due to excessive regenerative energy during deceleration or stop. May also be activated by surge voltage in power supply. Check points: Check for sudden speed reduction. Remedy:
|
THM (FR-PU04: Motor Overload) Motor overload cut-off (electronic thermal overcurrent protection) | Cause: The electronic overcurrent protection detects motor overheat due to overload or reduced cooling capability during low-speed operation. Check points: Check the motor for use under overload. Remedy:
|
THT (FR-PU04: Inv. Overload) Inverter overload cut-off (electronic thermal overcurrent protection) | Cause: If a current of more than 150% of the rated output current flows and overcurrent shut-off does not occur (200% or less), inverse-time characteristics activate protection to stop the inverter output to protect output transistors. Check points: Check the motor for use under overload. Remedy:
|
FIN (FR-PU04: H/Sink O/Temp) Fin overheat | Cause: If the cooling fin overheats, the overheat sensor is actuated to stop the inverter output. Check points: Check for too high ambient temperature. Check for cooling fin clogging. Remedy:
|
GF (FR-PU04: Ground Fault) Start-time output side ground fault overcurrent protection | Cause: A ground fault overcurrent flowed due to a ground fault which occurred in the inverter's output (load) side. (Valid when Pr. 40 = "1"). Check points: Check for a ground fault in the motor and connection cable. Remedy:
|
OHT (FR-PU04: OH Fault) External thermal relay | Cause: The external thermal relay (motor overheat protection) or internally mounted temperature relay in the motor switched on (contacts open). Check points: Check for motor overheating. Check that value of 7 (OH signal) is set correctly in Pr. 60 to Pr. 63. Remedy:
|
OLT (FR-PU04: Stll Prev STP) Stall prevention (overload) | Cause: The running frequency has fallen to 0 by stall prevention operation activated. OL appears while stall prevention is being activated. Check points: Check the motor for use under overload. Remedy:
|
OPT (FR-PU04: Option Fault) Communication error | Cause: A setting error or connection (connector) fault occurred during use of the RS-485 communication function. Check points: Check that the connector is plugged securely. Remedy:
|
PE (FR-PU04: Corrupt Memory) Parameter error | Cause: A fault occurred in parameters stored (example: E2PROM fault). Check points: Check for too many number of parameter write times. Remedy:
|
| PUE PU disconnected | Cause: Communication between inverter and PU is suspended (e.g., if the PU is disconnected with "1" set in parameter n17). Remedy:
|
| RET Retry count | Cause: If operation cannot be resumed properly within the number of retries set, this function stops the inverter output. Remedy:
|
| CPU CPU error | Cause: If the arithmetic operation of the built-in CPU does not end within a predetermined period, the inverter self-determines it as an alarm. Remedy:
|
| FN Fan trouble | Cause: The cooling fan stops due to a fault or operates differently from the setting of Pr. 76 "cooling fan operation selection". Remedy:
|
| OL Stall prevention (overcurrent) | Cause: Current of more than 150% of the rated inverter current flows in the motor during acceleration, constant speed, or deceleration. The function stops frequency change to prevent overcurrent shut-off. Remedy:
|
| oL Stall prevention (overvoltage) | Cause: During deceleration, if regenerative energy increases too much to exceed brake capability, this function stops the decrease in frequency to prevent overvoltage shut-off. Remedy:
|
| PS PU stop (Stopped with PU STOP key) | Cause: Pr. 75 "reset selection/PU stop selection" had been set and a stop was made by pressing the STOP/RESET key during external operation mode. Remedy:
|
| UV Undervoltage | Cause: Power supply voltage reduced below about 115VAC (230VAC for 400V series) resulting in control circuit issues. Remedy:
|
| Er1 Write disable error | Cause:
Remedy:
|
| Er2 Write-while-running / mode designation error | Cause:
Remedy:
|
| Er3 Calibration error | Cause: Analog input bias and gain calibration values are too close. Remedy:
|
How to Clear & Reset Mitsubishi FR-S500 Drive Faults
- Keypad Reset: Press the STOP / RESET key on the integrated operation panel while the fault code is indicated on the display. Important: Turn off all forward/reverse run commands (STF / STR) prior to resetting to prevent an unexpected motor restart.
- Control Terminal Reset (RES): Short the Reset input terminal (RES) to the common terminal (SD in sink logic) for at least 0.1 seconds, then release it. Terminal RES is mapped via multi-function input parameters Pr. 180 to Pr. 183.
- FR Configurator Software (Communication models): On FR-S500E models equipped with the RS-485 communication port, connect a PC with a converter cable and select “Inverter Reset / Clear Fault” in FR Configurator.
- Serial Network Reset: Write an Inverter Reset instruction command (HFD00) over the RS-485 serial communication bus to clear active trip faults.
- Main Power Cycle: Switch OFF the incoming AC mains power, wait until the LED display and red CHARGE LED turn completely off (wait at least 10 minutes for DC bus capacitor discharge), then turn main power back ON.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [P/+] and [N/-] (and confirm the internal red CHARGE indicator lamp is completely unlit) before opening terminal covers, servicing motor wiring, or touching terminals U, V, and W on the Mitsubishi FR-S500 inverter.