Mitsubishi MD-AX520 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Mitsubishi Electric MD-AX520 MELIPM permanent magnet motor drive unit series. Search or filter through the complete fault code directory below.

MELIPM PM Motor Drive Unit Power: 0.5 to 7.0 kW (0.75 to 10 HP) Sensorless Sine-Wave PWM Control
Power Range 0.5 – 7.0 kW (0.75 – 10 HP)
Supply Voltage 200–230V AC (3-Phase)
Control Modes Sensorless Sine-Wave PWM (PM Motor)
Operator Interface FR-DU04 Control Panel / FR-PU04

Complete Mitsubishi MD-AX520 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type E.OC1, E.OV1, or Overcurrent).

Fault Code and MeaningCause and Remedy
E.OC1

Acceleration time overcurrent

Cause:
The acceleration torque is beyond the drive unit capability; Outputs U, V, and W are in a short circuit or ground fault; The motor restarted during coasting; Or start signal given with only R1/S1 power.



Remedy:

  • Increase the acceleration time.

  • Change the acceleration/deceleration pattern to an S shape.

  • Check the motor winding resistance.

  • Check the connection cables for damage.

  • Restart the motor after a complete stop.

  • Supply main circuit power (R, S, T).


E.OC2

Constant speed time overcurrent

Cause:
Excessive load was applied instantaneously; Outputs U, V, and W resulted in a short circuit or ground fault during constant-speed operation; Drive capacity does not match motor.



Remedy:

  • Check the motor winding resistance.

  • Check the connection cables for damage.

  • Ensure drive unit capacity matches the motor.


E.OC3

Deceleration time overcurrent

Cause:
The deceleration torque is beyond the drive unit capability; Outputs U, V, and W resulted in a short circuit or ground fault during deceleration; Mechanical brake operates too early.



Remedy:

  • Increase the deceleration time.

  • Change the acceleration/deceleration pattern to an S shape.

  • Check the motor winding resistance.

  • Check the connection cables for damage.

  • Delay the brake operation timing.


E.GF

Output side ground fault overcurrent

Cause:
Any of outputs U, V, W is in a ground fault.



Remedy:

  • Check for ground faults in the motor and wiring.


E.OV1

Acceleration time overvoltage

Cause:
Surge compounded with power during acceleration; Regenerative energy handling capability is insufficient.



Remedy:

  • Install a reactor.

  • Fit a surge suppressor to the surge source.

  • Fit the regenerative brake option.


E.OV2

Constant speed time overvoltage

Cause:
Surge compounded with power; Load increased suddenly activating stall prevention; Regenerative energy capability insufficient.



Remedy:

  • Install a reactor.

  • Fit a surge suppressor to the surge source.

  • Fit the regenerative brake option.


E.OV3

Deceleration time overvoltage

Cause:
Deceleration torque beyond drive capability; Regenerative energy capability insufficient; Surge compounded with power during deceleration.



Remedy:

  • Increase the deceleration time.

  • Change acceleration/deceleration pattern to S shape.

  • Fit the regenerative brake option.

  • Install a reactor or surge suppressor.


E.THT

Electronic overcurrent protection (Transistor)

Cause:
The motor and drive unit are operated under overload.



Remedy:

  • Reduce the load.

  • Increase the capacities of the motor and drive unit.


E.THM

Electronic overcurrent protection (Thermal)

Cause:
The motor and drive unit are operated under overload.



Remedy:

  • Reduce the load.

  • Increase the capacities of the motor and drive unit.


E.IPF

Instantaneous power failure

Cause:
An instantaneous power failure occurred (15 to 100ms).



Remedy:

  • Check power supply stability.

  • Reset the alarm.


E.UVT

Undervoltage

Cause:
Large-capacity equipment started nearby; Jumper across terminals P/+-P1 disconnected.



Remedy:

  • Connect the jumper or DC reactor.

  • Check power supply capacity.


E.FIN

Fin overheat

Cause:
Heat sink temperature exceeded permissible value; Cooling fan failed.



Remedy:

  • Check ambient temperature.

  • Replace cooling fan if failed.

  • Clean heat sink fins.


E.OHT

External fault

Cause:
The external relay or equivalent component connected to the terminal assigned to OH signal operated.



Remedy:

  • Check external device/relay triggering the fault.

  • Check wiring of the OH signal terminal.


E.PUE

PU disconnection

Cause:
Connection fault of operation panel/parameter unit; RS-485 communication interrupted; Comm retries exceeded.



Remedy:

  • Check connection of the operation panel.

  • Check RS-485 wiring and parameters (Pr. 75, Pr. 121).


E.RET

Retry excess

Cause:
The number of alarms that occurred exceeded the retry setting.



Remedy:

  • Investigate the root cause of the recurring alarms.

  • Check Retry count parameter (Pr. 67).


E.OLT

Stall stop

Cause:
Motor overload activated stall prevention consecutively; E.OLT output selected in Pr. 156.



Remedy:

  • Reduce the load.

  • Increase capacities of motor and drive unit.

  • Check Pr. 156 setting.


E.LF

Phase failure

Cause:
A phase failure occurred in any of the outputs U, V, W.



Remedy:

  • Check wiring for breaks or loose connections.

  • Check motor windings.


E.P24

P24 Short Circuit

Cause:
The PC terminal output of the control circuit is in a short circuit.



Remedy:

  • Check the wiring connected to the PC terminal.

  • Reset via method other than RES terminal.


E.CTE

Panel power supply

Cause:
The power supply cable of the operation panel or parameter unit is in a short circuit.



Remedy:

  • Check the cable wiring for shorts.


E.OPT

Option fault

Cause:
The plug-in option fitted is other than specified; Power switched on with high power factor converter setting (Pr. 30 = 2).



Remedy:

  • Check the installed option card.

  • Check Parameter 30 setting.


E.CPU / E.6 / E.7

CPU fault

Cause:
The CPU malfunctioned or failed.



Remedy:

  • If the same message reappears after reset, replace the drive unit.


E.PE

Storage device fault

Cause:
The storage device failed.



Remedy:

  • If the same message reappears after reset, replace the drive unit.


E.BE

Brake circuit fault

Cause:
The regenerative brake circuit failed.



Remedy:

  • Immediately switch power off if E.BE reappears.

  • Leaving power on will overheat the brake resistor.

  • Replace drive unit if fault persists.


OL

Overload 1 (Alarm)

Cause:
Acceleration/Constant speed/Deceleration time overcurrent; Stall stop activated.



Remedy:

  • Reduce load.

  • Check Pr. 22 setting.


oL

Overload 2 (Alarm)

Cause:
Main circuit DC voltage more than 390V (Deceleration-time overvoltage).



Remedy:

  • Increase deceleration time.

  • Check regenerative brake capability.


RB

Brake duty (Alarm)

Cause:
More than 85% of the permissible value (Deceleration-time overvoltage).



Remedy:

  • Reduce braking duty cycle.

  • Check brake resistor sizing.


TH

Motor overheat (Alarm)

Cause:
More than 85% of the electronic overcurrent protection level.



Remedy:

  • Reduce motor load.

  • Check cooling.


FN

Fan failure (Alarm)

Cause:
Cooling fan fault; Fin overheat.



Remedy:

  • Replace cooling fan.

  • Clean heatsink.


Err

Operation error

Cause:
Parameter changing during external operation; Value outside range; RES signal remains ON; Connection fault.



Remedy:

  • Perform parameter changes in PU mode.

  • Check valid parameter ranges.

  • Turn off RES signal.

  • Check panel fitting status.


PS

Emergency stop operation

Cause:
STOP/RESET key was pressed during external operation.



Remedy:

  • Reset cannot be made by normal method.

  • Refer to Pr. 75 for reset procedures.


E.rE4

Copy error

Cause:
Parameters were copied to a different model.



Remedy:

  • Ensure source and destination drive models match.


How to Clear & Reset Mitsubishi MD-AX520 Drive Faults

  1. Keypad Reset: Press the STOP / RESET key on the front FR-DU04 control panel or attached FR-PU04 parameter unit while the fault code is displayed. Important: Deactivate all forward and reverse run command signals (STF / STR) before resetting to avoid sudden motor restart.
  2. Control Terminal Reset (RES): Connect the Reset input terminal (RES) to the common terminal (SD in sink logic) for at least 0.1 seconds, then open the connection. Terminal RES is mapped via multi-function input parameters Pr. 180 to Pr. 183.
  3. PC Software Tool: Connect a PC to the PU interface connector using an RS-485 serial communication converter, open Mitsubishi setup software / FR Configurator, and select “Inverter Reset / Clear Fault” in the diagnosis menu.
  4. RS-485 Communication Reset: Send an Inverter Reset instruction command (HFD00) over the RS-485 serial communication network via the PU communication channel.
  5. Main Power Cycle: Switch OFF the incoming main 3-phase AC power, wait until the control panel display and the red CHARGE LED turn completely off (allow at least 10 minutes for capacitor discharge), then restore AC mains power.
⚠️ High-Voltage & Permanent Magnet Safety Warning: Because the MD-AX520 operates high-efficiency permanent magnet (MELIPM / MM-CF) synchronous motors, dangerous high voltage is generated across output terminals U, V, and W as long as the motor rotor is spinning, even if the drive unit is completely disconnected from power. Always ensure the motor shaft has stopped completely, and verify with a calibrated multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [P/+] and [N/-] (and confirm the red CHARGE lamp is completely unlit) before servicing wiring or touching terminals.