Mitsubishi MD-AX520 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Mitsubishi Electric MD-AX520 MELIPM permanent magnet motor drive unit series. Search or filter through the complete fault code directory below.
Power Range
0.5 – 7.0 kW (0.75 – 10 HP)
Supply Voltage
200–230V AC (3-Phase)
Control Modes
Sensorless Sine-Wave PWM (PM Motor)
Operator Interface
FR-DU04 Control Panel / FR-PU04
Complete Mitsubishi MD-AX520 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type E.OC1, E.OV1, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| E.OC1 Acceleration time overcurrent | Cause: The acceleration torque is beyond the drive unit capability; Outputs U, V, and W are in a short circuit or ground fault; The motor restarted during coasting; Or start signal given with only R1/S1 power. Remedy:
|
| E.OC2 Constant speed time overcurrent | Cause: Excessive load was applied instantaneously; Outputs U, V, and W resulted in a short circuit or ground fault during constant-speed operation; Drive capacity does not match motor. Remedy:
|
| E.OC3 Deceleration time overcurrent | Cause: The deceleration torque is beyond the drive unit capability; Outputs U, V, and W resulted in a short circuit or ground fault during deceleration; Mechanical brake operates too early. Remedy:
|
| E.GF Output side ground fault overcurrent | Cause: Any of outputs U, V, W is in a ground fault. Remedy:
|
| E.OV1 Acceleration time overvoltage | Cause: Surge compounded with power during acceleration; Regenerative energy handling capability is insufficient. Remedy:
|
| E.OV2 Constant speed time overvoltage | Cause: Surge compounded with power; Load increased suddenly activating stall prevention; Regenerative energy capability insufficient. Remedy:
|
| E.OV3 Deceleration time overvoltage | Cause: Deceleration torque beyond drive capability; Regenerative energy capability insufficient; Surge compounded with power during deceleration. Remedy:
|
| E.THT Electronic overcurrent protection (Transistor) | Cause: The motor and drive unit are operated under overload. Remedy:
|
| E.THM Electronic overcurrent protection (Thermal) | Cause: The motor and drive unit are operated under overload. Remedy:
|
| E.IPF Instantaneous power failure | Cause: An instantaneous power failure occurred (15 to 100ms). Remedy:
|
| E.UVT Undervoltage | Cause: Large-capacity equipment started nearby; Jumper across terminals P/+-P1 disconnected. Remedy:
|
| E.FIN Fin overheat | Cause: Heat sink temperature exceeded permissible value; Cooling fan failed. Remedy:
|
| E.OHT External fault | Cause: The external relay or equivalent component connected to the terminal assigned to OH signal operated. Remedy:
|
| E.PUE PU disconnection | Cause: Connection fault of operation panel/parameter unit; RS-485 communication interrupted; Comm retries exceeded. Remedy:
|
| E.RET Retry excess | Cause: The number of alarms that occurred exceeded the retry setting. Remedy:
|
| E.OLT Stall stop | Cause: Motor overload activated stall prevention consecutively; E.OLT output selected in Pr. 156. Remedy:
|
| E.LF Phase failure | Cause: A phase failure occurred in any of the outputs U, V, W. Remedy:
|
| E.P24 P24 Short Circuit | Cause: The PC terminal output of the control circuit is in a short circuit. Remedy:
|
| E.CTE Panel power supply | Cause: The power supply cable of the operation panel or parameter unit is in a short circuit. Remedy:
|
| E.OPT Option fault | Cause: The plug-in option fitted is other than specified; Power switched on with high power factor converter setting (Pr. 30 = 2). Remedy:
|
| E.CPU / E.6 / E.7 CPU fault | Cause: The CPU malfunctioned or failed. Remedy:
|
| E.PE Storage device fault | Cause: The storage device failed. Remedy:
|
| E.BE Brake circuit fault | Cause: The regenerative brake circuit failed. Remedy:
|
| OL Overload 1 (Alarm) | Cause: Acceleration/Constant speed/Deceleration time overcurrent; Stall stop activated. Remedy:
|
| oL Overload 2 (Alarm) | Cause: Main circuit DC voltage more than 390V (Deceleration-time overvoltage). Remedy:
|
| RB Brake duty (Alarm) | Cause: More than 85% of the permissible value (Deceleration-time overvoltage). Remedy:
|
| TH Motor overheat (Alarm) | Cause: More than 85% of the electronic overcurrent protection level. Remedy:
|
| FN Fan failure (Alarm) | Cause: Cooling fan fault; Fin overheat. Remedy:
|
| Err Operation error | Cause: Parameter changing during external operation; Value outside range; RES signal remains ON; Connection fault. Remedy:
|
| PS Emergency stop operation | Cause: STOP/RESET key was pressed during external operation. Remedy:
|
| E.rE4 Copy error | Cause: Parameters were copied to a different model. Remedy:
|
How to Clear & Reset Mitsubishi MD-AX520 Drive Faults
- Keypad Reset: Press the STOP / RESET key on the front FR-DU04 control panel or attached FR-PU04 parameter unit while the fault code is displayed. Important: Deactivate all forward and reverse run command signals (STF / STR) before resetting to avoid sudden motor restart.
- Control Terminal Reset (RES): Connect the Reset input terminal (RES) to the common terminal (SD in sink logic) for at least 0.1 seconds, then open the connection. Terminal RES is mapped via multi-function input parameters Pr. 180 to Pr. 183.
- PC Software Tool: Connect a PC to the PU interface connector using an RS-485 serial communication converter, open Mitsubishi setup software / FR Configurator, and select “Inverter Reset / Clear Fault” in the diagnosis menu.
- RS-485 Communication Reset: Send an Inverter Reset instruction command (HFD00) over the RS-485 serial communication network via the PU communication channel.
- Main Power Cycle: Switch OFF the incoming main 3-phase AC power, wait until the control panel display and the red CHARGE LED turn completely off (allow at least 10 minutes for capacitor discharge), then restore AC mains power.
⚠️ High-Voltage & Permanent Magnet Safety Warning:
Because the MD-AX520 operates high-efficiency permanent magnet (MELIPM / MM-CF) synchronous motors, dangerous high voltage is generated across output terminals U, V, and W as long as the motor rotor is spinning, even if the drive unit is completely disconnected from power. Always ensure the motor shaft has stopped completely, and verify with a calibrated multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [P/+] and [N/-] (and confirm the red CHARGE lamp is completely unlit) before servicing wiring or touching terminals.