Panasonic MINAS A7 Servo Drive Fault Codes & Diagnostic Guide
Complete error code reference directory, alarm causes, and field-tested troubleshooting procedures for the Panasonic MINAS A7 high-speed AC servo driver series (including A7N RTEX & A7B EtherCAT). Search or filter through the complete fault code directory below.
Power Range
50 W – 22 kW
Supply Voltage
100V / 200V / 400V AC (1P / 3P)
Control Modes
Position, Speed, Torque & Full-Closed
Operator / Network Interface
EtherCAT, RTEX & PANATERM V7
Complete Panasonic MINAS A7 Servo Drive Fault Code Directory
Use the search box in the table below to quickly find your error code (e.g., type Err 16.0, Err 12.0, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| Err11.0.0 Control power supply undervoltage protection | Cause: The voltage across PN of the control power supply converter has fallen and dropped below the specified value.
Remedy: Measure the L1C-L2C line voltage of connector and terminal block. Take the following actions:
|
| Err12.0.0 Overvoltage protection | Cause: Power supply voltage exceeds the allowable input voltage across PN of the converter, is too high, or a surge occurred.
Remedy: Measure the line voltage (L1, L2, L3) and input correct voltage. Remove phase advance capacitor.
|
| Err13.0.0 to Err13.0.1 Main power supply undervoltage protection (voltage across PN) Err13.1.0 Main power supply undervoltage protection (AC interrupt detection) | Cause: Voltage across PN has dropped below specified value, or instantaneous power interruption occurred.
Remedy: Measure line voltage (L1, L2, L3).
|
| Err13.2.0 Main power supply phase loss protection (AC interception detection) | Cause: Missing phases of connectors (L1, L2, L3) detected.
Remedy: Check connection of main power input line. Measure voltage between connectors.
|
| Err14.0.0 Overcurrent protection 1 Err14.1.0 Overcurrent protection 2 | Cause: Current through the converter exceeded specified value.
Remedy:
|
| Err14.1.1 Overheat protection 2 | Cause: Temperature of the power element has risen over specified temperature.
Remedy:
|
| Err14.1.2 Overheat protection 3 | Cause: The dynamic brake circuit overheated and the thermal fuse has blown. Remedy: Replace the servo driver. |
| Err15.0.0 Overheat protection 1 | Cause: Temperature of the heat sink has risen over specified temperature.
Remedy: Ensure ambient temperature does not exceed operating range.
|
| Err15.1.0 Encoder overheat error protection | Cause: Encoder temperature exceeded error level.
Remedy:
|
| Err16.0.0 Overload protection | Cause: Actual torque command exceeds overload level (Pr5.12).
Remedy: Check torque waveform and overload warning display.
|
| Err16.1.0 Torque saturation error protection | Cause: Torque saturation condition continued based on Pr7.16 or Pr6.57 settings. Remedy: Check the operating state of this product and take the same action as for Err16.0.0. |
| Err18.0.0 Regenerative overload protection | Cause: The regenerative energy has exceeded the processing capacity of the regenerative resistor.
Remedy: Check the regenerative resistance load factor. Take the following actions:
|
| Err18.1.0 Regenerative transistor error protection | Cause: The regenerative drive transistor of this product is malfunctioning. Remedy: Replace the servo driver. |
| Err21.0.0 - Err21.0.1 Err21.0.90 Encoder communication disconnection error protection | Cause: Communication between the encoder and this product has been interrupted a set number of times, triggering the disconnection detecting function. Remedy:
|
| Err21.1.0 - Err21.1.3 Encoder communication error protection | Cause: This is primarily a data error due to noise.
Remedy:
|
| Err23.0.0 Encoder communication data error protection | Cause: This is primarily a data error due to noise.
Remedy:
|
| Err24.0.0 Position deviation excess protection | Cause: The position deviation pulse has exceeded the setting for Pr0.14 "Position deviation excess setup".
Remedy: Take the following actions:
|
| Err24.1.0 Speed deviation excess protection | Cause: The difference between the internal position command speed and the actual speed (speed deviation) has exceeded the value set for Pr6.02 "Speed deviation excess setup". Precaution: Internal position command speed rise time and speed deviation increases if forcibly set to 0 by emergency stop. Remedy:
|
| Err25.0.0 Hybrid deviation excess protection | Cause: When in full-closed control, the load position from the external scale and the motor position from the encoder have shifted more than the number of pulses set by Pr3.28. Remedy:
|
| Err26.0.0 Overspeed protection | Cause: The motor rotational speed has exceeded the value set for Pr5.13 "Over-speed level setup". Remedy:
|
| Err26.1.0 2nd Overspeed protection | Cause: The motor rotational speed has exceeded the value set for Pr6.15 "2nd overspeed level setting". Remedy:
|
| Err27.1.0 Absolute clear protection | Cause: Absolute encoder multi-turn data clear was executed with Set-up Support Software (PANATERM ver.7). Remedy: Confirm that absolute encoder multi-turn data clear was executed. Note: This is a safety measure and not an error. Be sure to reset control power source. |
| Err27.4.0 Position command error protection | Cause: The position command variation (value after electronic gear) exceeded the specified value. Remedy:
|
| Err27.5.0 Command generation error protection | Cause: An error, such as position command generation processing exceeding the computation range, has occurred. Remedy: Confirm that the electronic gear ratio and acceleration/deceleration constraints are fulfilled. |
| Err27.6.0 Operation command contention protection | Cause: (When Pr7.99 bit 0 = 1) A servo-on command was received by RTEX communication while frequency characteristics analysis (FFT) or trial run was executing. Remedy: Check whether the host device has sent a servo-on command by RTEX communication during FFT function or trial run execution. |
| Err27.6.1 Operation command contention protection | Cause: (When Pr7.99 bit 0 = 0) RTEX communication was established while frequency characteristics analysis (FFT) or trial run was executing. Remedy: Check whether RTEX communication has been established during FFT function or trial run execution. |
| Err27.6.2 Operation command contention protection | Cause: A request to switch to virtual full-closed control mode was received from PANATERM ver.7 during trial run, FFT, Z-phase search, or One Minute TUNING. Remedy: Check that a request to switch to virtual full-closed control mode was not transmitted by PANATERM during these operations. |
| Err27.7.0 Position information initialization error protection | Cause: Servo-on was executed during attribute C parameter enabling mode processing of a reset command in RTEX communication. Remedy: Check if in servo-off status during attribute C parameter enabling mode processing of a reset command in RTEX communication. |
| Err28.0.0 Pulse regeneration limit protection | Cause: The output frequency of pulse regeneration has exceeded the limit. Remedy:
|
| Err29.1.0 Counter overflow protection 1 | Cause: The calculated value of absolute encoder position/electronic gear ratio exceeded 32 bit width when position initialization was performed (e.g., after power on, during attribute C enabling, clearing multi-turn data). Remedy: Check the operational range for the absolute encoder (absolute external scale) position and review the electronic gear ratio. |
| Err29.2.0 - Err29.2.5 Counter overflow protection 2 | Cause: Semi-closed or Full-closed control: The value of position deviation in pulse units or command units has exceeded the specific limits (±2^30 or ±(2^34-1)). Remedy:
|
| Err31.0.□ Safety function error protection 1 | Cause: A safety function has detected an error. Remedy:
|
| Err31.2.□ Safety function error protection 2 | Cause: A safety function has detected an error. Remedy:
|
| Err33.0.0 Input overlapping assignment error 1 protection | Cause: There are overlapping input signal (SI1, SI2, SI3, and SI4) function assignment settings. Remedy:
|
| Err33.1.0 Input overlapping assignment error 2 protection | Cause: There are overlapping input signal (SI5, SI6, SI7, and SI8) function assignment settings. Remedy:
|
| Err33.2.0 Input function number error 1 protection | Cause: There are undefined numbers specified in input signal (SI1, SI2, SI3, and SI4) function assignments. Or there is an error in logical settings. When using External servo-on input (EX-SON), dynamic brake switching input (DB-OFF), forced alarm input (E_STOP) at input signals SI1, SI2, SI3, and SI4, only one or two control modes were set. Remedy:
|
| Err33.3.0 Input function number error 2 protection | Cause: Undefined numbers have been specified in the input signal (SI5, SI6, SI7, SI8) function assignment settings. Or there is an error in logical settings. When using External servo-on input (EX-SON), dynamic brake switching input (DB-OFF), forced alarm input (E_STOP) at input signals SI5, SI6, SI7, and SI8, only one or two control modes were set. Remedy:
|
| Err33.4.0 Output function number error 1 protection | Cause: An undefined number has been specified in the output signal (SO1) function assignment setting. Remedy:
|
| Err33.5.0 Output function number error 2 protection | Cause: There are undefined numbers specified in output signals (SO2 and SO3) function assignments. Remedy:
|
| Err33.8.0 Latch input assignment error protection | Cause: There are errors in latch correction pin (SI5, SI6, and SI7) function assignments. 1. EXT1, EXT2 and EXT3 are assigned to pins other than SI5 to SI7. 2. Not all the control modes have been assigned. Remedy:
|
| Err34.0.0 Motor movable range setup error protection | Cause: When a position command within the specified range is input, the motor has operated outside its movable range specified in Pr5.14 “Motor working range setup”. Possible causes: 1. The gain is not suitable. 2. The value set for Pr5.14 is low. 3. Conditions for forcibly issuing Err34.0.0 were fulfilled (Pr6.97). Remedy:
|
| Err34.1.0 Single-turn absolute movable range error protection | Cause: When an absolute encoder is connected and Pr0.15 “Absolute encoder setup” = 3, the motor (encoder) position has exceeded the motor movable range (encoder single-turn data). Remedy:
|
| Err36.□.0 EEPROM parameter error protection | Cause: Data in the parameter storage area has been damaged when reading the data from EEPROM at power-on. Remedy:
|
| Err37.□.0 EEPROM check code error protection | Cause: Data for EEPROM write confirmation was damaged when the data was read from the EEPROM at power-on. Remedy:
|
| Err38.0.0 Over-travel inhibit input protection 1 | Cause: Positive/negative direction over-travel inhibit inputs (POT, NOT) were both ON (when Pr5.04 = 0). Or one was ON when Pr5.04 = 2. Remedy:
|
| Err38.1.0 Over-travel inhibit input protection 2 | Cause: An operating command was received from Set-up Support Software while Pr5.04 = 0 and RTEX is off, and either POT or NOT are on. Or POT/NOT turned on while an operating command was in operation. Remedy:
|
| Err38.2.0 Over-travel inhibit input protection 3 | Cause: POT or NOT was set to a value other than Pr5.04 (disabled) while the assignment function implemented any of SI5 to SI7. Remedy:
|
| Err39.0.0 Analog input (AIN) excess protection | Cause: A voltage higher than that set in Pr4.24 “Analog input (AIN) excessive setting” was applied to analog input. Remedy:
|
| Err40.0.0 Absolute system down error protection | Cause: 1. The power supply to the absolute encoder and battery are down and capacitor voltage dropped. 2. The absolute encoder has not been cleared even once by the batteryless absolute encoder. Remedy:
|
| Err41.0.0 Absolute counter over error protection | Cause: The multi-turn counter of the absolute encoder has exceeded the specified value. Remedy:
|
| Err42.0.0 Absolute overspeed error protection | Cause: (Battery backup) 1. Motor speed exceeded specified value during power failure. 2. Encoder power interrupted during normal operation and switched to power failure mode, and speed exceeded value. Remedy:
|
| Err44.0.0 Single-turn counter error protection | Cause: A single-turn counter error has been detected. Remedy:
|
| Err45.0.0 Multi-turn counter error protection | Cause: A multi-turn counter error has been detected. Remedy:
|
| Err47.0.0 Absolute status error protection | Cause: The encoder turned more than the specified value during power-up. Remedy:
|
| Err50.0.0 External scale wiring error protection | Cause: Communication between the external scale and this product has been interrupted more than a set number of times. Remedy:
|
| Err50.1.□ External scale communication error protection | Cause: Primarily a data error due to noise. Communication error in data from external scale or cable connection error. Remedy:
|
| Err50.2.0 External scale communication data error protection | Cause: Primarily a data error due to noise. Error in communication data even though there is no communication error. Remedy:
|
| Err51.0.0 External scale status error protection 0 | Cause: 1 was returned for bit 0 of the external scale error code (ALMC). Remedy:
|
| Err51.1.0 External scale status error protection 1 | Cause: 1 was returned for bit 1 of the external scale error code (ALMC). Remedy:
|
| Err51.2.0 External scale status error protection 2 | Cause: 1 was returned for bit 2 of the external scale error code (ALMC). Remedy:
|
| Err51.3.0 External scale status error protection 3 | Cause: 1 was returned for bit 3 of the external scale error code (ALMC). Remedy:
|
| Err51.4.0 External scale status error protection 4 | Cause: 1 was returned for bit 4 of the external scale error code (ALMC). Remedy:
|
| Err51.5.0 External scale status error protection 5 | Cause: 1 was returned for bit 5 of the external scale error code (ALMC). Remedy:
|
| Err51.8.0 External scale and other error protection | Cause: An external scale error clear command was issued. Remedy:
|
| Err55.0.0 A-phase connection error protection | Cause: An error, such as a broken wire, has occurred in the A-phase wiring of the external scale. Remedy: Check the A-phase wiring of the external scale. |
| Err55.1.0 B-phase connection error protection | Cause: An error, such as a broken wire, has occurred in the B-phase wiring of the external scale. Remedy: Check the B-phase wiring of the external scale. |
| Err55.2.0 Z-phase connection error protection | Cause: An error, such as a broken wire, has occurred in the Z-phase wiring of the external scale. Remedy: Check the Z-phase wiring of the external scale. |
| Err68.□.□ Internal communication processing error protection (Includes Err68.0.0 through Err68.21.0) | Cause: An error has occurred in the internal microcomputer-to-microcomputer communication. Remedy:
|
| Err70.0.0 U-phase current detector error protection 1 | Cause: There is an error in the U-phase current detection offset value. Remedy:
|
| Err70.0.1 U-phase current detector error protection 2 | Cause: Detected U-phase current sticking. Remedy:
|
| Err70.1.0 W-phase current detector error protection 1 | Cause: There is an error in the W-phase current detection offset value. Remedy:
|
| Err70.1.1 W-phase current detector error protection 2 | Cause: Detected W-phase current sticking. Remedy:
|
| Err72.0.0 Thermal error protection | Cause: A thermal error has occurred. Remedy:
|
| Err75.0.□ External memory access error protection (Err75.0.0 to Err75.0.1) | Cause: An error occurred in the access process with peripheral components. Remedy:
|
| Err77.0.0 Microcomputer error protection 1 | Cause: An error has occurred in the internal microcontroller. Remedy:
|
| Err77.2.0 Microcomputer error protection 3 | Cause: An error has occurred in the internal microcontroller. Remedy:
|
| Err77.6.0 Microcomputer error protection 7 | Cause: An error has occurred in the internal microcontroller. Remedy:
|
| Err80.3.0 Incomplete PLL error protection | Cause: Phase lock (PLL lock) between RTEX communication synchronization could not be completed even when one second had elapsed since the start of the synchronization process. RTEX communication cannot be established (stopped with synchronization incomplete). Remedy:
|
| Err82.0.0 RTEX node address setting error protection | Cause: The rotary switch value for node address setting was set to a value other than 0 to 31. Remedy: Check the rotary switch value for node address setting. After correctly setting the rotary switch value for node address setting (0 to 31), restart the control power for the product. |
| Err83.0.0 RTEX continuous communication error protection 1 | Cause: An error (CRC error) that occurred during reading of received data addressed to the local node persisted for the number of times set for Pr7.95 “RTEX continuous communication error protection 1 detection count”. Remedy:
|
| Err83.1.0 RTEX continuous communication error protection 2 | Cause: An error (CRC error, receiving failure, or cyclic data error) that occurred during reading of received data addressed to the local node persisted for the number of times set for Pr7.96 “RTEX continuous communication error protection 2 detection count”. Remedy:
|
| Err84.0.0 RTEX communication timeout error protection | Cause: The number of incidences set with Pr7.97 “RTEX communication timeout error protection detection count” continues when communication data has not been received and the RTEX communication IC is not outputting the receipt interrupt processing initialization signal (receiving failure). Remedy:
|
| Err84.3.0 RTEX communication synchronization error protection | Cause: An error occurred in the internal synchronization process. Remedy:
|
| Err84.5.0 RTEX communication cycle error protection | Cause: A receive interrupt startup signal was received from the RTEX communication IC, but there was an error in the output cycle, and RTEX communication was out of sync. Remedy:
|
| Err85.0.0 Retracting operation completion (I/O) | Cause: Triggered when the I/O retracting operation completes normally. The alarm generated during the retracting operation is switched by Pr6.86:bit 15. Remedy:
|
| Err85.1.0 Retracting operation completion (communication) | Cause: Triggered when the communication retracting operation completes normally. The alarm generated during the retracting operation is switched by Pr6.86:bit 15. Remedy:
|
| Err85.2.0 Retracting operation error | Cause: Issued when a retracting operation cannot be executed or is interrupted, such as: - Pr6.85 setting has an error. - Retracting enabled but comm cycle < 250 μs. - Over-travel inhibit (POT, NOT) or STOP input detected during operation. - Main power OFF, servo-off, alarm triggered, or STO input during operation. - Execution conditions fulfilled while inhibit/stop input was detected. - Execution conditions fulfilled during trial run or frequency measurement. - Could not start due to servo-off state. Remedy:
|
| Err86.0.0 / Err86.1.0 RTEX cyclic data error protection 1 & 2 | Cause: There is an error in cyclic command area data (C/R, MAC-ID, or cyclic command). There continued to be an error in Sub_Chk while in 32-byte mode for the number of times set for Pr7.98. Remedy:
|
| Err86.2.0 RTEX_Update Counter error protection | Cause: Update_Counter was not updated normally due to the cumulative total exceeding the number of times set for Pr7.38 “RTEX_Update_Counter error protection setup”. (Indicates mismatch in command update cycle between host and product). Remedy:
|
| Err87.0.0 Forced alarm input protection | Cause: Forced alarm input (E-STOP) has been entered. Remedy:
|
| Err87.1.0 Retracting operation completion (I/O) | Cause: The I/O retracting operation has been completed normally. Remedy:
|
| Err87.2.0 Retracting operation completion (communication) | Cause: The communication retracting operation has been completed normally. Remedy: This is a safety measure to notify the operator that the retracting operation has been run, and is not a problem as long as the retracting operation was intended. Be sure to run homing after clearing the alarm. |
| Err87.3.0 to Err87.3.6 Retracting operation error | Cause: Issued in the following cases when retracting operation execution is disabled:
Remedy:
|
| Err90.2.0 RTEX multi-axis synchronization error protection | Cause: A communication error occurred or communication was lost while transitioning to synchronization establishment in full-synchronous mode. Remedy: Take the same action as for Err83.0.0 "RTEX continuous communication error protection 1" or Err84.0.0 "RTEX communication timeout error protection". |
| Err91.1.0 RTEX Command error protection | Cause: Issued when a cyclic command is defined (byte 1:bits 6 to 4), but is not received normally.
Remedy:
|
| Err91.3.0 RTEXCommand error protection2 | Cause: Issued when the timing of a homing cancellation does not enable cancellation during homing command execution.
Remedy: Check whether homing command is being canceled in proximity to the home signal. (We recommend stopping the motor before canceling.) |
| Err92.0.0 Encoder data recovery error protection | Cause: The internal position information initialization process was not executed normally when in semi-closed control and absolute mode. Remedy:
|
| Err92.1.0 External scale data recovery error protection | Cause: The internal position information initialization process was not executed normally when in full-closed control and absolute mode. Remedy:
|
| Err92.3.0 to Err92.3.2 Multi-turn data upper limit value disagreement error protection | Cause: In continuous rotating absolute encoder mode, the encoder multi-turn data upper-limit value does not agree with the multi-turn data upper-limit value for the driver parameters. Remedy: Check the parameter setup values. |
| Err93.0.0 Parameter setup error protection 1 | Cause: The electronic gear ratio exceeded the allowable range. Remedy: Check the value set for the parameter, and set it so that the electronic gear ratio is in the range of 1/1000 to 128000 times. |
| Err93.2.0 Parameter setup error protection 2 | Cause: The external scale ratio was outside the allowable range. Remedy: Check the value set for the parameter, and set it so that it is in the range of 1/40 ≤ External scale ratio ≤ 20480. |
| Err93.3.0 to Err93.3.5 External scale connection error protection | Cause: The value set for Pr3.23 "External scale selection" does not match the external scale type for the connected serial communication type. Remedy:
|
| Err93.5.0 Parameter setup error protection 4 | Cause:
Remedy: Check the parameter setup values. For the correct setting conditions, see "4.1.4 Supported Mode Table". |
| Err93.8.0 Parameter setup error protection 6 | Cause:
Remedy: Check the parameter setup values. |
| Err94.2.0 Homing error protection | Cause: An error occurred during the profile homing operation. Remedy: Confirm that there are no errors in sensor settings, etc. |
| Err94.3.0 Homing error protection 2 | Cause:
Remedy:
|
| Err95.□.0 Motor automatic recognition error protection □ | Cause: The motor and this product do not match. Remedy: Replace the motor with one that matches this product. |
| Err96.4.0 Host controller error protection 3 | Cause: An error occurred in the host controller of this product. (Related to RTEX communication synchronization setup delays). Remedy:
|
| Err96.6.0 Host controller error protection 5 | Cause: An error occurred in the host controller of this product. Remedy:
|
| Err98.1.0 to Err98.3.0 RTEXHardware error protection □ | Cause: An error occurred in the internal RTEX communication circuit. Remedy:
|
| Err98.5.0 Hardware self-diagnostic error protection 1 | Cause: The current detector has malfunctioned. Remedy: Replace the servo driver with a new one. |
| Other numbers Other error protection | Cause:
Remedy:
|
| System error protection (7-segment display: 31, 32, 33, 35, 36, 37) | Cause: An error has occurred inside the product. Remedy:
|
How to Clear & Reset Panasonic MINAS A7 Servo Drive Faults
- Alarm Clear Input (A-CLR): Apply an ON signal to the digital input configured as A-CLR (Alarm Clear) via the X4 / control connector for at least 120 ms. Note that thermal-related alarms (such as Err 16.0 Overload Protection) have an enforced internal cooling period of 10 to 30 seconds before reset acceptance.
- PANATERM V7 PC Tool: Connect your PC via the USB port on the front panel, launch Panasonic PANATERM V7 software, navigate to the “Alarm” / “Troubleshooting” window, and click “Clear Alarm”.
- Fieldbus Network Reset (EtherCAT / RTEX): For MINAS A7B (EtherCAT), write the CiA402 Fault Reset bit (Controlword 6040h bit 7, transition from `0` to `1`). For MINAS A7N (RTEX), execute the network alarm reset command byte from your motion master controller.
- Front Panel Button Operation: On models equipped with the integrated 7-segment display, press the MODE / SET keys to enter Alarm Clear mode (d05 or equivalent auxiliary function) and hold the designated key sequence to clear current latched alarms.
- Main & Control Power Cycle: For non-clearable protection trips (such as Err 14.0 Overcurrent, Err 15.0 Overvoltage, or CPU errors), turn off both main power (L1, L2, L3) and control power (L1C, L2C). Wait until the front CHARGE LED turns off completely before reapplying power.
⚠️ High-Voltage Electrical Safety Warning:
Even after turning off main power, the internal smoothing capacitors remain dangerously charged. Always check that the red front-panel CHARGE LED is completely extinguished, and verify with a calibrated digital multimeter that the DC bus voltage across terminals [P] and [N] (or B1/B2) is strictly below 50VDC before inspecting motor leads (U, V, W), servicing dynamic brake connections, or handling terminal blocks.