ABB

Home / ABB

ABB Drives Fault Codes & Troubleshooting

Comprehensive fault code reference directory for ABB low-voltage AC drives, medium-voltage inverters, DC converters, and high-performance servo motion systems. Select your drive model series below to access parameter checks, root cause analysis, and physical inspection workflows.

24 AC Inverter Series 2 DC Converter Series 3 Servo Motion Drives

ABB AC Variable Frequency Drives

24 Models
ACS880 →

Industrial Single & Multidrive (Direct Torque Control – DTC)

ACS580 →

Standard General Purpose Drive (0.75 to 500 kW)

ACS355 →

General Machinery OEM Drive with Integrated Safe Torque Off (STO)

ACS180 →

Compact Machinery Micro Drive (0.25 to 22 kW)

ACS150 →

Classic Component Micro Drive with Built-in Keypad & Potentiometer

ACS310 →

Dedicated Centrifugal Pump and Fan Control Drive

ACH180 →

Compact HVAC Drive for Air Handling Units, Fans & Compressors

ACS380 →

Advanced Machinery Drive with Customized Icon Keypad

ACS550 →

Classic General Purpose Inverter (Assistant Control Panel)

ACS560 →

Basic General Purpose Drive for Essential Industrial Needs

ACS800 →

Heavy Industrial Legacy Inverter (Direct Torque Control Architecture)

ACS850 →

High-Performance Machinery Drive Module (Crane & Hoist Control)

ACSM1 →

High-Performance Motion Control Module for Synchronous & Asynchronous Motors

ACH480 →

Building Automation Drive for Direct Cabinet HVAC Mounting

ACH550 →

Classic Dedicated HVAC Variable Frequency Drive

ACH580 →

Ultra-Low Harmonic HVAC & Building Automation Inverter

ACQ80 →

Solar Pump Micro Drive for Off-Grid Agricultural & Water Systems

ACQ580 →

Dedicated Water and Wastewater Pumping Drive (Multi-Pump Control)

ACQ810 →

Heavy-Duty Water Industry Inverter Module (Submersible Pumps)

ACS255 →

Micro Inverter with IP66 Washdown Enclosure Options

ACS280 →

Compact General Purpose Drive for Basic Machine Automation

ACS480 →

Compact Energy-Optimized Drive for Standard Pumps, Fans & Conveyors

ACS510 →

Standard Industrial Fan and Pump Application Inverter

ACS530 →

General Purpose Drive for Standard Variable and Constant Torque Loads

ABB Industrial DC Drives

2 Models

ABB Servo & Motion Drives

3 Models

Most Common ABB Drive Fault Codes

Diagnostic Quick Reference
Fault Code Hex / Legacy Fault Name Common Root Cause
2310 F0001 Overcurrent Short acceleration ramp, mechanical load jam, or motor output cable phase-to-phase short.
3210 F0002 DC Link Overvoltage Rapid motor deceleration causing excessive regenerative energy without a dynamic braking resistor.
2330 F0016 Earth / Ground Fault Leakage current to protective ground, damp motor terminal box, or motor stator insulation breakdown.
7122 F0009 Motor Overload Operating above motor Full Load Amps (FLA) for extended periods; check thermal model parameter group 35.
4310 F0003 Excess Temperature Clogged cabinet dust filters, internal cooling fan failure, or ambient temperature exceeding 40°C–50°C.
3130 F0020 Input Phase Loss Blown incoming 3-phase line fuse, unseated disconnect terminal, or severe utility voltage imbalance (>3%).

How to Clear & Reset ABB Faults

  1. Keypad Reset: On the standard or Assistant Control Panel, press the red RESET softkey (or STOP button).
  2. Digital Input (DI) Pulse: If hardwired for remote automation, pulse the programmed digital input (check Parameter 31.11 Fault reset selection in ACS580/ACS880).
  3. Drive Composer Software: Connect via USB on the control panel keypad and click “Reset” inside the Drive Composer monitoring dashboard.
  4. Power Cycle: Disconnect 3-phase line supply (and external 24V auxiliary power, if equipped), wait 5 minutes until all LEDs extinguish, and reapply power.
⚠️ High-Voltage Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus capacitor voltage measures strictly below 50VDC before opening enclosure covers or inspecting terminals U2, V2, and W2 on any ABB drive.