Delta ASDA-A+ servo drive

Home / Delta / Delta ASDA-A+ servo drive

Delta ASDA-A+ Servo Drive Alarm Codes & Diagnostic Guide

Complete alarm code reference directory, trip causes, and step-by-step diagnostic procedures for the Delta ASDA-A+ high-power AC servo drive series. Search or filter through the complete alarm code directory below.

High-Power Precision AC Servo System Power: 3.0 to 7.5 kW (4.0 to 10 HP) 20-bit (1,280,000 ppr) Optical Encoder & Modbus
Power Range 3.0 – 7.5 kW (4 – 10 HP)
Supply Voltage 200–230V AC (3-Phase)
Control Modes Position (Pt/Pr), Speed, Torque
Operator Interface Integrated 5-Digit 7-Segment Keypad

Complete Delta ASDA-A+ Servo Drive Alarm Code Directory

Use the search box in the table below to quickly find your alarm code (e.g., type AL001, AL003, or Overcurrent).

Fault Code and MeaningCause and Remedy
ALE01

Overcurrent

Cause:

  • Short-circuit at drive output (U, V, W).

  • Motor wiring error.

  • IGBT error (Heat sink overheated).

  • Control parameter setting error.

  • Control command setting error (unstable input).




Remedy:



  • Check wiring connections; repair short-circuited wires and avoid exposed metal.

  • Follow the wiring steps in the user manual to reconnect wiring.

  • Contact your distributor for assistance or contact Delta.

  • Set settings back to factory default and re-adjust.

  • Ensure input command frequency is stable; activate filter function.


ALE02

Overvoltage

Cause:

  • The main circuit voltage has exceeded its maximum allowable value.

  • Input power error (Incorrect power input).




Remedy:



  • Use voltmeter to check input voltage; use correct power supply or stabilizing power.


ALE03

Undervoltage

Cause:

  • The main circuit voltage is below its minimum specified value.

  • No input voltage at main circuit.

  • Input power error (Incorrect power input).




Remedy:



  • Reconfirm voltage wiring.

  • Reconfirm power switch.

  • Use correct power supply or serial stabilizing power.


ALE05

Regeneration error

Cause:

  • Regenerative resistor is not connected.

  • Regenerative switch transistor fault.

  • Parameter setting is in error.




Remedy:



  • Reconnect regenerative resistor.

  • Contact your distributor for assistance or contact Delta.

  • Confirm specifications and correctly reset parameter again.


ALE06

Overload

Cause:

  • The drive has exceeded its rated load during continuous operation.

  • Control system parameter setting is incorrect (mechanical vibration or Accel/Decel too fast).

  • The wiring of drive and encoder is in error.




Remedy:



  • Increase motor capacity or reduce load.

  • Adjust gain value of control circuit; Decrease Accel/Decel time setting.

  • Ensure all wiring is correct (Check U, V, W and encoder).


ALE07

Overspeed

Cause:

  • Speed input command is not stable (too much fluctuation).

  • Over-speed parameter setting is defective (value too low).




Remedy:



  • Ensure input command frequency is stable and activate filter function (P1-06, P1-07, P1-08).

  • Correctly set over-speed parameter setting (P2-34).


ALE08

Abnormal pulse control command

Cause:

  • Pulse command frequency is higher than rated input frequency.




Remedy:



  • Correctly set the input pulse frequency.


ALE09

Excessive deviation

Cause:

  • Maximum deviation parameter setting is too small.

  • Gain value is too small.

  • Torque limit is too low.

  • There is an overload.




Remedy:



  • Increase the parameter setting value of P2-35.

  • Correctly adjust gain value.

  • Correctly adjust torque limit value.

  • Reduce external applied load or re-estimate the motor capacity.


ALE10

Watch dog execution time out

Cause:

  • Watch dog execution error.




Remedy:



  • Check and reset the power supply.

  • If abnormal conditions persist after reset, contact distributor or Delta.


ALE11

Encoder error (Position detector fault)

Cause:

  • The wiring of encoder is in error.

  • Encoder is loose.

  • The wiring of encoder is defective (connections not tight).

  • Encoder is damaged.

  • The circuit (loop) of Encoder is in error.




Remedy:



  • Ensure all wiring is correct according to user manual.

  • Install the motor again.

  • Conduct the wiring again.

  • Repair or replace the motor.

  • Repair or replace the drive.


ALE12

Adjustment error

Cause:

  • The setting value of drift adjustment has exceeded its maximum allowable value.




Remedy:



  • Remove CN1 wiring.

  • Execute the drift adjustment again (Set P2-08 to 20 first, and then set P4-10 to 5).

  • If error persists, contact distributor or Delta.


ALE13

Emergency stop activated

Cause:

  • Emergency stop switch is activated.




Remedy:



  • Activate (reset) emergency stop switch.


ALE14

Reverse (CWL) limit switch error

Cause:

  • Reverse limit switch is activated.

  • Servo system is not stable.




Remedy:



  • Activate (reset) reverse limit switch.

  • Modify parameter setting and re-estimate motor capacity.


ALE15

Forward (CCWL) limit switch error

Cause:


  • Forward limit switch is activated.

  • Servo system is not stable.




Remedy:


  • Activate forward limit switch.

  • Modify parameter setting and re-estimate motor capacity.


ALE16

IGBT temperature error

Cause:


  • The drive has exceeded its rated load during continuous operation.

  • Short-circuit at drive output.




Remedy:


  • Increase motor capacity or reduce load.

  • Ensure all wiring is correct.


ALE17

Memory error

Cause:

Data error in Memory read-out / write-in.



Remedy:

If the error does not clear after resetting the power supply, please contact your distributor for assistance or contact with Delta.
ALE18

DSP communication error

Cause:

Control power is in error.



Remedy:

If the error does not clear after resetting the power supply, please contact your distributor for assistance or contact with Delta.
ALE19

Serial communication error

Cause:


  • Communication parameter setting is defective.

  • Communication address is incorrect.

  • Communication value is incorrect.




Remedy:


  • Correctly set parameter setting.

  • Correctly set communication address.

  • Correctly set communication value.


ALE20

Serial communication time out

Cause:


  • Setting value in time out parameter is not correct.

  • Not receiving communication command for a long time.




Remedy:


  • Correctly set P3-07.

  • Tighten the communication cable, make sure the communication cable is not damaged and ensure all wiring is correct.


ALE21

Command write-in error

Cause:

Control power is in error.



Remedy:

If the error does not clear after resetting the power supply, please contact your distributor for assistance or contact with Delta.
ALE22

Input power phase loss

Cause:

Control power supply is in error.



Remedy:

If the fault does not clear even when the three-phase power is connected correctly, please contact your distributor for assistance or contact with Delta.
ALE23

Pre-overload warning

Cause:

The drive is going to overload.



Remedy:


  1. Please refer to the correction actions of ALE06.

  2. Increase the setting value of P1-56 or set P1-56 to 100 and above.


ALE97

Internal command execution time out

Cause:

An error occurs when internal command is executing.



Remedy:

If the error does not clear after resetting the power supply, please contact your distributor for assistance or contact with Delta.
ALE98

DSP communication error

Cause:

Maybe the hardware is damaged.



Remedy:

If the error does not clear after resetting the power supply, please contact your distributor for assistance or contact with Delta.
ALE99

DSP communication error

Cause:

Maybe the hardware is damaged.



Remedy:

If the error does not clear after resetting the power supply, please contact your distributor for assistance or contact with Delta.
ALE04

"Mismatch" error

Cause:

The type of the servo motor is incorrect.



Remedy:

Repair or replace the servo drive or the servo motor.
ALE24

Encoder error (Position detector fault)

Cause:

Maybe the Encoder is damaged.



Remedy:

If the error does not clear after resetting the power supply, please contact your distributor for assistance or contact with Delta.
ALE25

Encoder error (Position detector fault)

Cause:

The servo drive automatically detect the servo motor is in error.



Remedy:


  1. Please connect the grounding (green color) of U, V, W terminal to the heatsink of the servo drive.

  2. Ensure that the encoder signal cables are placed in separate conduits from the cables connected to R, S, T and U, V, W terminals to prevent the interference.

  3. Please use shielded cables for Encoder wiring.


How to Clear & Reset Delta ASDA-A+ Servo Drive Alarms

  1. Digital Input Reset (ARST): Apply a momentary contact pulse to the external digital input configured as ARST (Alarm Reset, function code 0x02) via parameters P2-10 to P2-17 for at least 100 milliseconds.
  2. Keypad Reset: Diagnose and resolve the cause of the alarm trip, navigate to parameter P0-01 on the front 5-digit LED keypad, and enter value 1 (or execute the keypad reset sequence) to clear the error.
  3. Delta ASDA-Soft PC Tool: Connect your PC via the RS-232 / RS-485 serial communication port, launch ASDA-Soft, navigate to the Alarm Information / Diagnostics tab, and click “Clear Alarm”.
  4. Modbus Serial Reset: Transmit an alarm clear command by writing value 0x0001 to parameter address 0001H (P0-01) over the built-in RS-485 / RS-422 Modbus serial communication link.
  5. Power Cycle: Disconnect AC main circuit line power (R, S, T) and control circuit power (L1c, L2c), wait until the internal CHARGE LED and keypad display turn completely off (approx. 5 minutes for bus capacitor discharge), then restore mains power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 25VDC across terminals [P+] and [-] (or [P+] and [D]) and ensure that the red CHARGE LED is completely extinguished before opening terminal covers or servicing motor power terminals U, V, and W on the Delta ASDA-A+ servo drive.