Delta CP2000 drive

Home / Delta / Delta CP2000 drive

Delta CP2000 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and field troubleshooting procedures for the Delta CP2000 intelligent sensorless vector control series. Search and identify error codes below.

HVAC & Fan/Pump Vector Drive Power: 0.75 to 400 kW (1.0 to 536 HP) Built-in BACnet & 10k Step PLC
Power Range 0.75 – 400 kW (1 – 536 HP)
Supply Voltage 230V / 460V / 575V / 690V AC
Control Modes V/F, SVC, PMSVC Control
Operator Interface KPC-CC01 Multi-Line LCD Keypad

Complete Delta CP2000 Drive Fault Code Directory

Use the search box in the table below to quickly find your error code (e.g., type ocA, ovn, GFF, or Overheating).

Fault Code and MeaningCause and Remedy

CE1



Communication error 1

(RS-485 Modbus illegal function code)

Cause:

  • Incorrect communication command from upper unit.

  • Malfunction caused by interference.

  • Different communication setting from the upper unit.

  • Disconnection or bad connection of the cable.




Remedy:

  • Check if the communication command is correct.

  • Verify the wiring and grounding of the communication circuit. Separate communication circuit from main circuit or wire at 90 degrees.

  • Check if the setting for Pr.09-02 is the same as the setting for the upper unit.

  • Check the cable and replace it if necessary.



CK1



Communication command error 1

(Keypad communication data, illegal function code)

Cause:

  • Incorrect communication command from keypad.

  • Malfunction caused by interference.

  • Different communication setting from keypad.

  • Disconnection or bad connection of the cable.




Remedy:

  • Remove the keypad and then reconnect it to the motor drive.

  • Verify the wiring and grounding. Separate communication circuit from main circuit.

  • Check if the Baud rate = 19200 bps, Format = RTU8, N, 2.

  • Check the cable and replace it if necessary.



CE2



Communication error 2

(RS-485 Modbus illegal data address)

Cause:

  • Incorrect communication command from upper unit.

  • Malfunction caused by interference.

  • Different communication setting from the upper unit.

  • Disconnection or bad connection of the cable.




Remedy:

  • Check if the communication command is correct.

  • Verify wiring and grounding. Separate communication circuit from main circuit.

  • Check if Pr.09-02 setting matches the upper unit.

  • Check the cable and replace it if necessary.



CK2



Communication address error

(Keypad communication data, illegal data address)

Cause:

  • Incorrect communication command from keypad.

  • Malfunction caused by interference.

  • Different communication setting from keypad.

  • Disconnection or bad connection of the cable.




Remedy:

  • Remove the keypad and then reconnect it to the motor drive.

  • Verify wiring and grounding. Separate communication circuit from main circuit.

  • Check if the Baud rate = 19200 bps, Format = RTU8, N, 2.

  • Check the cable and replace it if necessary.



CE3



Communication error 3

(RS-485 Modbus illegal data value)

Cause:

  • Incorrect communication command from upper unit.

  • Malfunction caused by interference.

  • Different communication setting from upper unit.

  • Disconnection or bad connection of the cable.




Remedy:

  • Check if the communication command is correct.

  • Verify wiring and grounding. Separate communication circuit from main circuit.

  • Check if Pr.09-02 setting matches the upper unit.

  • Check the cable and replace it if necessary.



CK3



Communication data error

(Keypad communication data, illegal data value)

Cause:

  • Incorrect communication command from keypad.

  • Malfunction caused by interference.

  • Different communication setting from keypad.

  • Disconnection or bad connection of the cable.




Remedy:

  • Remove the keypad and then reconnect it to the motor drive.

  • Verify wiring and grounding. Separate communication circuit from main circuit.

  • Check if the Baud rate = 19200 bps, Format = RTU8, N, 2.

  • Check the cable and replace it if necessary.



CE4



Communication error 4

(RS-485 Modbus data is written to read-only address)

Cause:

  • Incorrect communication command from upper unit.

  • Malfunction caused by interference.

  • Different communication setting from the upper unit.

  • Disconnection or bad connection of the cable.




Remedy:

  • Check if the communication command is correct.

  • Verify wiring and grounding. Separate communication circuit from main circuit.

  • Check if Pr.09-02 setting matches the upper unit.

  • Check the cable and replace it if is necessary.



CK4



Communication slave error

(Keypad communication data is written to read-only address)

Cause:

  • Incorrect communication command from keypad.

  • Malfunction caused by interference.

  • Different communication setting from keypad.

  • Disconnection or bad connection of the cable.




Remedy:

  • Remove the keypad and then reconnect it to the motor drive. If problem persists, check drive status (e.g. PLC function enablement).

  • Verify wiring and grounding. Separate communication circuit from main circuit.

  • Check if the Baud rate = 19200 bps, Format = RTU8, N, 2.

  • Check the cable and replace it if is necessary.



CE10



Communication error 10

(RS-485 Modbus transmission time-out)

Cause:

  • The upper unit does not transmit the communication command within Pr.09-03 setting time.

  • Malfunction caused by interference.

  • Different communication setting from the upper unit.

  • Disconnection or bad connection of the cable.




Remedy:

  • Check if the upper unit transmits the command within the setting time.

  • Verify wiring and grounding. Separate communication circuit from main circuit.

  • Check if Pr.09-02 setting matches the upper unit.

  • Check the cable and replace it if necessary.



CK10



Keypad communication time out

(Keypad communication data, transmission time-out)

Cause:

  • Incorrect communication command from keypad.

  • Malfunction caused by interference.

  • Different communication setting from keypad.

  • Disconnection or bad connection of the cable.




Remedy:

  • Remove the keypad and then reconnect it to the motor drive.

  • Verify wiring and grounding. Separate communication circuit from main circuit.

  • Check if the Baud rate = 19200 bps, Format = RTU8, N, 2.

  • Check the cable and replace it if necessary.



SE1



Save error 1

(Keypad COPY error 1: Keypad copy time-out)

Cause:

  • Communication connection error (interference, unacceptable command).

  • Keypad error.

  • Control board error.




Remedy:

  • Check if error occurs randomly or only when copying certain parameters.

  • If you cannot clear the error, please contact Delta.



SE2



Save error 2

(Keypad COPY error 2: parameter writing error)

Cause:

  • Attempting to copy new firmware version parameters to a drive with old firmware version.

  • Data error during copy process or failure to save to EEPROM.

  • Malfunction caused by interference.




Remedy:

  • Check the status of Data ROM and remove error causes first.

  • Verify wiring and grounding of the main circuit, control circuit, and encoder.

  • If you cannot clear the error, please contact Delta.



oH1



IGBT over-heating warning

(AC motor drive detects over-heating of IGBT)

Cause:

  • Ambient temperature or cabinet temperature too high.

  • Obstruction in ventilation hole or heat sink.

  • Cooling fan not running.

  • Insufficient ventilation space.

  • Drive overload or high carrier frequency.




Remedy:

  • Check ambient temperature and inspect ventilation holes.

  • Remove obstructions or replace cooling fan.

  • Install/add cooling fan or air conditioner to lower cabinet temperature.

  • Increase ventilation space.

  • Decrease loading, decrease carrier frequency, or replace with a larger capacity drive.



oH2



Board-level component overheating warning

(Detected over heat of board-level component)

Cause:

  • Ambient temperature or cabinet temperature too high.

  • Obstruction in ventilation hole or heat sink.

  • Cooling fan not running.

  • Insufficient ventilation space.

  • Drive overloaded.




Remedy:

  • Check ambient temperature and inspect ventilation holes.

  • Remove obstructions or replace cooling fan.

  • Install/add cooling fan or air conditioner.

  • Increase ventilation space.

  • Decrease loading, decrease carrier frequency, or replace with a larger capacity drive.



PID



PID feedback error

(PID feedback loss; analog signal < 4 mA)

Cause:

  • Loose or broken PID feedback wiring.

  • Feedback device malfunction.

  • Hardware error.




Remedy:

  • Tighten the terminals again or replace with a new cable.

  • Replace with a new feedback device.

  • If error persists after checking wiring, return to factory for repair.



AnL



ACI analog signal loss

(Analog input current loss < 4 mA)

Cause:

  • Loose or broken ACI wiring.

  • External device error.

  • Hardware error.




Remedy:

  • Tighten the terminals again or replace with a new cable.

  • Replace new device.

  • If error persists after checking wiring, return to factory for repair.



uC



Under current

(Low current detection)

Cause:

  • Broken motor cable.

  • Improper setting for the low current protection (Pr.06-71, Pr.06-72, Pr.06-73).

  • Low load.




Remedy:

  • Exclude the connection issue of the motor and its load.

  • Set the proper settings for Pr.06-71, Pr.06-72, and Pr.06-73.

  • Check the loading status and ensure it matches motor capacity.


oSPD
Over speed warning

Cause:

  • Improper setting for Pr.10-25 (FOC bandwidth).

  • Improper bandwidth setting for ASR speed controller.

  • Incorrect motor parameter setting.

  • Malfunction caused by interference.




Remedy:

  • Decrease setting value for Pr.10-25.

  • Increase the bandwidth setting for ASR speed controller.

  • Reset motor parameter and run parameter tuning.

  • Verify wiring of the control circuit and grounding to prevent interference.


dAvE
Deviation Warning

Cause:

  • Improper parameter setting for the slip error.

  • Improper setting for ASR parameter and acceleration/deceleration.

  • Accel./Decel. time is too short.

  • Motor locked.

  • Mechanical brake is not released.

  • Incorrect parameter setting of torque limit (Pr.06-12, Pr.11-17~20).

  • Malfunction caused by interference.




Remedy:

  • Reset proper value for Pr.10-13 and Pr.10-14.

  • Reset ASR parameters and set proper Accel./Decel. time.

  • Remove the causes of motor lock.

  • Check the active timing of the system.

  • Adjust to proper torque limit setting value.

  • Verify wiring of the control/main circuit to prevent interference.


PHL
Phase loss (Input phase loss)

Cause:

  • Phase loss of the input power.

  • Single phase power input on a three-phase model.

  • The power voltage has changed.

  • Loose wiring terminal of input power.

  • Input cable of 3-phase power is broken.

  • Unbalance in three-phase input power.




Remedy:

  • Verify wiring of the main circuit.

  • Use a model with voltage that matches the power.

  • Check if the MC of the main circuit is broken. Cycle power. If PHL persists, return to factory.

  • Tighten the terminal screws.

  • Replace the broken part of the cable.

  • Check settings for Pr.06-50 and Pr.06-52.

  • Check the status of three-phase power.


ot1
Over-torque 1

Cause:

  • Incorrect parameter setting (Pr.06-07, Pr.06-08).

  • Mechanical error (e.g., lock due to over-torque).

  • The load is too large.

  • Accel./Decel. time and working cycle is too short.

  • V/F voltage is too high.

  • Motor capacity is too small.

  • Over-load during low-speed operation.

  • Torque compensation is too large.

  • Improper speed tracking settings.




Remedy:

  • Configure settings for Pr.06-07 and Pr.06-08 again.

  • Remove causes of malfunction/lock.

  • Decrease loading or replace with larger capacity motor.

  • Increase setting values for Pr.01-12~01-19.

  • Adjust V/F curve (Pr.01-01~01-08), especially mid-point voltage.

  • Adjust torque compensation (Pr.07-26).

  • Correct parameter settings for speed tracking (Pr.07-09).


ot2
Over-torque 2

Cause:

  • Incorrect parameter setting (Pr.06-10, Pr.06-11).

  • Mechanical error / Load too large.

  • Accel./Decel. time too short.

  • V/F voltage is too high.

  • Motor capacity too small.

  • Torque compensation too large.

  • Improper speed tracking settings.




Remedy:

  • Configure settings for Pr.06-10 and Pr.06-11 again.

  • Remove mechanical lock / Decrease loading.

  • Increase Accel./Decel. time (Pr.01-12~01-19).

  • Adjust V/F curve (Motor 2, Pr.01-35~01-42).

  • Replace with larger capacity motor.

  • Adjust torque compensation (Pr.07-26).

  • Correct speed tracking settings (Pr.07-09).


oH3 (PTC)
Motor over-heating

Cause:

  • Motor locked or load too large.

  • Ambient temperature is too high.

  • Motor cooling system/fan error.

  • Operates at low-speed too long.

  • V/F voltage too high.

  • Incorrect motor rated current setting.

  • PTC improper setting/wiring.

  • Harmonics too high.




Remedy:

  • Clear motor lock / Decrease loading.

  • Install cooling fan/AC or change installation place.

  • Replace fan or check cooling system.

  • Decrease low-speed operation time or use dedicated motor.

  • Adjust V/F curve settings.

  • Configure correct rated current value.

  • Check connection between PTC thermistor and heat protection.

  • Use remedies to reduce harmonics.


oH3 (PT100)
Motor over-heating

Cause:

  • Motor locked or load too large.

  • Ambient temperature is too high.

  • Motor cooling system error.

  • Operates at low-speed too long.

  • V/F voltage too high.

  • Incorrect motor rated current setting.

  • PT100 improper setting/wiring.




Remedy:

  • Clear motor lock / Decrease loading.

  • Improve ambient cooling.

  • Check cooling system / Replace fan.

  • Decrease low-speed operation time or upgrade motor.

  • Adjust V/F curve settings.

  • Configure correct rated current.

  • Check connection between PT100 thermistor and heat protection.


oSL
Over slip warning

Cause:

  • Incorrect motor parameter.

  • Load is too large.

  • Improper settings for Pr.07-29, Pr.07-30, and Pr.10-29.




Remedy:

  • Check the motor parameter.

  • Decrease the loading.

  • Check the parameter settings for oSL protection.


tUn
Auto tuning

Cause:

  • The motor parameter is running auto-tuning.




Remedy:

  • When the auto-tuning is finished, the warning automatically clears.


OPHL
Output phase loss

Cause:

  • Unbalanced three-phase impedance of the motor.

  • Wiring is incorrect or cable broken.

  • Motor is single-phase (Drive requires three-phase).

  • Current sensor broken or loose control board cable.

  • Capacity of drive is larger than motor.




Remedy:

  • Replace the motor.

  • Check and replace the cable.

  • Choose a three-phase motor.

  • Reconnect control board cable. Check 3-phase current balance. Return to factory if error persists.

  • Choose matched capacity for drive and motor.


SE3
Copy model error 3

Cause:

  • Keypad copy between different power range drives.




Remedy:

  • It is mainly to prevent parameter copies between different HP/models. Perform Manual Reset.


CGdn
CANopen guarding time-out

Cause:

  • The guarding time is too short, or less detection times.

  • Malfunction caused by interference.




Remedy:

  • Increase the guarding time (Index 100C) and detection times.

  • Verify wiring/grounding. Separate communication circuit from main circuit (90 degrees).

  • Ensure communication circuit is wired in series.

  • Use CANopen cable or add terminating resistance.


CHbn
CANopen heartbeat error

Cause:

  • The heartbeat time is too short.

  • Malfunction caused by interference.

  • Communication cable is broken or bad connection.




Remedy:

  • Increase heartbeat time (Index 1016).

  • Verify wiring/grounding and separation from main circuit.

  • Ensure series wiring and terminating resistance.

  • Check or replace the communication cable.


CbFn
CANopen bus off error

Cause:

  • CANopen card is not installed (Hardware).

  • Master received wrong package (Software).

  • Too much interference on BUS.

  • CAN_H and CAN_L shorted.

  • Communication cable broken/bad connection.




Remedy:

  • Make sure the CANopen card is installed.

  • Reset CANopen speed (Pr.09-37).

  • Verify wiring, grounding, and separation from main circuit.

  • Use terminating resistance.

  • Check or replace communication cable.


CIdn
CANopen index error

Cause:

  • Incorrect setting of CANopen index.




Remedy:

  • Reset CANopen Index (Pr.00-02 = 7).


CAdn
CANopen station address error

Cause:

  • Incorrect setting of CANopen station address (Only supports 1-127).




Remedy:

  • Disable CANopen (Pr.09-36 = 0).

  • Reset CANopen (Pr.00-02 = 7).

  • Reset CANopen station address (Pr.09-36).


CFrn
CANopen memory error

Cause:

  • CANopen internal memory error (often after firmware update).




Remedy:

  • Disable CANopen (Pr.09-36 = 0).

  • Reset CANopen (Pr.00-20 = 7).

  • Reset CANopen station address (Pr.09-36).


CSdn (ID 43)
CANopen SDO time-out

Cause:

  • Slave is not connected.

  • The synchronize cycle is set too short.

  • Malfunction caused by interference.

  • Disconnection or bad connection of the communication cable.




Remedy:

  • Connect slave and CANopen BUS.

  • Increase the synchronization time (Index 1006).

  • Verify wiring and grounding. Separate communication circuit from main circuit (or wire at 90 degrees). Ensure series wiring. Use CANopen cable or add terminating resistance.

  • Check the status of the cable, or replace the cable.


CSbn (ID 44)
CANopen SDO receives register overflow

Cause:

  • Too much SDO from the upper unit (causes buffer overflow).




Remedy:

  • Check if the master sends too much SDO command.

  • Make sure the master sends SDO command according to the command format.


CPtn (ID 46)
CANopen format error

Cause:

  • The upper unit sends incorrect communication packet (slave cannot recognize data).




Remedy:

  • Make sure the master sends the packet based on CANopen DS301 standard command format.


PLrA (ID 47)
RTC adjust

Cause:

  • RTC time different after drive powered off > 7 days.

  • KPC-CC01 disconnected for a long time.

  • KPC-CC01 does not adjust the RTC time.

  • PLC detects unreasonable RTC time.




Remedy:

  • Stop the PLC program and restart it.

  • Adjust the RTC time and cycle the power.

  • If necessary, replace with a new KPC-CC01.


PLiC (ID 48)
InnerCOM error

Cause:

  • Communication cable is loose.

  • Malfunction caused by interference.




Remedy:

  • Check the connection of the communication cable.

  • Verify wiring and grounding. Separate communication circuit from main circuit.

  • Install terminal resistor(s) on the first and last unit of the communication circuit.


PLrt (ID 49)
Keypad RTC time-out

Cause:

  • KPC-CC01 is not connected to the control board while using the RTC function.




Remedy:

  • Do not remove the KPC-CC01 keypad while using RTC function.


PLod (ID 50)
PLC opposite defect (Download error)

Cause:

  • Incorrect component number is found when downloading the PLC program.

  • Source code detects incorrect address (e.g. exceeds range).




Remedy:

  • Use the correct component number.

  • Check if the program is correct and re-download.


PLSv (ID 51)
PLC save memory error

Cause:

  • An incorrect written address is detected during PLC operation (e.g. address exceeds range).




Remedy:

  • Make sure the write-in address is correct and re-download the program.


PLdA (ID 52)
Data defect

Cause:

  • External Modbus has written/read incorrect data to internal PLC program.

  • Program detects incorrect write-in address when decoding/downloading.




Remedy:

  • Check if the upper unit transmits the correct command.

  • Check if the program is correct and re-download the program.


PLFn (ID 53)
Function defect

Cause:

  • Unsupported command has used while downloading the program.




Remedy:

  • Check if the firmware of the drive is the old version. If yes, contact Delta.

  • Check if the program is correct and re-download.


PLor (ID 54)
PLC buffer overflow

Cause:

  • The program detects source code error during PLC operation (command exceeds maximum capacity).




Remedy:

  • Disable PLC.

  • Delete PLC program (Pr.00-02 = 6).

  • Enable PLC.

  • Re-download PLC program.


PLFF (ID 55)
Function defect (Code error)

Cause:

  • The PLC runs an incorrect command during operation.

  • There is no program in the PLC (normal warning in this state).




Remedy:

  • Check if the program is correct and re-download the program.


PLSn (ID 56)
Checksum error

Cause:

  • The program detects checksum error during PLC operation (after power on).




Remedy:

  • Disable PLC.

  • Remove PLC program (Pr.00-02 = 6).

  • Enable PLC.

  • Re-download PLC program.


PLEd (ID 57)
No end command

Cause:

  • There is no "END" command during PLC operation.




Remedy:

  • Disable PLC.

  • Remove PLC program (Pr.00-02 = 6).

  • Enable PLC.

  • Re-download PLC program.


PLCr (ID 58)
PLC MCR error

Cause:

  • The MC command is continuously used for more than 9 times.

  • No corresponded MCR command detected.




Remedy:

  • The MC command cannot be used continuously for 9 times. Check and reset the program.

  • Re-download the program.


PLdF (ID 59)
PLC download fail

Cause:

  • PLC download is forced to stop, so the program write-in is incomplete.

  • Momentary power loss during downloading.




Remedy:

  • Check if there is any error in the program and re-download the PLC program.


PLSF (ID 60)
PLC scan time fail

Cause:

  • The PLC scan time exceeds the maximum allowable time (400ms).




Remedy:

  • Check if the source code is correct and re-download the program.


PCGd (ID 61)
CAN/M guarding error

Cause:

  • Slave is not connected or CANopen BUS cable is not connected.

  • Malfunction caused by interference.

  • Communication cable is broken or bad connected.




Remedy:

  • Connect the Slave and CANopen BUS.

  • Verify wiring/grounding of communication circuit (separate from main circuit/wire 90 deg).

  • Make sure communication circuit is wired in series.

  • Use CANopen cable or add terminating resistance.

  • Check or replace the communication cable.


PCbF (ID 62)
CAN/M BUS off

Cause:

  • Malfunction caused by interference (error packets > 255).

  • Communication cable is broken or bad connected.




Remedy:

  • Verify wiring/grounding of communication circuit.

  • Make sure communication circuit is wired in series.

  • Use CANopen cable or add terminating resistance.

  • Check or replace the communication cable.


PCnL (ID 63)
CAN/M node lack

Cause:

  • The configured node quantity is different from the actual nodes.

  • Communication cable is broken or bad connected.




Remedy:

  • Connect BUS to the original slave, or change the configured node numbers to meet the actual node quantity.

  • Check or replace the communication cable.


PCCt
CANopen Master cycle time-out

Cause:

When the transmitted packet from CANopen master exceeds the maximum allowable quantity in a certain time.



Remedy:

Increase the time setting of D1090 synchronization cycle.
PCSF
CANopen Master SDO overflow

Cause:

Internal PLC transmits too much SDO at once.



Remedy:

The PLC program needs to confirm receiving the SDO feedback data before sending another SDO command.
PCSd
CANopen Master SDO time-out

Cause:

When the CANopen master transmits a SDO command, and does not receive feedback from the Slave within 1 sec.



Remedy:

Check if the Slave responds within 1 second.
PCAd
CANopen Master station address error

Cause:

When the CANopen master detects an incorrect or repeated station address from the Slave.



Remedy:

Set the correct slave station address.
PCTo
CAN/M time-out

Cause:

Malfunction caused by interference OR The command from the upper unit does not meet the CANopen format.



Remedy:

  • Verify wiring/grounding of the communication circuit (separate from main circuit or wire 90 degrees).

  • Make sure the communication circuit is wired in series.

  • Use CANopen cable or add terminating resistance.

  • Contact Delta for further confirmation.


ECid
ExCom ID fail (Duplicate MAC ID error)

Cause:

  • The setting address exceeds the range (0–63).

  • The speed setting exceeds the range.

  • The address is duplicated with other nodes on the BUS.




Remedy:

  • Check the address setting of the communication card (Pr.09-70).

  • Standard: 0–2, non-standard: 0–7.

  • Reset the address.


ECLv
ExCom power loss (Low voltage of communication card)

Cause:

The 5V power that drive provides to communication card is too low OR The card is loose.



Remedy:

  • Switch the communication card to other CP2000 drives. If error persists, replace card; if not, replace drive.

  • Use another communication card to test. If error persists, replace drive; if not, replace card.

  • Make sure the communication card is well inserted.


ECtt
ExCom test mode

Cause:

Communication command error.



Remedy:

Cycle the power.
ECbF
ExCom Bus off

Cause:

Poor connection of the cable OR Bad quality of the cable.



Remedy:

Re-connect the cable OR Replace the cable.
ECnP
ExCom no power (No power on DeviceNet)

Cause:

The drive detects that DeviceNet has no power.



Remedy:

Check if the cable and power is normal. If yes, return to the factory for repair.
ECFF
ExCom factory defect

Cause:

Factory default setting error.



Remedy:

Use DCISoft to reset to the default value.
ECiF
ExCom inner error

Cause:

Noise interference OR The memory is broken.



Remedy:

  • Verify wiring of the control circuit and wiring/grounding of the main circuit.

  • Cycle the power.

  • Reset to the default value. If error exists, replace communication card.


ECio
ExCom IO Net break

Cause:

The cable is loose OR Incorrect parameter setting for master communication.



Remedy:

Re-install the cable OR Check the setting for master communication parameter.
ECPP
ExCom Parameter data error

Cause:

The GSD file is incorrect.



Remedy:

Get the correct GSD file from the software.
ECPi
ExCom configuration data error

Cause:

The GSD file is incorrect.



Remedy:

Get the correct GSD file from the software.
ECEF
Ethernet link fail

Cause:

Ethernet cable is loose OR Bad quality of Ethernet cable.



Remedy:

Re-connect the cable OR Replace the cable.
ECto
Communication time-out

Cause:

Communication card is not connected with the upper unit OR Communication error of the upper unit.



Remedy:

Check if the connection of the communication cable is correct OR Check if the communication of the upper unit is normal.
ECCS
Checksum error

Cause:

Noise interference.



Remedy:

Verify wiring of the control circuit, and wiring/grounding of the main circuit to prevent interference.
ECrF
Return defect

Cause:

Communication card is returning to default setting.



Remedy:

No actions.
Eco0
Modbus TCP over

Cause:

  • Master communication value > allowable quantity.

  • Upper unit is online without communicating/does not break off link.

  • New Modbus TCP connection built every time upper unit connects.




Remedy:

  • Reduce Master communication value.

  • Revise program of upper unit (break off communication when not used).

  • Revise program of upper unit (use same Modbus TCP connection).


ECo1
EtherNet/IP over

Cause:

  • Master communication value > allowable quantity.

  • Upper unit is online without communicating/does not break off link.

  • New Modbus TCP connection built every time upper unit connects.




Remedy:

  • Reduce Master communication value.

  • Revise program of upper unit (break off communication when not used).

  • Revise program of upper unit (use same Modbus TCP connection).


ECiP
IP fail (IP setting error)

Cause:

IP conflict OR DHCP IP configuration error.



Remedy:

Reset IP OR MIS check if DHCP Server works normally.
EC3F
Mail fail

Cause:

Communication card establishes alarm conditions.



Remedy:

No actions.
ECbY
ExCom busy

Cause:

Communication packets are too much for the communication card to process.



Remedy:

Reduce communication packets.
ECCb
ExCom card break

Cause:

Communication card break off.



Remedy:

Re-install communication card.
CPLP (90)

Copy PLC: password error

Cause: PLC password is incorrect (during PLC copy process).



Remedy:

  • Reset and enter correct PLC password.


CPL0 (91)

Copy PLC: Read mode error

Cause: When copy PLC read mode and the process is incorrect.



Remedy:

  • Cycle the power and copy PLC read mode again.


CPL1 (92)

Copy PLC: Write mode error

Cause: When copy PLC write mode and the process is incorrect.



Remedy:

  • Cycle the power and copy PLC read mode again.


CPLv (93)

Copy PLC: version error

Cause: Non-CP2000 PLC program is copied to CP2000.



Remedy:

  • Check if the copied PLC program is for CP2000.

  • Use the correct CP2000 PLC program.


CPLS (94)

Copy PLC: size error

Cause: The PLC copied to CP2000 exceeds the allowable capacity.



Remedy:

  • Check if the copied PLC program is for CP2000.

  • Use CP2000 PLC program with correct capacity.


CPLF (95)

Copy PLC: PLC function

Cause: PLC function is enabled when KPC-CC01 is running copy PLC.



Remedy:

  • Disable PLC function first, then run the PLC copy function again.


CPLt (96)

Copy PLC: time-out

Cause: KPC-CC01 is removed while copying PLC program.



Remedy:

  • The KPC-CC01 cannot be removed during the PLC copy process.


ictn (101)

InrCOM time-out

Cause:

  • Malfunction caused by interference.

  • Different communication conditions with the upper unit.

  • Communication cable break off or not connected well.




Remedy:

  • Verify wiring/grounding of communication circuit (separate from main circuit or wire 90 degrees).

  • Check if Pr.09-02 setting matches the upper unit.

  • Check cable status or replace the cable.


SpdR (105)

Estimated speed reverse

Cause:

  • The motor runs in reverse direction at start.

  • Difference between measured Rr and Rs value is too large.

  • Insufficient output torque is dragged to reverse direction by load.




Remedy:

  • Check if motor is held when started, or start motor with speed source.

  • Proceed with motor parameter auto-tuning again.

  • Increase current limit (Pr.06-12) to increase output torque.


dEb (123)

Deceleration energy backup

Cause: Instantaneous power off or low voltage and unstable/sudden heavy load causing voltage drop.



Remedy:

  • Check the power consumption.


ocA (1)

Over-current during acceleration

Cause:

  • Acceleration time is too short.

  • Short circuit at motor output (poor insulation/wiring).

  • Motor burnout or aging insulation.

  • Load is too large.

  • Impulsive change of load.

  • Torque compensation too large.




Remedy:

  • Increase acceleration time (or S-curve time).

  • Check motor cable and remove short circuits.

  • Check motor insulation with megger.

  • Replace drive with larger capacity model if load exceeds rating.

  • Check contactor timing at output (U/V/W).

  • Adjust V/F curve setting (reduce voltage if too high).

  • Adjust torque compensation (Pr.07-26).

  • Perform speed tracking if motor starts in free run.


ocd (2)

Over-current during deceleration

Cause:

  • Deceleration time too short.

  • Mechanical brake activates too early.

  • Short-circuit or ground fault at output.

  • Load too large or impulsive change.

  • Hardware error.




Remedy:

  • Increase deceleration time.

  • Check action timing of mechanical brake.

  • Check motor cable and insulation (megger).

  • Install AC reactor on output side if cable is too long.

  • Check for short circuits between terminals (U, V, W) and ground.


ocn (3)

Over-current during steady operation

Cause:

  • Short-circuit at motor output.

  • Motor shaft lock / burnout.

  • Impulsive load change.

  • Over-torque offset value too high.




Remedy:

  • Check motor cable and remove short circuits.

  • Troubleshoot motor shaft lock or insulation.

  • Check motor capacity vs drive rating.

  • Adjust Over-torque offset and Torque compensation (Pr.07-26).

  • Install AC reactor if motor cable is too long.


GFF (4)

Ground fault

Cause:

  • Motor burnout or aging insulation.

  • Short circuit due to broken cable.

  • Large stray capacitance (long cable).

  • Hardware failure.




Remedy:

  • Check motor insulation with megger.

  • Replace broken cables.

  • Decrease carrier frequency if cable length > 100m.

  • Return to factory if hardware failure persists after checking external factors.


occ (5)

IGBT short circuit

Cause: IGBT error or Short-circuit detecting circuit error.



Remedy:

  • Check motor wiring.

  • Cycle power; if error persists, return to factory.


ocS (6)

Over-current at stop

Cause: Over-current or hardware failure in current detection at stop.



Remedy:

  • Verify wiring/grounding to prevent interference.

  • Cycle power. If hardware failure (cd1, cd2, cd3) shows, return to factory.


ovA (7)

Over-voltage during acceleration

Cause:

  • Acceleration is too slow (regenerative energy).

  • Power voltage too high or surge from phase-in capacitor.

  • Regenerative voltage of motor inertia.

  • Motor ground fault.




Remedy:

  • Decrease acceleration time or use brake unit/DC bus.

  • Check input voltage range.

  • Install AC reactor if power system causes surges.

  • Use over-voltage stall prevention (Pr.06-01).

  • Check wiring of brake resistor/unit.


ovd (8)

Over-voltage during deceleration

Cause:

  • Deceleration time too short (large regenerative energy).

  • Stall prevention level too small.

  • Power voltage too high.

  • Motor ground fault.




Remedy:

  • Increase deceleration time.

  • Connect brake resistor, brake unit, or DC bus.

  • Use S-curve acceleration/deceleration.

  • Adjust braking level.

  • Install AC reactor for power surges.

  • Troubleshoot ground faults on motor cable/terminals.



ovn


Over-voltage at constant speed

Cause:




  • Impulsive change of the load.

  • The setting for stall prevention level is smaller than no-load current.

  • Regenerative voltage of motor inertia.

  • Power voltage is too high.

  • ON/OFF switch action of phase-in capacitor in the same power system.

  • Motor ground fault.

  • Incorrect wiring of brake resistor or brake unit.

  • Malfunction caused by interference.



Remedy:




  • Connect brake resistor, brake unit or DC bus to the drive; Reduce load; Replace with larger capacity model.

  • Ensure stall prevention level is larger than no-load current.

  • Use over-voltage stall prevention function (Pr.06-01) or a brake unit.

  • Check if input voltage is within rated range and check for voltage spikes.

  • Install an AC reactor if power supply surges occur.

  • Check for ground faults on motor cable, wiring box, and terminals.

  • Verify wiring of brake resistor/unit.

  • Verify control circuit wiring and grounding to prevent interference.



ovS


Over-voltage at stop

Cause:




  • Power voltage is too high.

  • ON/OFF switch action of phase-in capacitor in the same power system.

  • Incorrect wiring of brake resistor or brake unit.

  • Malfunction caused by interference.

  • Hardware failure in voltage detection.

  • Motor ground fault.



Remedy:




  • Check if input voltage is within rated range.

  • Install an AC reactor.

  • Check wiring of brake resistor/unit.

  • Verify wiring and grounding.

  • Check if error codes cd1–cd3 occur after cycling power; return to factory if yes.

  • Check for ground faults on motor cable and terminals.



LvA


Low-voltage during acceleration

Cause:




  • Power-off or poor power supply condition.

  • Power voltage changes.

  • Starting up a motor with large capacity.

  • The load is too large.

  • DC bus issues.

  • Missing short-circuit plate or DC reactor between terminals +1 and +2.



Remedy:




  • Improve power supply condition.

  • Adjust voltage to the power range of the drive.

  • Check power system and increase capacity of power equipment.

  • Reduce load, increase drive capacity, or increase acceleration time.

  • Install DC reactor(s).

  • Connect short circuit plate or DC reactor between terminal +1 and +2.



Lvd


Low-voltage during deceleration

Cause:




  • Power-off or poor power supply condition.

  • Power voltage changes.

  • Starting up a motor with large capacity.

  • Sudden load.



Remedy:




  • Improve power supply condition.

  • Adjust voltage to the power range of the drive.

  • Check power system and increase capacity of power equipment.

  • Reduce the load or increase the drive capacity.

  • Install DC reactor(s).



Lvn


Low-voltage at constant speed

Cause:




  • Power-off or poor power supply condition.

  • Power voltage changes.

  • Starting up a motor with large capacity.

  • Sudden load.



Remedy:




  • Improve power supply condition.

  • Adjust voltage to the power range of the drive.

  • Check power system and increase capacity of power equipment.

  • Reduce the load or increase the drive capacity.

  • Install DC reactor(s).



LvS


Low-voltage at stop

Cause:




  • Power-off or poor power supply condition.

  • Incorrect drive models (power spec mismatch).

  • Power voltage changes.

  • Starting up a motor with large capacity.



Remedy:




  • Improve power supply condition.

  • Check if the power specification matches the drive.

  • Adjust voltage to power range. Cycle power; if error exists, return to factory.

  • Check power system and increase capacity of power equipment.

  • Install DC reactor(s).



OrP


Phase loss protection (Input)

Cause:




  • Phase loss of input power.

  • Single phase power input to three-phase model.

  • Power voltage changes.

  • Loose wiring terminal of input power.

  • The input cable of three-phase power is cut off.

  • Input power voltage changes too much.

  • Unbalanced three-phase input power.



Remedy:




  • Correctly install the wiring of the main circuit power.

  • Choose the model whose power matches the voltage.

  • Verify main circuit; cycle power. Return to factory if error persists.

  • Tighten terminal screws according to torque manual.

  • Wire correctly and replace cut cables.

  • Verify settings for Pr.06-50 (Time for Input Phase Loss) and Pr.06-52.

  • Check the power three-phase status.



oH1


IGBT overheating

Cause:




  • Ambient temperature/cabinet temperature too high or obstruction in ventilation.

  • Obstruction on heat sink or fan not running.

  • Insufficient ventilation space.

  • Drive does not match the load.

  • Drive has run at >100% rated output for a long time.



Remedy:




  • Check ambient temp, inspect ventilation holes, remove heating objects, or install cooling fan/AC.

  • Remove obstruction or replace cooling fan.

  • Increase ventilation space of the drive.

  • Reduce load, reduce carrier frequency, or replace with larger capacity drive.

  • Replace the drive with a larger capacity model.



oH2


Board level component overheating

Cause:




  • Ambient temperature/cabinet temperature too high or obstruction in ventilation.

  • Obstruction on heat sink or fan not running.

  • Insufficient ventilation space.

  • Drive does not match the load.

  • Unstable power.

  • Load changes frequently.



Remedy:




  • Check ambient temp, inspect ventilation holes, remove heating objects, or install cooling fan/AC.

  • Remove obstruction or replace cooling fan.

  • Increase ventilation space of the drive.

  • Reduce load, reduce carrier frequency, or replace with larger capacity drive.

  • Install reactor(s).

  • Reduce load changes.



tH1o


IGBT temperature detection failure

Cause:




  • Hardware failure (NTC broken or wiring failure).



Remedy:




  • Wait for 10 minutes, then cycle power. Check if protection still exists. If yes, return to factory.



tH2o


Capacitor hardware error

Cause:




  • Hardware failure (NTC broken or wiring failure).



Remedy:




  • Wait for 10 minutes, then cycle power. Check if protection still exists. If yes, return to factory.



oL


Over load

Cause:




  • The load is too large.

  • Accel./Decel. time or working cycle too short.

  • V/F voltage is too high.

  • The capacity of the drive is too small.

  • Overload during low-speed operation.

  • Torque compensation is too large.

  • Incorrect stall prevention setting.

  • Output phase loss.

  • Improper parameter settings for speed tracking function.



Remedy:




  • Reduce the load.

  • Increase setting for Pr.01-12~01-19 (accel/decel time).

  • Adjust V/F curve settings (Pr.01-01~01-08); check mid-point voltage.

  • Replace the drive with a larger capacity model.

  • Reduce load at low speed, increase drive capacity, or decrease carrier frequency (Pr.00-17).

  • Adjust torque compensation (Pr.07-26) until current reduces.

  • Set stall prevention to proper value.

  • Check three-phase motor status and cables.

  • Correct speed tracking parameters and adjust maximum current (Pr.07-09).



EoL1


Electronic thermal relay 1 protection

Cause:




  • The load is too large.

  • Accel./Decel. time or working cycle too short.

  • V/F voltage is too high.

  • Overload during low-speed operation (General motor vs VFD motor).

  • Incorrect setting for motor type (Pr.06-13).

  • Incorrect value of electronic thermal relay or max motor frequency.

  • One drive connected to multiple motors.

  • Incorrect stall prevention setting.

  • Torque compensation is too large.

  • Motor fan error or unbalanced three-phase impedance.



Remedy:




  • Reduce the load.

  • Increase Accel/Decel time.

  • Adjust V/F curve settings.

  • Decrease low-speed operation time or replace with dedicated VFD motor/increase capacity.

  • Set Pr.06-13 correctly (0 for inverter motor, 1 for standard motor).

  • Reset to correct motor rated current and frequency.

  • Set Pr.06-13 = 2 (disable) and install external thermal relays on each motor.

  • Set stall prevention to proper value.

  • Adjust torque compensation gain.

  • Check/replace fan or replace motor.


EoL2

Electronic thermal relay 2 protection

Cause: The load is too large.


Remedy:
Reduce the load.


Cause: Accel./Decel. time or the working cycle are too short.


Remedy:
Increase the setting values for Pr.01-12–01-19 (accel./decel. time).


Cause: V/F voltage is too high.


Remedy:
Adjust the settings for Pr.01-01–01-08 (V/F curve), especially the setting value for the mid-point voltage. Refer to Pr.01-43.


Cause: Overload during low-speed operation.


Remedy:


  • Decrease low-speed operation time.

  • Replace the drive with a dedicated to VFD model.

  • Increase the motor capacity.




Cause: Incorrect setting for VFD dedicated motors (Pr.06-27).


Remedy:
Set Pr.06-27 = 1 (Electronic thermal relay selection motor 2 = standard motor with fan on shaft).


Cause: Incorrect value of electronic thermal relay.


Remedy:
Reset to the correct motor rated current.


Cause: The maximum motor frequency is set too low.


Remedy:
Reset to the correct motor rated frequency.


Cause: One drive to multiple motors.


Remedy:
Set Pr.06-27 = 2 (Disable) and install thermal relay on each motor.


Cause: Torque compensation is too large.


Remedy:
Adjust torque compensation (Pr.07-26) until current reduces and motor does not stall.


Cause: Motor fan error.


Remedy:
Check the status of the fan, or replace the fan.


Cause: Unbalanced three-phase impedance of the motor.


Remedy:
Replace the motor.
oH3 (PTC)

Motor overheating (PTC)

Cause: Motor shaft lock.


Remedy:
Remove the shaft lock.


Cause: The load is too large.


Remedy:
Reduce the load or increase motor capacity.


Cause: Ambient temperature is too high.


Remedy:
Change installation place, add cooling fan or air conditioner.


Cause: Motor cooling system error or Fan error.


Remedy:
Check cooling system or replace fan.


Cause: Operate at low-speed too long.


Remedy:
Decrease low-speed time, replace with VFD dedicated motor, or increase capacity.


Cause: V/F voltage is too high.


Remedy:
Adjust settings for Pr.01-01–01-08.


Cause: Motor rated current mismatch.


Remedy:
Reset to the correct motor rated current.


Cause: Check if the PTC is properly set and wired.


Remedy:
Check the connection between PTC thermistor and the heat protection.


Cause: Unbalanced three-phase impedance or High Harmonics.


Remedy:
Replace motor or use remedies to reduce harmonics.
oH3 (PT100)

Motor overheating (PT100)

Cause: PT100 input value > Pr.06-57 setting.


Remedy:


  • Check for motor shaft lock or overload.

  • Check ambient temperature.

  • Check cooling system and fan.

  • Check connection of PT100 thermistor.


ot1

Over torque 1

Cause: Incorrect parameter setting.


Remedy:
Reset Pr.06-07 and Pr.06-08.


Cause: Mechanical failure (e.g. over-torque, mechanical lock).


Remedy:
Remove the causes of malfunction.


Cause: The load is too large or Motor capacity too small.


Remedy:
Reduce load or replace with larger capacity motor.


Cause: Accel./Decel. time too short.


Remedy:
Increase setting values for Pr.01-12–Pr.01-19.


Cause: V/F voltage is too high.


Remedy:
Adjust settings for Pr.01-01–01-08.


Cause: Torque compensation is too large.


Remedy:
Adjust torque compensation (Pr.07-26).


Cause: Improper parameter settings for speed tracking function.


Remedy:
Correct settings for speed tracking (Start function, adjust Pr.07-09).
ot2

Over torque 2

Cause: Output current exceeds Pr.06-10 for time Pr.06-11.


Remedy:


  • Reset Pr.06-07 and Pr.06-08.

  • Check for mechanical failure/lock.

  • Reduce load or increase motor capacity.

  • Increase Accel./Decel. time.

  • Adjust V/F curve settings.

  • Adjust torque compensation.


uC

Under current

Cause: Motor cable disconnection.


Remedy:
Troubleshoot the connection between the motor and the load.


Cause: Improper setting of low-current protection.


Remedy:
Reset Pr.06-71, Pr.06-72 and Pr.06-73 to proper settings.


Cause: The load is too low.


Remedy:
Check the load status and if motor capacity matches the load.
LiT

Limit Error

Cause: The limit ON/OFF switch is on incorrect position.


Remedy:
Install the limit ON/OFF switch to correct position.


Cause: Deceleration time is too long (motor cannot stop at limited position).


Remedy:
Reduce deceleration time. Adjust brake level (Pr.07-01).


Cause: The motor cannot stop due to over-voltage stall prevention.


Remedy:
Reset the over-voltage stall prevention.


Cause: Malfunction caused by interference.


Remedy:
Verify wiring of the control circuit and wiring/grounding of the main circuit.
cF1

EEPROM write error

Cause: Internal EEPROM cannot be programmed.


Remedy:
Press “RESET” key or reset parameters to default. Cycle power. If error persists, return to factory for repair.
cF2

EEPROM read error

Cause: Internal EEPROM cannot be read.


Remedy:
Press “RESET” key or reset parameters to default. Cycle power. If error persists, return to factory for repair.
cd1

U-phase error

Cause: Hardware failure (U-phase current detection error).


Remedy:
Cycle the power. If cd1 still exists, return to the factory for repair.
cd2

V-phase error

Cause: Hardware failure (V-phase current detection error).


Remedy:
Cycle the power. If cd2 still exists, return to the factory for repair.
cd3

W-phase error

Cause: Hardware failure (W-phase current detection error).


Remedy:
Cycle the power. If cd3 still exists, return to the factory for repair.
Hd0

cc hardware failure

Cause: Hardware failure (current clamp protection error).


Remedy:
Cycle the power. If Hd0 still exists, return to the factory for repair.
Hd1

oc hardware error

Cause: Hardware failure (oc protection error).


Remedy:
Cycle the power. If Hd1 still exists, return to the factory for repair.
Hd2

ov hardware error

Cause: Hardware failure (ov protection error).


Remedy:
Cycle the power. If Hd2 still exists, return to the factory for repair.
Hd3

occ hardware error

Cause: Hardware failure (occ IGBT short-circuit detection).


Remedy:
Cycle the power. If Hd3 still exists, return to the factory for repair.
AUE

Auto-tuning error

Cause: Press “STOP” key during auto-tuning.


Remedy:
Re-execute auto-tuning.


Cause: Incorrect motor capacity or parameters.


Remedy:
Check motor capacity. Set correct parameters (Pr.01-01–Pr.01-02). Set Pr.01-00 larger than motor rated frequency.


Cause: Incorrect motor wiring.


Remedy:
Check the wiring.


Cause: Motor shaft lock.


Remedy:
Remove the cause of motor shaft lock.


Cause: Electromagnetic contactor is ON at output side.


Remedy:
Make sure the electromagnetic valve is OFF.


Cause: The load is too large.


Remedy:
Reduce the load or replace with larger capacity motor.
AFE

PID loss ACI

Cause: PID feedback cable is loose or cut off.


Remedy:
Tighten the terminal or replace the cable.


Cause: Feedback device failure.


Remedy:
Replace the device with a new one.


Cause: Hardware failure.


Remedy:
Check all wiring. If AFE fault still exists, return to factory for repair.
42 (PGF1)

PG feedback error

Cause:



  • Incorrect parameter setting of encoder.

  • Check wiring of the encoder.

  • PG card or PG encoder failure.

  • Malfunction caused by interference.




Remedy:



  • Reset encoder parameter (Pr.10-02).

  • Re-wire the encoder.

  • Replace PG card or encoder with a new one.

  • Verify wiring of the control circuit and wiring/grounding of the main circuit to prevent interference.


43 (PGF2)

PG feedback loss

Cause:



  • Incorrect setting of encoder parameter.

  • Incorrect selection of the control mode.




Remedy:



  • Reset encoder parameters (Pr.10-00 and Pr.10-02).

  • Choose the correct control mode.


44 (PGF3)

PG feedback stall

Cause:



  • Incorrect setting of encoder parameter.

  • Pr. 01-00 is set too small.

  • Incorrect setting for ASR parameters and accel./decel. time.

  • Incorrect setting for PG feedback stall.




Remedy:



  • Reset encoder parameter (Pr.10-01).

  • Set proper value for Pr.01-00.

  • Reset ASR parameters. Set correct accel./decel. time.

  • Reset proper values for Pr.10-10 and Pr.10-11.


45 (PGF4)

PG slip error

Cause:



  • Incorrect settings for PG feedback parameters.

  • Incorrect settings for ASR parameters and accel./decel. time.

  • Incorrect settings of encoder parameters.

  • Accel./Decel. time is too short.

  • Incorrect settings of torque limit parameters (Pr.06-12, Pr.11-17–20).

  • Motor shaft lock.

  • Mechanical brake is not released.




Remedy:



  • Reset correct values for Pr.10-13 and Pr.10-14.

  • Reset ASR parameters. Set correct accel./decel time.

  • Reset encoder parameters (Pr.10-01).

  • Reset proper accel./decel. time.

  • Reset proper setting values for Pr.06-12 and Pr.11-17–Pr. 17-20.

  • Remove causes of motor shaft lock.

  • Check the action sequence of the system.


48 (ACE)

ACI loss (Analog Input Loss)

Cause:



  • ACI cable is loose or cut off.

  • External device failure.

  • Hardware failure.




Remedy:



  • Tighten the terminal. Replace the cable with a new one.

  • Replace the device with a new one.

  • Check all the wiring. If ACE still exists, return to the factory for repair.


49 (EF)

External fault

Cause:



  • External fault (MIx = EF triggered).




Remedy:



  • Press RESET key after the fault is cleared.


50 (EF1)

Emergency stop

Cause:



  • When MIx = EF1 activates.




Remedy:



  • Verify if the system is back to normal condition, and then press "RESET" key to go back to the default.


51 (bb)

External base block

Cause:



  • When MIx = bb activates.




Remedy:



  • Verify if the system is back to normal condition, and then press "RESET" key to go back to the default.


52 (Pcod)

Password is locked

Cause:



  • Incorrect password input through Pr.00-07.




Remedy:



  • Input the correct password after rebooting the motor drive.

  • If you forget the password:

    • Step 1: Input 9999 and press ENTER.

    • Step 2: Repeat step 1. Input 9999 and press ENTER. (Finish within 10 seconds).



  • Parameter settings return to default when the "Input 9999" process is finished.


54 (CE1)

Illegal command

Cause:



  • Incorrect communication command from the upper unit.

  • Malfunction caused by interference.

  • Different communication setting from the upper unit.

  • Disconnection or bad connection of the cable.




Remedy:



  • Check if the communication command is correct.

  • Verify wiring/grounding. Use twisted pair/shielded cable or wire in 90 degrees.

  • Check if the setting for Pr.09-02 is the same as the setting for the upper unit.

  • Check the cable and replace it if necessary.


55 (CE2)

Illegal data address

Cause:



  • Incorrect communication command from the upper unit.

  • Malfunction caused by interference.

  • Different communication setting from the upper unit.

  • Disconnection or bad connection of the cable.




Remedy:



  • Check if the communication command is correct.

  • Verify wiring/grounding.

  • Check if the setting for Pr.09-02 is the same as the setting for the upper unit.

  • Check the cable and replace it if necessary.


56 (CE3)

Illegal data value

Cause:



  • Incorrect communication command from the upper unit.

  • Malfunction caused by interference.

  • Different communication setting from the upper unit.

  • Disconnection or bad connection of the cable.




Remedy:



  • Check if the communication command is correct.

  • Verify wiring/grounding.

  • Check if the setting for Pr.09-02 is the same as the setting for the upper unit.

  • Check the cable and replace it if necessary.


57 (CE4)

Data is written to read-only address

Cause:



  • Incorrect communication command from the upper unit.

  • Malfunction caused by interference.

  • Different communication setting from the upper unit.

  • Disconnection or bad connection of the cable.




Remedy:



  • Check if the communication command is correct.

  • Verify wiring/grounding.

  • Check if the setting for Pr.09-02 is the same as the setting for the upper unit.

  • Check the cable and replace it if necessary.


58 (CE10)

Modbus transmission time-out

Cause:



  • The upper unit does not transmit the communication command within Pr.09-03 setting time.

  • Malfunction caused by interference.

  • Different communication setting from the upper unit.

  • Disconnection or bad connection of the cable.




Remedy:



  • Check if the upper unit transmits the communication command within the setting time for Pr.09-03.

  • Verify wiring/grounding.

  • Check if the setting for Pr.09-02 is the same as the setting for the upper unit.

  • Check the cable and replace it if necessary.


60 (bF)

Brake transistor error

Cause:



  • Hardware error.

  • Malfunction caused by interference.

  • Using the incorrect brake resistor.

  • Incorrect wiring of the brake resistor.




Remedy:



  • Press "RESET". If bF still exists, return to factory.

  • Power off and check if B2 to DC- is short-circuited. If yes, return to factory.

  • Verify wiring/grounding to prevent interference.

  • Check if the resistance value matches the drive.

  • Verify the wiring (Refer to optional accessories instruction).


61 (ydc)

Y-connection / Δ-connection switch error

Cause:



  • The electromagnetic valve operates incorrectly during Y-Δ switch.

  • Incorrect parameter setting.

  • The wiring of Y-Δ switch function is incorrect.




Remedy:



  • Check if the electromagnetic valve works normally. If not, replace it.

  • Check if related parameters are all set up and set correctly.

  • Check the wiring.


62 (dEb)

Deceleration energy backup error

Cause:



  • Unstable power source or the power is off.

  • There is any other large load operates in the power system.




Remedy:



  • Check the power system.

  • Replace power system with a larger capacity.

  • Use a different power system from the large load system.


63 (oSL)

Over slip error

Cause:



  • Any of the motor parameters in parameter group 5 may be incorrect.

  • Overload.

  • Any of the setting value of Pr.07-29, 07-30, and 10-29 is improper.




Remedy:



  • Check the motor parameters.

  • Decrease the load.

  • Check the setting of oSL protection function related parameters.


64 (ryF)

Electric valve switch error

Cause:



  • The input power is abnormal.

  • Malfunction caused by interference.

  • Hardware failure.




Remedy:



  • Check if the power is shut down during the drive operation. Check if three-phase input is normal.

  • Verify the wiring/grounding of the main circuit.

  • Cycle the power after checking the power. If ryF error still exists, return to the factory for repair.


65 (PGF5)

PG hardware error

Cause:



  • Wiring Error or No U,V, W Input Signal.

  • Encoder error.

  • Incorrect setting of encoder parameter.

  • Verify if the motor selecting switch on the PG card is on the right side.

  • Wrong PG card.




Remedy:



  • Re-wire correctly.

  • Verify if it is a UVW signal encoder.

  • Reset correct values for Pr.10-00.

  • Verify if using a UVW signal encoder or a Delta wire-saving encoder.

  • Verify if using a wrong PG card then choose a right one.


SdRv (ID 68)
Reverse direction of the speed feedback

Cause:

  • The setting of Pr.10-25 FOC bandwidth of speed observer is improper.

  • The setting of motor parameter is incorrect.

  • The motor cable is abnormal or broken.

  • A reverse force is exerted, or the motor runs in a reverse direction at start.

  • Malfunction caused by interference.




Remedy:

  • Decrease the setting of Pr.10-25.

  • Reset the motor parameter and execute parameter tuning.

  • Check if the cable is well functioned or replace the cable.

  • Start speed tracking function (Pr.07-12).

  • Verify the wiring of the control circuit and wiring/grounding of the main circuit to prevent interference.


SdOr (ID 69)
Over speed rotation feedback

Cause:

  • The setting of Pr.10-25 FOC bandwidth of speed observer is improper.

  • The setting of ASR bandwidth of speed controller is improper.

  • The setting of motor parameter is incorrect.

  • Malfunction caused by interference.




Remedy:

  • Decrease the setting of Pr.10-25.

  • Increase the bandwidth of ASR speed controller.

  • Reset motor parameter and execute parameter tuning.

  • Verify the wiring of the control circuit and wiring/grounding of the main circuit to prevent interference.


SdDe (ID 70)
Large deviation of speed feedback

Cause:

  • Improper parameter setting for abnormal rotating slip function.

  • Improper parameter setting for ASR and acceleration/deceleration.

  • The acceleration/deceleration time is too short.

  • Motor shaft lock.

  • The mechanical brake is not released.

  • Incorrect parameter setting for torque limit (Pr.06-12, Pr.11-17~20).

  • Malfunction caused by interference.




Remedy:

  • Reset proper setting for Pr.10-13 and Pr.10-14.

  • Reset ASR parameters. Set proper acceleration/deceleration time.

  • Reset proper acceleration/deceleration time.

  • Remove the cause of motor shaft lock.

  • Verify the system action timeline.

  • Adjust the setting to proper value.

  • Verify the wiring of the control circuit and wiring/grounding of the main circuit to prevent interference.


WDTT (ID 71)
Watchdog error

Cause: Hardware interference.



Remedy:

  • Verify the wiring of the control circuit and wiring/grounding of the main circuit to prevent interference.

  • If the WDTT fault still exists, return to the factory for repair.


STL1 (ID 72)
STO Loss 1 (STO1–SCM1 internal loop detection error)

Cause:

  • STO1 and SCM1 short circuit lines are not connected.

  • Hardware failure.

  • Bad connection of the IO card.

  • The IO card does not match the version of the control board.




Remedy:

  • Connect the short circuit line.

  • After you make sure all the wiring is correct, if STOL fault still exists after cycling the power, please return to the factory for repair.

  • Check if the PIN of IO card is broken. Check if the IO card connects to the control board correctly, and if the screws are tightened well.

  • Contact local agent or Delta.


S1 (ID 73)
Emergency stop for external safety

Cause:

  • The switch action of S1 and SCM (OPEN).

  • S1 and SCM short circuit lines are not connected.

  • Malfunction caused by interference.

  • Hardware failure.

  • Poor connection of the IO card.

  • The IO card does not match the version of the control board.




Remedy:

  • Reset the switch and cycle the power.

  • Re-connect the short circuit lines.

  • Verify the wiring/grounding of the main circuit, control circuit and encoder to prevent interference.

  • If S1 fault still exists after cycling the power, please return to the factory for repair.

  • Check if the PIN of IO card is broken or loose. Tighten screws.

  • Contact local agent or Delta.


Brk (ID 75)
External brake error

Cause:

  • Mechanical brake error.

  • Incorrect parameter setting (If there is no brake-confirming signal).

  • Signal cable is loose or cut off.

  • The time of Pr.02-56 is set too short.

  • Malfunction caused by interference.




Remedy:

  • Verify if the mechanical brake can work correctly. Replace mechanical brake.

  • Set Pr.02-56 = 0.

  • Tighten the screws or replace the signal cable with a new one.

  • Increase the time setting of Pr.02-56.

  • Verify the wiring/grounding of the main circuit, control circuit and encoder to prevent interference.


STO (ID 76)
Safety Torque Off function active

Cause:

  • The switch action of STO1/SCM1 and STO2/SCM2 (OPEN).

  • Poor connection of the IO card.

  • The IO card does not match the version of the control board.




Remedy:

  • Reset the switch (ON) and cycle the power.

  • Check if the PIN of IO card is broken. Check connection and screws.

  • Contact local agent or Delta.


STL2 (ID 77)
STO Loss 2 (STO2–SCM2 internal loop detection error)

Cause:

  • STO2 and SCM2 short circuit lines are not connected.

  • Hardware failure.

  • Poor connection of the IO card.

  • The IO card does not match the version of the control board.




Remedy:

  • Connect the short circuit lines.

  • If STL2 fault still exists after cycling the power, return to the factory for repair.

  • Check PINs and screws of IO card.

  • Contact local agent or Delta.


STL3 (ID 78)
STO Loss 3 (STO1–SCM1 and STO2–SCM2 internal loop error)

Cause:

  • STO1 and SCM1, or STO2 and SCM2 short circuit lines are not connected.

  • Hardware failure.

  • Poor connection of the IO card.

  • The IO card does not match the version of the control board.




Remedy:

  • Re-connect the short circuit lines.

  • If STL3 fault still exists after cycling the power, return to the factory for repair.

  • Check PINs and screws of IO card.

  • Contact local agent or Delta.


OPHL (ID 82)
Output phase loss U phase

Cause:

  • The three-phase impedance of motor is unbalanced.

  • The motor is wired incorrectly.

  • Using a single-phase motor.

  • The current sensor is damaged.

  • The drive capacity is much larger than the motor capacity.




Remedy:

  • Replace the motor.

  • Check the cable condition. Replace the cable.

  • Choose a three-phase motor.

  • Check the flat cable of the control board. If fault exists, return to factory. Verify three-phase current balance.

  • Make sure the capacity of the drive and motor match to each other.


OPHL (ID 83)
Output phase loss V phase

Cause:

  • Unbalanced three-phase impedance of the motor.

  • Check if the wiring is incorrect.

  • Check if the motor is a single-phase motor.

  • Check if the current sensor is broken.

  • Check if the drive capacity is larger than the motor capacity.




Remedy:

  • Replace the motor.

  • Check the cable and replace it if necessary.

  • Choose a three-phase motor.

  • Check control board cable. Return to factory if fault persists.

  • Choose the drive that matches the motor capacity.


OPHL (ID 84)
Output phase loss W phase

Cause:

  • Unbalanced three-phase impedance of the motor.

  • Check if the wiring is incorrect.

  • Check if the motor is a single-phase motor.

  • Check if the current sensor is broken.

  • Check if the drive capacity is larger than the motor capacity.




Remedy:

  • Replace the motor.

  • Check the cable and replace it if necessary.

  • Choose a three-phase motor.

  • Check control board cable. Return to factory if fault persists.

  • Choose the drive that matches the motor capacity.


AboF (ID 85)
PG ABZ loss protection

Cause:

  • PG card signal cable is not wired or is broken.

  • PG card screws are loose.

  • Malfunction caused by interference.

  • Hardware failure (PG card VP power issue or Encoder broken).

  • Cable between encoder and PG card is too long (VP voltage drop).




Remedy:

  • Re-wire the PG card.

  • Tighten all PG card screws.

  • Verify wiring/grounding to prevent interference.

  • Cycle power. If fault persists, return to factory.

  • Reduce cable length or use external power source for encoder.


UvoF (ID 86)
PG UVW loss protection

Cause:

  • PG card signal cable is not wired or is broken.

  • PG card screws are loose.

  • Malfunction caused by interference.

  • Hardware failure.

  • Cable between encoder and PG card is too long.




Remedy:

  • Re-wire the PG card.

  • Tighten all PG card screws.

  • Verify wiring/grounding to prevent interference.

  • Cycle power. If fault persists, return to factory.

  • Reduce cable length or supply power from another source.


oL3

Overload protection at low frequency
(Low frequency and high current protection)

Cause: The drive operates at a frequency below 15 Hz, and output current is too large.



Remedy:

  • Enhance the heat dissipation capacity for the cabinet.

  • Lower the carrier frequency (Pr.00-17).

  • Decrease the voltage settings that correspond to frequency below 15 Hz in the V/F curve.

  • Change Pr.00-11 to general control mode.

  • Replace the drive with a larger power model.


RoPd

Rotor position detection error
(Rotor position detection error protection)

Cause:

  • Motor cable abnormal or broken.

  • Motor coil error.

  • Hardware failure.

  • Drive’s current feedback line error.




Remedy:

  • Check or replace the cable.

  • Replace the motor.

  • IGBT broken. Return to the factory for repair.

  • Cycle the power. If RoPd still occurs during operation, return to the factory for repair.


FStp

Force to stop
(Keypad forces PLC to Stop)

Cause:

  • Pr.00-32 = 1: keypad STOP button is valid.

  • Press STOP button during PLC operation.




Remedy:

  • Check if it is necessary to set Pr.00-32 = 0, so the keypad STOP button is invalid.

  • Verify the timing of STOP function.


TRAP

CPU error 0
(CPU crash)

Cause:

  • Hardware interference.

  • Hardware failure.

  • CPU is in an infinite loop.




Remedy:

  • Verify the wiring of control circuit, and the wiring/grounding of the main circuit to prevent interference.

  • If TRAP fault still exists, return to the factory for repair.

  • Cycle the power. If the TRAP fault still exists, return to the factory for repair.


CGdE

CANopen guarding error

Cause:

  • The guarding time is too short, or less detection times.

  • Malfunction caused by interference.

  • Communication cable is broken or bad connected.




Remedy:

  • Increase the guarding time (Index 100C) and detection times.

  • Verify the wiring and grounding of the communication circuit. (Recommended to separate from main circuit or wire in 90 degrees).

  • Make sure the communication circuit is wired in series.

  • Use CANopen cable or add terminating resistance.

  • Check or replace the communication cable.


CHbE

CANopen heartbeat error

Cause:

  • The heartbeat time is too short.

  • Malfunction caused by interference.

  • Communication cable is broken or bad connected.




Remedy:

  • Increase heartbeat time (Index 100C).

  • Verify the wiring and grounding of the communication circuit.

  • Make sure the communication circuit is wired in series.

  • Use CANopen cable or add terminating resistance.

  • Check or replace the communication cable.


CbFE

CANopen bus off error

Cause:

  • CANopen card not installed.

  • Check if the CANopen speed is correct.

  • Malfunction caused by interference.

  • Communication cable is broken or bad connected.




Remedy:

  • Make sure the CANopen card is installed.

  • Reset CANopen speed (Pr.09-37).

  • Verify wiring/grounding of communication circuit.

  • Use CANopen cable or add terminating resistance.

  • Check or replace the communication cable.


CIdE

CANopen index error

Cause: Incorrect setting of CANopen index.



Remedy: Reset CANopen Index (Pr.00-02 = 7).
CAdE

CANopen station address error
(only supports 1–127)

Cause: Incorrect setting of CANopen station address.



Remedy:

  • Disable CANopen (Pr.09-36 = 0).

  • Reset CANopen (Pr.00-02 = 7).

  • Reset CANopen station address (Pr.09-36).


CFrE

CANopen memory error

Cause: CANopen internal memory error (Data change during firmware update).



Remedy:

  • Disable CANopen (Pr.09-36 = 0).

  • Reset CANopen (Pr.00-02 = 7).

  • Reset CANopen station address (Pr.09-36).


ictE

InrCOM time-out error
(Internal communication time-out)

Cause:

  • Malfunction caused by interference.

  • The communication condition is different with the upper unit.

  • Communication cable is broken or bad connected.




Remedy:

  • Verify wiring and grounding of communication circuit (separate from main circuit).

  • Verify the setting of Pr.09-02 is the same as the setting of upper unit.

  • Check or replace the communication cable.


SfLK

PMLess shaft lock
(Drive has RUN command but PM motor does not turn)

Cause:

  • Improper setting of the speed observer bandwidth.

  • Motor shaft lock.

  • Motor error (e.g. demagnetization).




Remedy:

  • Increase the setting value.

  • Remove causes of the motor shaft lock.

  • Replace the motor with a new one.


AUE1

Auto-tune error 1
(No feedback current error)

Cause:

  • Motor is not wired.

  • The electromagnetic contactor is used as an open state on the output side (U/V/W).




Remedy:

  • Wire the motor correctly.

  • Verify that the electromagnetic valve is closed.


AUE2

Auto-tune error 2
(Motor phase loss error)

Cause:

  • Incorrect motor wiring or wire error.

  • Motor error.

  • The electromagnetic contactor is open on the output side (U/V/W).




Remedy:

  • Wire the motor correctly.

  • Check if the motor works normally.

  • Verify that the three-phases of the electromagnetic valve are all closed.

  • Check if the wires are broken.


AUE3

Auto-tune error 3
(No load current I0 measurement error)

Cause:

  • Incorrect settings for the motor parameter (rated current).

  • Motor error.




Remedy:

  • Check the settings for Pr.05-01 / Pr.05-13 / Pr.05-34.

  • Check if the motor works normally.


AUE4

Auto-tune error 4
(Leakage inductance Lsigma measurement error)

Cause:

  • Motor error.

  • Incorrect setting of motor parameters (base frequency).




Remedy:

  • Check if the motor works normally.

  • Check the setting of Pr.01-01.


CBM

C/B mismatch
(Control board matching error)

Cause: Incorrect control board.



Remedy: Replace with the correct control board. If the CBM still exists, contact Delta for further confirmation.

How to Clear & Reset Delta CP2000 Drive Faults

  1. Keypad Reset: Once the abnormal root cause is removed, press the red RESET / STOP key on the KPC-CC01 digital keypad to clear the fault status.
  2. Multi-Function Input Terminal Reset (MI): If configured on terminals MI1 through MI8 (Parameter Group 02-01 to 02-08 set to 05: External Fault Reset), pulse the corresponding digital input to reset.
  3. Parameter Restoration (Factory Reset): Go to parameter 00-02 (Parameter Reset) and set it to 9 (for 50Hz factory default reset) or 10 (for 60Hz factory default reset) if you need to restore parameter logic.
  4. Serial Communication Reset: Send a reset bit via RS-485 Modbus RTU or BACnet network communication by toggling the reset command bit in the control register.
  5. Full Power Cycle: Shut off input AC mains power, verify that the keypad and internal CHARGE LED indicators have turned completely off (approx. 5 minutes for capacitor discharge), and restore mains power.
⚠️ High-Voltage Electrical Safety Warning: Hazardous residual voltages exist in internal DC bus capacitors even after mains power is disconnected. Always wait until the red CHARGE LED turns completely OFF and verify with a calibrated voltmeter that the voltage across DC bus terminals [+1/DC+] and [DC-] is less than 25VDC before touching terminals, power chokes, or motor wiring (U/T1, V/T2, W/T3).