Emotron FDU Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Emotron FDU dedicated pump and fan drive series. Search or filter through the complete diagnostic directory below.
Power Range
0.55 – 3,000 kW (0.75 – 4,000 HP)
Supply Voltage
230 – 690V AC (3-Phase)
Control Modes
V/Hz, Direct Torque Control (DTC)
Operator Interface
Detachable Multi-Language Control Panel
Complete Emotron FDU Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type Overcurrent, Overvoltage, Desat, or Motor Temp).
| Trip Condition | Cause and Remedy |
|---|---|
| Motor I2t “I2t” | Cause: I2t value is exceeded.
Remedy:
|
| PTC Motor thermistor (PTC) | Cause: Motor thermistor (PTC) exceeds maximum level. Note: Only valid if option board PTC/PT100 is used. Remedy:
|
| Motor PTC Motor thermistor (PTC) | Cause: Motor thermistor (PTC) exceeds maximum level. Note: Only valid if [337] is enabled. Remedy:
Applicable Sizes: 002 - 105 |
| PT100 Motor PT100 elements | Cause: Motor PT100 elements exceeds maximum level. Note: Only valid if option board PTC/PT100 is used. Remedy:
|
| Motor lost Phase loss or imbalance | Cause: Phase loss or too great imbalance on the motor phases. Remedy:
|
| Locked rotor Rotor blocking | Cause: Torque limit at motor standstill:
Remedy:
|
| Ext trip 1 External input (DigIn 1-8) | Cause: External input (DigIn 1-8) active:
Note: Exact trip message is dependent on [431] ExtTrip1 Text. Remedy:
|
| Ext trip 2 External input (DigIn 1-8) | Cause: External input (DigIn 1-8) active:
Note: Exact trip message is dependent on [432] ExtTrip2 Text. Remedy:
|
| Ext trip 3 External input (DigIn 1-8) | Cause: External input (DigIn 1-8) active:
Note: Exact trip message is dependent on [433] ExtTrip3 Text. Remedy:
|
| Ext trip 4 External input (DigIn 1-8) | Cause: External input (DigIn 1-8) active:
Note: Exact trip message is dependent on [434] ExtTrip4 Text. Remedy:
|
| Ext Mot Temp External input (DigIn 1-8) | Cause: External input (DigIn 1-8) active:
Remedy:
|
| Internal error Internal alarm | Cause: Internal alarm. Remedy: Contact service. |
| Mon MaxAlarm Max alarm level (overload) | Cause: Max alarm level (overload) has been reached. Remedy:
|
| Mon MinAlarm Min alarm level (underload) | Cause: Min alarm level (underload) has been reached. Remedy:
|
| Comm error Serial communication error | Cause: Error on serial communication (option). Remedy:
|
| Encoder Encoder loss/speed deviation | Cause: Lost encoder board, encoder cable or encoder pulses. Motor speed deviation in between reference and measured speed detected. Note: Only valid if option board Encoder is used. Remedy:
|
| Pump Master pump selection error | Cause: No master pump can be selected due to error in feedback signalling. Note: Only used in Pump Control. Remedy:
|
| Over temp Heatsink overtemperature | Cause: Heatsink temperature too high:
Remedy:
|
| Over curr F Motor peak current exceeded | Cause: Motor current exceeds the peak AC drive current:
Remedy:
|
| Over volt D(eceleration) Over volt G(eneration) High DC Link voltage | Cause: Too high DC Link voltage:
Remedy:
|
| Over volt (Mains) O(ver) volt M(ains) cut High supply voltage | Cause: Too high DC Link voltage, due to too high mains voltage. Remedy:
|
| Under voltage Low DC Link voltage | Cause: Too low DC Link voltage:
Remedy:
|
| LC Level Liquid cooling level low | Cause: Low liquid cooling level in external reservoir. External input (DigIn 1-8) active:
Note: Only valid for AC drive types with Liquid Cooling option. Remedy:
|
| OPTION Option specific trip | Cause: If an Option specific trip occurs. Remedy: Check the description of the specific option. |
| Desat / Desat U± / Desat V± / Desat W± / Desat BCC Output stage failure | Cause: Failure in output stage:
Remedy:
Applicable Sizes: 002 - 105 (Standard Desat), 090 & Up (Desat Phase / BCC trips) |
| DC link error Voltage ripple high | Cause: DC link voltage ripple exceeds maximum level. Remedy:
|
| Power Fault Undetermined Power Fault | Cause: One of the PF (Power Fault) trips below has occurred, but could not be determined. Remedy: Check the PF errors and try to determine the cause. The trip history can be helpful. |
| PF Fan Err * Fan module error | Cause: Error in fan module. Remedy: Check for clogged air inlet filters in panel door and blocking material in fan module. Applicable Sizes: 090 & Up |
| PF HCB Err * Controlled rectifier error | Cause: Error in controlled rectifier module (HCB). Remedy: Check mains supply voltage. Applicable Sizes: 060 & Up |
| PF Curr Err Current balance error | Cause: Error in current balancing:
Remedy:
Applicable Sizes: 430 & Up |
| PF Overvolt Power module overvoltage | Cause: Error in voltage balancing, overvoltage detected in one of the power modules (PEBB). Remedy:
Applicable Sizes: 430 & Up |
| PF Comm Err * Internal communication error | Cause: Internal communication error. Remedy: Contact service. |
| PF Int Temp * Internal temperature high | Cause: Internal temperature too high. Remedy: Check internal fans. |
| PF Temp Err * Temperature sensor malfunction | Cause: Malfunction in temperature sensor. Remedy: Contact service. |
| PF DC Err * DC-link / Mains supply fault | Cause: DC-link error and mains supply fault. Remedy:
Applicable Sizes: 060 & Up |
| PF Sup Err * Mains supply fault | Cause: Mains supply fault. Remedy:
|
| PF PBuC * Powerboard microcontroller reset | Cause: Powerboard micro controller reset by watchdog. Remedy: Not specified. |
| Brake Brake fault / engagement fail | Cause: Brake tripped on brake fault (not released) or Brake not engaged during stop. Remedy:
|
| AnIn Analogue input signal low | Cause: An analogue input signal is below 75% of the configured minimum value. Remedy:
|
How to Clear & Reset Emotron FDU Drive Faults
- Keypad Reset: Press the red RESET button on the front control panel display. If operating via remote control, ensure the drive is permitted to reset from the keypad via menu [21A] Keypad Reset.
- Digital Input Reset (DigIn): Trigger an external contact if configured in menu [520] Digital Inputs (e.g., assign parameter [261] Reset to an active digital input terminal such as DigIn 1 to DigIn 8).
- Serial Communication / Fieldbus: Send a reset pulse by setting Bit 3 (Fault Acknowledge/Reset) in the Fieldbus Control Word over Modbus RTU, Profibus, Profinet, or Ethernet/IP networks.
- Autoreset Function: If enabled in menu [250] Autoreset, the drive will automatically attempt a programmed number of reset cycles for specific faults (such as Overvoltage or Motor Thermal Overload) before latching a hard trip.
- Full Power Cycle: Switch off main 3-phase incoming AC power, wait at least 5 to 7 minutes until the control panel display goes completely dark and intermediate DC link capacitors discharge, then reapply power.
⚠️ High-Voltage Electrical Safety Warning:
Always wait a minimum of 5 to 7 minutes after disconnecting mains power. Verify with a calibrated digital DC voltmeter that the intermediate DC link bus voltage measures strictly below 50VDC across terminals [DC+] and [DC-] before opening terminal covers, checking output motor wiring, or servicing terminals U, V, and W on the Emotron FDU drive.