Emotron VS Series Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the CG Emotron VS series general purpose AC drives (VSX, VSM, VSS). Search or filter through the complete fault code directory below.
Power Range
0.4 – 22 kW (0.5 – 30 HP)
Supply Voltage
1-Ph 220V / 3-Ph 415V AC
Control Modes
V/F Control & Sensorless Vector (SVC)
Operator Interface
LED Keypad / Graphical LCD Panel
Complete Emotron VS Series Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type Err01, Err04, or Overcurrent).
| Fault Code | Description, Causes, and Solutions |
|---|---|
| Err01 | Err01 fault indicates Accel overcurrent. This means the inverter's output current has exceeded the safe threshold during the motor's acceleration phase. Possible Causes: 1: The output circuit is grounded or short circuited. 2: The acceleration time is too short. 3: Manual torque boost or V/F curve is not appropriate. 4: The voltage is too low. 5: The startup operation is performed on the rotating motor. 6: A sudden load is added during acceleration. 7: The AC drive model is of too small power class. Solutions: 1: Eliminate external faults. 2: Increase the acceleration time. 3: Adjust the manual torque boost or V/F curve. 4: Adjust the voltage to normal range. 5: Select rotational speed tracking restart or start the motor after it stops. 6: Remove the added load. 7: Select an AC drive of higher power class. |
| Err02 | Err02 fault indicates Decel overcurrent. This means the inverter's output current has exceeded the safe threshold during the motor's deceleration phase. Possible Causes: 1: The output circuit is grounded or short circuited. 2: The deceleration time is too short. 3: The voltage is too low. 4: A sudden load is added during deceleration. 5: The braking unit and braking resistor are not installed. Solutions: 1: Eliminate external faults. 2: Increase the deceleration time. 3: Adjust the voltage to normal range. 4: Remove the added load. 5: Install the braking unit and braking resistor. |
| Err03 | Err03 fault indicates Constant-speed overcurrent. This means the inverter's output current has exceeded the safe threshold while the motor was operating at a steady, constant speed. Possible Causes: 1: The output circuit is grounded or short circuited. 2: The voltage is too low. 3: A sudden load is added during operation. 4: The AC drive model is of too small power class. Solutions: 1: Eliminate external faults. 2: Adjust the voltage to normal range. 3: Remove the added load. 4: Select an AC drive of higher power class. |
| Err04 | Err04 fault indicates Accel overvoltage. This means the drive's internal DC bus voltage has risen above the maximum safe limit during motor acceleration. Possible Causes: 1: The input voltage is too high. 2: An external force drives the motor during acceleration. 3: The acceleration time is too short. 4: The braking unit and braking resistor are not installed. Solutions: 1: Adjust the voltage to normal range. 2: Cancel the external force or install a braking resistor. 3: Increase the acceleration time. 4: Install the braking unit and braking resistor. |
| Err05 | Err05 fault indicates Decel overvoltage. This means the drive's internal DC bus voltage has risen above the maximum safe limit during motor deceleration. Possible Causes: 1: The input voltage is too high. 2: An external force drives the motor during deceleration. 3: The deceleration time is too short. 4: The braking unit and braking resistor are not installed. Solutions: 1: Adjust the voltage to normal range. 2: Cancel the external force or install the braking resistor. 3: Increase the deceleration time. 4: Install the braking unit and braking resistor. |
| Err06 | Err06 fault indicates Constant-speed overvoltage. This means the inverter's internal DC bus voltage exceeded the safe limit while the motor was operating at a steady, constant speed. Possible Causes: 1: The input voltage is too high. 2: An external force drives the motor during deceleration. Solutions: 1: Adjust the voltage to normal range. 2: Cancel the external force or install the braking resistor. |
| Err07 | Err07 fault indicates Bus undervoltage. This means the DC bus voltage has dropped below the minimum threshold required for proper inverter operation. Possible Causes: 1: Instantaneous power failure occurs on the input power supply. 2: The AC drive's input voltage is not within the allowable range. 3: The bus voltage is abnormal. 4: The rectifier bridge and buffer resistor are faulty. 5: The drive board is faulty. 6: The main control board is faulty. Solutions: 1: Reset the fault. 2: Adjust the voltage to normal range. 3: Contact the agent or CG. |
| Err08 | Err08 fault indicates Short circuit. This means there is an abnormally high current flow due to a direct connection between phases or to ground, bypassing the normal load. Possible Causes: 1: The output circuit is grounded or short circuited. 2: The connecting cable of the motor is too long. 3: The module overheats. 4: The internal connections become loose. 5: The main control board is faulty. 6: The drive board is faulty. 7: The inverter module is faulty. Solutions: 1: Eliminate external faults. 2: Install a reactor or an output filter. 3: Check the air filter and the cooling fan. 4: Connect all cables properly. 5: Contact the agent or CG. |
| Err09 | Err09 fault indicates Power input phase loss. This means that one or more phases from the main AC power supply feeding the inverter are missing or disconnected. Possible Causes: 1: The three-phase power input is abnormal. 2: The drive board is faulty. 3: The lightening board is faulty. 4: The main control board is faulty. Solutions: 1: Eliminate external faults. 2: Contact the agent or CG. |
| Err10 | Err10 fault indicates Power output phase loss. This means there is a missing or disconnected phase in the power being delivered from the inverter to the motor. Possible Causes: 1: The cable connecting the AC drive and the motor is faulty. 2: The AC drive's three-phase outputs are unbalanced when the motor is running. 3: The drive board is faulty. 4: The module is faulty. Solutions: 1: Eliminate external faults. 2: Check whether the motor Three-phase winding is normal. 3: Contact the agent or CG. |
| Err11 | Err11 fault indicates Motor overload. This means the motor is drawing current exceeding its thermal or operational capacity for an extended period. Possible Causes: 1: E0-17 is set improperly. 2: The load is too heavy or locked-rotor occurs on the motor. 3: The AC drive model is of too small power class. Solutions: 1: Set E0-17 correctly. 2: Reduce the load and check the motor and the mechanical condition. 3: Select an AC drive of higher power class. |
| Err12 | Err12 fault indicates Inverter overload. This means the inverter is outputting a current beyond its rated capacity for a duration that exceeds its safe limits. Possible Causes: 1: The load is too heavy or locked-rotor occurs on the motor. 2: The AC drive model is of too small power class. Solutions: 1: Reduce the load and check the motor and mechanical condition. 2: Select an AC drive of higher power class. |
| Err13 | Err13 fault indicates External equipment fault. This means the drive has received a fault signal from external equipment via its digital inputs (DI). Possible Causes: 1: External fault signal is input via DI. Solutions: 1: Reset the operation. |
| Err14 | Err14 fault indicates Module overheat. This means the internal temperature of the inverter module has exceeded its safe operating limit. Possible Causes: 1: The ambient temperature is too high. 2: The air filter is blocked. 3: The fan is damaged. 4: The thermally sensitive resistor of the module is damaged. 5: The inverter module is damaged. Solutions: 1: Lower the ambient temperature. 2: Clean the air filter. 3: Replace the damaged fan. 4: Replace the damaged thermally sensitive resistor. 5: Replace the inverter module. |
| Err15 | Err15 fault indicates EEPROM read/write fault. This means there is a hardware failure or data corruption issue with the inverter's internal memory chip. Possible Causes: 1: The EEPROM chip is damaged. Solutions: 1: Replace the main control board. |
| Err16 | Err16 fault indicates Motor auto-tuning cancelled. This means the motor parameter identification process was manually interrupted by the user. Possible Causes: 1: Since the identification process, press STOP / RST key. Solutions: 1: Press STOP / RST key to reset. |
| Err17 | Err17 fault indicates Motor auto-tuning fault. This means the drive encountered an error while trying to automatically measure and identify the motor's parameters. Possible Causes: 1: The motor and the inverter output terminals are not connected. 2: The motor does not disengage the load. 3: The electrical fault. Solutions: 1: Check the connection between the inverter and motor. 2: The motor is disengaged load. 3: Check the motor. |
| Err18 | Err18 fault indicates Communication overtime error. This means the drive has lost communication with the connected PC or master device for a duration longer than the set timeout limit. Possible Causes: 1: The PC is not working properly. 2: The communication line is not normal. 3: H0 set communication parameters set incorrectly. Solutions: 1: Check the PC Connection. 2: Check the communication cable. 3: The communication parameters are set correctly. |
| Err19 | Err19 fault indicates PID feedback loss. This means the active feedback signal for the PID controller has dropped below the minimum allowable threshold. Possible Causes: 1: PID feedback set value is less than F0.24. Solutions: 1: Check the PID feedback signal or set to an appropriate value F0.24. |
| Err20 | Err20 fault indicates Continuous running time reached. This means the inverter has operated continuously for the duration specified by its running time limit parameter. Possible Causes: 1: Set the running time to reach this function. Solutions: 1: Refer C1.14 Description. |
| Err21 | Err21 fault indicates Parameter upload fault. This means an error occurred while trying to copy or upload parameters from the inverter to an external parameter copy card. Possible Causes: 1: Is not installed or is not plugged parameter copy card. 2: Parameter copy card abnormalities. 3: The control board abnormalities. Solutions: 1: A copy of the card is properly installed parameters. 2: Contact for technical support. |
| Err22 | Err22 fault indicates Parameter download fault. This means an error occurred while trying to copy or download parameters from the external copy card to the inverter. Possible Causes: 1: Is not installed or is not plugged parameter copy card. 2: Parameter copy card abnormalities. 3: The control board abnormalities. Solutions: 1: A copy of the card is properly installed parameters. 2: Contact for technical support. |
| Err23 | Err23 fault indicates Braking unit fault. This means there is an issue detected in the braking circuit, external resistor, or associated hardware. Possible Causes: 1: The brake line failure or damage the brake pipe. 2: An external braking resistor is too small. Solutions: 1: Check the brake unit, replace the brake pipe. 2: Increasing the braking resistor. |
| Err24 | Err24 fault indicates Module temperature detection disconnection. This means the drive has lost the signal from its internal temperature monitoring sensor, usually due to a physical break. Possible Causes: The temperature sensor failure or cable break. Solutions: Contact for technical support. |
| Err25 | Err25 fault indicates Load becoming 0. This means the current drawn by the motor has dropped below the threshold defined by parameter E0.22, indicating a possible loss of load (like a broken belt or dry pump). Possible Causes: The AC drive running current is lower than E0.22. Solutions: Check that the load is disconnected or the setting E0-22 and E0-23 is correct. |
| Err26 | Err26 fault indicates With-wave current limit fault. This means the drive's output current has hit the strict hardware current limit, often due to a severe overload or a stalled motor condition. Possible Causes: 1: The load is too heavy or locked rotor occurs on the motor. 2: The AC drive model is of too small power class. Solutions: 1: Reduce the load and check the motor and mechanical condition. 2: Select an AC drive of higher power class. |
| Err27 | Err27 fault indicates Inverter soft-start relay is off. This means the soft-start bypass relay inside the inverter failed to close properly, likely due to insufficient incoming power or a hardware failure. Possible Causes: 1: The grid voltage is too low. 2: Rectifier module failure. Solutions: 1: Check the grid voltage. 2: Demand for technical support. |
| Err28 | Err28 fault indicates Software version compatibility fault. This means there is a mismatch between the firmware versions of the main control board and the display/control panel. Possible Causes: 1: The upper and lower transmission module parameters in the parameter version of the control panel version mismatch. Solutions: re-upload module parameters to pass down. |
| Err29 | Err29 fault indicates Instantaneous overcurrent. This means there was a sudden, massive spike in output current exceeding the hardware protection limit, usually caused by a short circuit or extreme sudden load. Possible Causes: 1: Inverter output circuit being grounded or short-circuit; 2: The acceleration and deceleration time is too short; 3: Manually torque boost or V/F curve not appropriate; 4: Voltage too low; 5: Start the running motor; 6: Sudden-load in the acceleration process; 7: Model selection of inverter power is too small. Solutions: 1: Troubleshooting peripheral problems; 2: To increase the acceleration time; 3: Adjust the manually torque boost or V/F curve; 4: Adjust the voltage to normal range; 5: Select RPM track start or start after motor stopped; 6: Cancel sudden-load; 7: Select the inverter with higher rating. |
| Err30 | Err30 fault indicates Instantaneous overvoltage. This means a sudden, extreme spike in the internal DC bus voltage was detected, exceeding the maximum safe limit. Possible Causes: 1: Input voltage is too high; 2: There is external force drag the motor to run in deceleration process; 3: The deceleration time is too short; 4: No installation of braking resistor. Solutions: 1: Adjust the voltage to normal range; 2: Cancel external force or install brake resistor; 3: To increase the deceleration time; 4: Install braking resistor. |
| Err39 | Err39 fault indicates Motor temperature too high. This means the motor's internal temperature, as read by the connected PTC sensor, has exceeded the configured protection threshold. Possible Causes: 1: PTC sensor configuration not right. 2: Motor temperature protection value too small. 3: Motor temperature too high. Solutions: 1: Reset PTC sensor parameter. 2: Increase motor temperature protection value. 3: Wait until motor is cooled. |
| Err40 | Err40 fault indicates The set running time ends. This means the drive's internal timer has reached the maximum allowed continuous running time configured in the parameters. Possible Causes: 1: Running time more than A0.25. Solutions: 1: Contact the dealer. |
| Err41 | Err41 fault indicates Overload warning. This means the drive's output current has exceeded the pre-set overload warning threshold (E0.19) triggering a warning alert. Possible Causes: 1: when E0.18 = 00100 and the current output amp is more than E0.19. Solutions: 1: Check the current load. |
| A33 | A33 fault indicates Pre-warning of Weak Light. This means the drive's output frequency has remained at or below the lower limit of the PI output for longer than the set delay time, indicating a low-energy/weak light condition. Possible Causes: Output frequency is lower than or equal with lower limit of PI output frequency, and has continued under this state for a duration greater than delay time of weak light. Solutions: Check the lower limit of PI output frequency and weak-light delay the set value. |
| A34 | A34 fault indicates Pre-warning of Full-water. This means the water-level feedback signal has stayed below the set threshold for longer than the allowed delay time, triggering a full-water pre-warning. Possible Causes: Water-level feedback is lower than the set threshold and has continued under this state for a duration greater than the delay time. Solutions: Check the pre-warning point of water level. |
How to Clear & Reset Emotron VS Series Drive Faults
- Keypad Reset: Press the STOP/RST key on the integrated LED or LCD operator panel. Ensure the run command switch or terminal is opened before resetting the trip.
- Digital Input Reset (DI): If programmed in digital input function group (parameter group C0), pulse the assigned multi-function terminal (DI1–DI6) configured for the Fault Reset function.
- Automatic Fault Reset: Enable auto-reset functions via parameter E1-09 (Auto Reset Times) and E1-10 (Auto Reset Interval) to clear transient trips automatically.
- Modbus RTU Communication: Send a reset command by writing bit 7 (Fault Reset) in the communication control word via the built-in RS485 serial interface.
- Mains Power Cycle: Switch off the input AC power supply. Wait approximately 5 to 10 minutes until the keypad screen turns off and the internal DC bus charge LED is completely extinguished, then restore mains power.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that the DC bus voltage across (+) and (-) or braking terminals is strictly below 36V DC before touching motor leads, opening terminal covers, or handling terminals U, V, and W on the Emotron VS Series drive.