Emotron VSB Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Emotron VSB compact AC drive series. Search or filter through the complete fault code directory below.

Compact General Purpose Drive Power: 0.75 to 5.5 kW (1.0 to 7.5 HP) Embedded Modbus RTU (RS-485)
Power Range 0.75 – 5.5 kW (1 – 7.5 HP)
Supply Voltage 1-Ph 200–240V / 3-Ph 380–480V
Control Modes Sensorless Vector (SVC) & V/F
Operator Interface Detachable Keypad with Potentiometer

Complete Emotron VSB Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OC-1, OV-2, or OL-1).

Fault DisplayDescription, Causes, and Solutions
oC1
(Code: 1)

oC1 fault indicates Accel overcurrent.

This means the inverter's output current has exceeded the safe threshold during the motor's acceleration phase.



Possible Causes:

1: Torque boost is too big under V/f control.

2: Starting frequency is too high.

3: Accel time is too short.

4: Motor parameters are improperly set.

5: Output short circuit (phase-to-phase short circuit or output ground short circuit).

6: Overload is too heavy.

7: Inappropriate V/f curve under V/f control.

8: Restart the rotating motor.



Solutions:

1: Reduce torque boost value.

2: Drop starting frequency.

3: Prolong the Accel time.

4: Set the parameters correctly according to motor nameplate.

5: Check motor connection and output ground impedance.

6: Reduce the load.

7: Set V/f curve correctly.

8: Reduce current limited value or start through speed search.
oC2
(Code: 2)

oC2 fault indicates Constant-speed overcurrent.

This means the inverter's output current has exceeded the safe threshold while the motor was operating at a steady, constant speed.



Possible Causes:

1: Output short circuit (phase-to-phase short circuit or output ground short circuit).

2: Overload is too heavy.

3: Power rating of the drive is relatively small.

4: Input voltage is too low.



Solutions:

1: Check motor connection and output ground impedance.

2: Reduce the load.

3: Select appropriate drive power rating.

4: Check power grid voltage.
oC3
(Code: 3)

oC3 fault indicates Decel overcurrent.

This means the inverter's output current has exceeded the safe threshold during the motor's deceleration phase.



Possible Causes:

1: Output short circuit (phase-to-phase short circuit or output ground short circuit).

2: Load inertia is too big.

3: Decel time is too short.

4: Input voltage is too low.



Solutions:

1: Check motor connection and output ground impedance.

2: Use dynamic brake.

3: Prolong the Decel time.

4: Check power grid voltage.
ov1
(Code: 4)

ov1 fault indicates Accel overvoltage.

This means the drive's internal DC bus voltage has risen above the maximum safe limit during motor acceleration.



Possible Causes:

1: Load inertia is too big.

2: Abnormal input voltage.

3: Output short circuit (phase-to-phase short circuit or output ground short circuit).



Solutions:

1: Use dynamic brake.

2: Check power grid voltage.

3: Check motor connection and output ground impedance.
ov2
(Code: 5)

ov2 fault indicates Constant-speed overvoltage.

This means the inverter's internal DC bus voltage exceeded the safe limit while the motor was operating at a steady, constant speed.



Possible Causes:

1: Load variation is too big.

2: Abnormal input voltage.

3: Output short circuit (phase-to-phase short circuit or output ground short circuit).

4: Improper parameter setting of regulator under SVC control.



Solutions:

1: Check the load.

2: Check power grid voltage.

3: Check motor connection and output ground impedance.

4: Properly set regulator parameters.
ov3
(Code: 6)

ov3 fault indicates Decel overvoltage.

This means the drive's internal DC bus voltage has risen above the maximum safe limit during motor deceleration.



Possible Causes:

1: Load inertia is too big.

2: Abnormal input voltage.



Solutions:

1: Use dynamic braking.

2: Check power grid voltage.
FAL
(Code: 7)

FAL fault indicates Module protection.

This means the inverter's internal hardware protection for the power module has been triggered due to abnormal operating conditions.



Possible Causes:

1: Output short circuit (phase-to-phase short circuit or output ground short circuit).

2: Fan damaged or air duct blocked.

3: Direct connection of inverter module.

4: Switching power supply damaged.

5: Control board abnormal.

6: Ambient temperature is too high.

7: Loose connection of control board.

8: Overvoltage or overcurrent.



Solutions:

1: Check motor connection and output ground impedance.

2: Clear the air duct or replace the fan.

3: Seek services.

4: Seek services.

5: Seek services.

6: Reduce ambient temperature.

7: Pull out and reinsert the cables of control board.

8: Handle it with the solutions of overvoltage or overcurrent.
tUN
(Code: 8)

tUN fault indicates Parameter identification failed.

This means the drive could not successfully complete the auto-tuning process to determine the motor's electrical characteristics.



Possible Causes:

1: Bad motor connection.

2: Identification during rotation of the motor.

3: Bias between motor parameters and their setting is too big.



Solutions:

1: Check motor connection.

2: Identification in stationary status of the motor.

3: Set the parameters correctly according to motor nameplate.
oL1
(Code: 9)

oL1 fault indicates Drive overloaded.

This means the inverter is outputting a current higher than its rated capacity for a duration that exceeds its thermal overload limits.



Possible Causes:

1: Torque boost is too big under V/f control.

2: Starting frequency is too high.



Solutions:

1: Reduce torque boost value.

2: Drop starting frequency.
oL2
(Code: 10)

oL2 fault indicates Motor overloaded.

This means the motor is drawing current exceeding its rated capacity, triggering the drive's thermal protection algorithm for the motor.



Possible Causes:

1: Torque boost is too big under V/f control.

2: Inappropriate V/f curve under V/f control.

3: Motor parameters are improperly set.

4: Improper setting of motor overloaded protection time.

5: Motor stalled or sharp variation of load.

6: Long-term running of ordinary motor at low speed with heavy load.



Solutions:

1: Reduce torque boost value.

2: Set V/f curve correctly.

3: Set the parameters correctly according to motor nameplate.

4: Properly set the motor overloaded protection time.

5: Identify the causes of motor stalling or check the load condition.

6: Select variable frequency motor.
CtC
(Code: 11)

CtC fault indicates Current detection abnormal.

This means the drive's internal current sensing circuitry has failed or detected an implausible current reading.



Possible Causes:

1: Abnormal connection of control board.

2: Switching power supply damaged.

3: Hall device damaged.

4: Output ground leakage.



Solutions:

1: Seek services.

2: Seek services.

3: Seek services.

4: Seek services.
GdP
(Code: 12)

GdP fault indicates Output ground short-circuit protection.

This means a short circuit to ground has been detected on the output side of the drive or the motor.



Possible Causes:

1: Output connection ground short circuit.

2: Motor insulation abnormal.

3: Inverter module abnormal.

4: Output ground leakage current is too big.



Solutions:

1: Check motor connection and output ground impedance.

2: Check the motor.

3: Seek services.

4: Seek services.
ISF
(Code: 13)

ISF fault indicates Input power supply abnormal.

This means there is an issue with the incoming AC power supply, such as severe phase imbalance or a wiring issue.



Possible Causes:

1: Serious voltage imbalance among three phases of power supply.

2: Abnormal bus capacitance.

3: Abnormal input wiring of power supply.



Solutions:

1: Check power grid voltage.

2: Seek services.

3: Check power supply input wiring.
oPL
(Code: 14)

oPL fault indicates Output phase loss.

This means one or more phases in the power being delivered from the inverter to the motor are disconnected or severely unbalanced.



Possible Causes:

1: Motor cable connection abnormal.

2: Imbalance among motor three phases.

3: Incorrect setting of vector control parameters.



Solutions:

1: Check motor connection.

2: Check or replace the motor.

3: Correctly set vector control parameters.
oH1
(Code: 16)

oH1 fault indicates Heat sink thermal protection.

This means the temperature of the drive's internal heat sink has exceeded the safe operating threshold.



Possible Causes:

1: Ambient temperature is too high.

2: Fan damaged.

3: Air duct blocked.

4: Temperature sensor abnormal.

5: Inverter module abnormal.



Solutions:

1: Drop ambient temperature.

2: Replace the fan.

3: Clear air duct.

4: Seek services.

5: Seek services.
oH3
(Code: 18)

oH3 fault indicates Module temperature detection undisconnected.

This means the drive's internal temperature sensing circuit is failing to provide valid readings or is detecting an extreme out-of-bounds temperature.



Possible Causes:

1: Module detection circuit damaged.

2: Thermistor damaged.

3: Ambient temperature is too low.



Solutions:

1: Seek services.

2: Seek services.

3: Raise ambient temperature.
PEr
(Code: 24)

PEr fault indicates External equipment error.

This means the drive has received a fault signal from external machinery or an external sensor via its digital input terminals.



Possible Causes:

1: External fault terminal is enabled.

2: Stall condition lasts too long.



Solutions:

1: Check the status of external fault terminal.

2: Check if the load is abnormal.
to2
(Code: 26)

to2 fault indicates Consecutive running time attained.

This means the drive has been operating without stopping for a continuous duration that exceeds the pre-programmed time limit.



Possible Causes:

1: "Consecutive running time attained" enabled.



Solutions:

1: See specification of Group E0.
to3
(Code: 27)

to3 fault indicates Cumulative running time attained.

This means the total accumulated running time of the drive has reached the user-defined maximum threshold.



Possible Causes:

1: "Cumulative running time attained" enabled.



Solutions:

1: See specification of Group E0.
TrC
(Code: 31)

TrC fault indicates Port communication abnormal.

This means the serial communication link between the drive and an external controller or PC has been disrupted or configured incorrectly.



Possible Causes:

1: Improper setting of baud rate.

2: Communication port disconnection.

3: Upper computer/device does not work.

4: Drive communication parameter error.



Solutions:

1: Set properly.

2: Reconnect.

3: Make upper computer/device work.

4: Set properly.
oCr
(Code: 37)

oCr fault indicates Benchmark protection.

This means an internal hardware fault, specifically related to the reference voltage or benchmark switching power, has been detected.



Possible Causes:

1: Switching power supply damaged.

2: Control board damaged.



Solutions:

1: Seek services.

2: Seek services.
SP1
(Code: 38)

SP1 fault indicates 5V power supply out-of-limit.

This means the drive's internal 5-volt DC control power supply has drifted outside of acceptable operational limits.



Possible Causes:

1: Switching power supply damaged.

2: Control board damaged.



Solutions:

1: Seek services.

2: Seek services.
AIP
(Code: 40)

AIP fault indicates AI input out-of-limit.

This means the analog input signal received by the drive is either too high or too low compared to the configured allowable range.



Possible Causes:

1: Control board damaged.

2: AI input is too high or low.



Solutions:

1: Seek services.

2: Set AI input within correct range.
LoU
(Code: 41)

LoU fault indicates Undervoltage protection.

This means the incoming mains voltage or internal DC bus voltage has dropped below the minimum required for safe operation.



Possible Causes:

1: Input voltage abnormal.

2: Switching power supply abnormal.



Solutions:

1: Check input power grid voltage.

2: Seek services.
Plo
(Code: 45)

Plo fault indicates PID detection out-of-limit.

This means the feedback signal for the closed-loop PID controller has exceeded the acceptable deviation limits.



Possible Causes:

1: PID feedback channel abnormal.

2: Inappropriate setting of PID parameters.



Solutions:

1: Check the feedback channel.

2: Set properly.
ICF
(Code: 46)

ICF fault indicates Inside communication fault.

This means the internal data communication between the control board and the power board or microprocessors has failed.



Possible Causes:

1: Drive chip abnormal.

2: Severe noise on site.



Solutions:

1: Seek services.

2: Take corresponding countermeasures to the noise or seek service.

How to Clear & Reset Emotron VSB Drive Faults

  1. Keypad Reset: Press the red STOP/RESET button on the front operator panel. If the drive is commanded from remote terminals, ensure keypad reset authority is enabled in control parameter settings.
  2. Digital Input (DI) Terminal Reset: Configure any multi-function digital input terminal (X1 to X4) to the fault reset function. Apply a momentary 24V DC signal to reset the active trip condition.
  3. Modbus RTU Communication: Send a fault clear command via the onboard RS-485 serial communication port (terminals 485+ and 485-) by setting the reset bit in the serial control register.
  4. Automatic Fault Reset: For non-critical trip conditions such as transient overvoltage or temporary overcurrent, configure the auto-reset parameters to allow automatic clearance after a programmed delay.
  5. Mains Power Cycle: Disconnect AC input mains power. Wait at least 5 minutes until the LED display and charge lamp turn off completely to discharge intermediate capacitors, then reapply power.
⚠️ High-Voltage Electrical Safety Warning: Always wait at least 5 minutes after disconnecting AC supply power and verify with a calibrated digital multimeter that intermediate DC bus voltage across terminals [+ / -] measures strictly below 36V DC before inspecting terminals, removing covers, or touching motor leads U, V, and W on the Emotron VSB drive.