Fuji

Home / Fuji

Fuji Electric Drives Fault Codes & Troubleshooting

Technical diagnostic directory for Fuji Electric FRENIC industrial AC drives, FVR micro inverters, and Alpha AC servo motion systems. Select your drive model series below to access parameter checks, trip code descriptions, and physical test sequences.

12 FRENIC & FVR Series 2 Alpha Servo Systems Dynamic Torque Vector Control

Fuji Electric FRENIC & FVR Inverters

12 Models

Fuji Electric Alpha AC Servo Systems

2 Models

Most Common Fuji Electric Fault Codes

Diagnostic Quick Reference
Trip Code Trip Name Common Physical Trigger Recommended First Check
OC1 Overcurrent (Acceleration) Inverter output current exceeded threshold during ramp-up due to short accel time or jammed motor shaft. Increase acceleration ramp time (Function Code F07) and inspect motor leads with cables disconnected.
OC2 / OC3 Overcurrent (Decel / Constant) Excessive deceleration rate or sudden mechanical load fluctuation during steady operation. Extend deceleration ramp time (Function Code F08) and verify mechanical torque load.
OU1 / OU2 DC Bus Overvoltage Motor regeneration energy during deceleration charging internal DC link capacitors above safe limit (400V/800V). Verify dynamic braking resistor connectivity across P(+) and DB terminals; enable torque limiter.
LU Undervoltage Main DC link voltage fell below minimum allowable level due to utility power outage or loose line terminal. Measure incoming line AC voltage across L1/R, L2/S, L3/T and inspect main magnetic contactor.
OH1 Heatsink Overheat Inverter power module heatsink temperature exceeded maximum operating threshold. Inspect cooling fan operation, clean heatsink air channels, and replace clogged enclosure intake filters.
OL1 Motor 1 Overload Electronic thermal relay tripped due to prolonged continuous operation above motor rated full load amps. Check thermal overload setting in Function Code F10/F11 against motor physical nameplate rating.
OLU Inverter Overload Inverter internal power semiconductors (IGBTs) overloaded by continuous heavy cycle operation. Lower carrier frequency (Function Code F26) and verify drive sizing against heavy machine duty requirements.
EF Ground Fault Current leakage to earth detected at inverter output terminals (U, V, W). Inspect motor cable insulation for cuts/pinches and test motor stator windings with a 500V Megger.

How to Clear & Reset Fuji Electric VFD Faults

  1. Keypad Reset: Press the red RESET key on the standard keypad (TP-E1U) or multifunction LCD operator (TP-G1-J1).
  2. Control Terminal Reset (RST): Momentarily close the digital input terminal assigned to function [RST] (Default setting `9` in function codes E01–E09).
  3. FRENIC Loader Software: Connect via USB or RS-485 interface, navigate to the diagnostic monitor window, and click “Trip Reset”.
  4. Power Cycle: Disconnect incoming 3-phase power supply, wait until the keypad 7-segment display and charge lamp extinguish completely, and restore line power.
⚠️ High-Voltage Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus capacitor voltage measures strictly below 50VDC across terminals [P(+)] and [N(-)] before opening enclosure covers or inspecting terminals U, V, and W on any Fuji Electric drive.