Hitachi NE-S1 inverter

Home / Hitachi / Hitachi NE-S1 inverter

Hitachi NE-S1 Inverter Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, LED status indications, and step-by-step troubleshooting procedures for the Hitachi NE-S1 ultra-compact AC inverter series. Search or filter through the complete fault code directory below.

Ultra-Compact Micro Inverter Power: 0.2 to 4.0 kW (0.25 to 5.0 HP) Built-in RS-485 Modbus RTU
Power Range 0.2 – 4.0 kW (0.25 – 5.0 HP)
Supply Voltage 1-Ph 200–240V / 3-Ph 200–240V & 380–480V
Control Modes Sine Wave PWM V/f Control (Variable / Constant)
Operator Interface Integrated RUN/STOP/RESET & Optional Keypad

Complete Hitachi NE-S1 Inverter Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type E01, E07, E09, or Overcurrent).

Fault Code and MeaningCause and Remedy
E01
Over-current event while at constant speed

Cause:

The inverter output was short-circuited, or the motor shaft is locked or has a heavy load. These conditions cause excessive current for the inverter, so the inverter output is turned OFF. The dual-voltage motor may be wired incorrectly.



Remedy:


  • Check for short circuits at the output.

  • Check if the motor shaft is locked or load is too heavy.

  • Verify motor wiring.


E02
Over-current event during deceleration

Cause:

The inverter output was short-circuited, or the motor shaft is locked or has a heavy load. These conditions cause excessive current for the inverter.



Remedy:


  • Check braking requirements or deceleration time.

  • Check for short circuits or mechanical locks.


E03
Over-current event during acceleration

Cause:

The inverter output was short-circuited, or the motor shaft is locked or has a heavy load.



Remedy:


  • Check acceleration time setting.

  • Verify motor wiring and mechanical load.


E04
Over-current event during other conditions

Cause:

The inverter output was short-circuited, or the motor shaft is locked or has a heavy load.



Remedy:


  • General check of output wiring and motor condition.


E05
Overload protection

Cause:

When a motor overload is detected by the electronic thermal function, the inverter trips and turns OFF its output.



Remedy:


  • Reduce motor load.

  • Note: The inverter will not accept any reset command within about 10 seconds after tripping.


E07
Over-voltage protection

Cause:

When the DC bus voltage exceeds a threshold, due to regenerative energy from the motor.



Remedy:


  • Check deceleration time (increase if possible).

  • Check for need of braking resistor.


E08
Memory error

Cause:

When the built-in memory has problems due to noise or excessive temperature, the inverter trips and turns OFF its output to the motor.



Remedy:


  • Turn off the inverter power once.

  • If E08 displays again after power up, the internal memory may have failed.

  • Initialize the inverter and re-set parameters.


E09
Under-voltage error

Cause:

A decrease of internal DC bus voltage below a threshold results in a control circuit fault. This condition can also generate excessive motor heat or cause low torque.



Remedy:


  • Check input power supply voltage.

  • Check for power interruptions.


E10
Current detection error

Cause:

If an error occurs in the internal current detection system, the inverter will shut off its output and display the error code.



Remedy:


  • Check for electrical noise interference.

  • Contact service if error persists.


E11
CPU error

Cause:

A malfunction in the built-in CPU has occurred, so the inverter trips and turns OFF its output to the motor.



Remedy:


  • The inverter will not accept reset commands via RS terminal or keypad.

  • Turn off the inverter power and restart.


E12
External trip

Cause:

A signal on an intelligent input terminal configured as EXT has occurred. The inverter trips and turns OFF the output to the motor.



Remedy:


  • Remove the external trip signal.

  • Reset the inverter.


E13
USP error

Cause:

When the Unattended Start Protection (USP) is enabled, an error occurred when power is applied while a Run signal is present.



Remedy:


  • Ensure Run signal is OFF before powering up.

  • Clear the error to enter Run Mode.


E14
Ground fault protection

Cause:

The inverter is protected by the detection of ground faults between the inverter output and the motor upon during powerup tests.



Remedy:


  • Check motor and cabling for ground faults.

  • Turn off the inverter power to reset (Keypad reset not accepted).


E15
Input over-voltage protection

Cause:

The inverter tests for input over-voltage after the inverter has been in Stop Mode for 100 seconds. An over-voltage condition exists.



Remedy:


  • Check input power supply voltage.

  • After fault is cleared, inverter can enter Run Mode again.


E19
Inverter thermal detection circuit error

Cause:

When the thermal sensor in the inverter module is not connected.



Remedy:


  • Internal hardware check required.


E21
Temperature error

Cause:

When the inverter internal temperature is above the threshold, the thermal sensor detects excessive temperature of power devices.



Remedy:


  • Check cooling fan operation.

  • Check for blocked ventilation or high ambient temperature.


E30
Driver error

Cause:

An internal inverter error has occurred at the safety protection circuit between the CPU and main driver unit. Excessive electrical noise may be the cause.



Remedy:


  • Check for EMC/Electrical noise sources.

  • Turn power off and on.


E34
Output phase loss protection

Cause:

When a phase loss on its outputs is detected, the inverter output is turned off. (Activated only when C157=01).



Remedy:


  • Check output wiring for loose connections.

  • Check motor phases.


E38
Low-speed overload protection

Cause:

If overload occurs during the motor operation at a very low speed, the inverter will detect the overload and shut off the output.



Remedy:


  • Reduce load at low speeds.


E40
Operator connection error

Cause:

When the connection between inverter and operator keypad failed.



Remedy:


  • Check connection between keypad and inverter.


E41
Modbus communication error

Cause:

When "trip" is selected (C076=00) as a behavior in case of communication error, inverter trips when timeout happens.



Remedy:


  • Check Modbus communication lines.

  • Check communication settings.


How to Clear & Reset Hitachi NE-S1 Inverter Faults

  1. Standard Front Panel Reset: Press the unified RUN/STOP/RESET button on the front of the inverter once the error cause has been eliminated. If using an optional digital operator (NES1-OP or OPE-SR/SBK), press the red STOP/RESET key. Note that the reset triggers when releasing the key.
  2. Intelligent Terminal Reset (RS): If an intelligent digital input terminal (terminals 1 through 5) is assigned to function 18: RS (Reset), close the contact for at least 12 ms, then open it. The fault clears on the falling edge of the RS signal.
  3. ProDriveNext PC Software: Connect your PC via the RS-485 serial communication port (RJ45 interface), open Hitachi ProDriveNext, check the trip history log under parameter d081, and issue a software fault reset command.
  4. Modbus RTU Communication: Write a logic ‘1’ to the Reset control bit via RS-485 Modbus RTU network registers to remotely clear trip conditions from a PLC or HMI.
  5. Mains Power Cycle: Switch off the main AC line power (terminals L1, L2, N/L3). Wait at least 10 minutes until the internal charge lamp / display turns completely off and intermediate capacitors discharge, then restore power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [+1/PD] and [-] (or between [+] and [-]) before inspecting motor wiring, opening protective terminal covers, or touching output terminals U/T1, V/T2, and W/T3 on the Hitachi NE-S1 drive.