Hitachi SJ-P1 Drive Fault Codes & Diagnostic Guide

Comprehensive fault code reference directory, trip alarm causes, and step-by-step diagnostic procedures for the Hitachi SJ Series Type P1 (SJ-P1) high-performance industrial inverter. Search or filter through the complete fault code directory below.

Advanced Multi-Mode Inverter Power: 0.4 to 160 kW (0.5 to 250 HP) Induction & PM Motor Control
Power Range 0.4 – 160 kW (0.5 – 250 HP)
Supply Voltage 200–240V / 380–500V (3-Phase)
Control Modes IM / PM Sensorless Vector & V/f
Operator Interface Full-Color TFT LCD Operator

Complete Hitachi SJ-P1 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type E001, E005, or Overcurrent).

Fault Code and MeaningCause and Remedy
E001

Overcurrent error

Cause:


  • A steep load change occurred or motor hunting.

  • Insufficient acceleration or deceleration time.

  • Output line short-circuit, ground fault, or motor lock.

  • System environment changes or aging deterioration.




Remedy:


  • Adjust Overcurrent suppression [bA120] or Overload limit [bA122].

  • Increase acceleration time [FA-10] or deceleration time [FA-12].

  • Check wiring and motor insulation.

  • Clean fans/ducts or reduce motor load.


E005

Motor overload error

Cause:


  • Operation under heavy load continued.

  • Thermal level setting [bC110] is incorrect.

  • Insufficient acceleration torque or load inertia is large.

  • Overvoltage suppression function is active causing current increase.




Remedy:


  • Re-examine operation/load conditions.

  • Adjust motor thermal level setting [bC110].

  • Increase acceleration [FA-10] or deceleration [FA-12] time.

  • Clean cooling fan/ducts if environment is hot.


E006

Braking resistor overload error

Cause:


  • Insufficient deceleration time.

  • Load inertia is large or capacity of braking resistor is small.

  • Continuous regenerative operation or external force rotating the motor.




Remedy:


  • Set longer deceleration time in [FA-12].

  • Re-examine choice of resistor capacity.

  • Reduce repetition cycle of operation.


E007

Overvoltage error

Cause:


  • Power supply voltage fluctuation.

  • Large load inertia causing high regenerative power.

  • Motor rotated by external force (fan, crane).

  • Mutual interference from two inverters on the same shaft.




Remedy:


  • Check power supply; consider AC reactor.

  • Enable overvoltage suppression [bA140]/[bA146].

  • Use a braking resistor, braking unit, or regenerative converter.

  • Increase deceleration time [FA-12].


E008

Memory error

Cause:


  • Noise interference.

  • Power-off occurred during memory access.




Remedy:


  • Install noise shielding plates.

  • Restore data from keypad backup or initialize inverter.

  • If initialization fails, repair is required.


E009

Undervoltage error

Cause:


  • Power supply voltage decreased or power failure.

  • PS capacity insufficient.

  • Contact fault in circuit breaker.

  • Capacitor deterioration or circuit failure.




Remedy:


  • Re-examine power supply environment.

  • Use retry function if failure was temporary.

  • Check magnetic contactor/breaker. Repair if necessary.


E010

Current detector error

Cause:


  • Current detector circuit is broken.

  • Noise source is nearby.




Remedy:


  • If error recurs after reset, repair is required.

  • Implement noise countermeasures (shielding).


E011

CPU error

Cause:


  • Internal CPU malfunction.

  • Noise source nearby.

  • Data inconsistency during writing.




Remedy:


  • Reset, power cycle, or initialize the inverter.

  • If no recovery, CPU is broken (repair required).

  • Use shielding plates against noise.


E012

External trip error

Cause:


  • External device triggered the trip signal.

  • Terminal logic reversed or wiring wrong.




Remedy:


  • Check external device status.

  • Verify input terminal assignment and A/B contact settings.


E013

USP error

Cause:


  • Operation command entered immediately upon power ON (within 1-2 seconds).

  • Operation command was not released before power ON.




Remedy:


  • Wait 2 seconds or longer after power ON to enter operation command.

  • Release operation command (switch off) before turning on power.


E014

Ground fault error

Cause:


  • Ground fault in wires or motor.

  • Motor insulation deterioration.




Remedy:


  • Turn OFF power. Disconnect motor wires. Check motor/wires.

  • Do not turn ON power while ground fault exists.


E015

Incoming overvoltage error

Cause:


  • Incoming voltage is too high.

  • Power supply has become unstable.




Remedy:


  • Re-examine power supply environment.

  • Check for facility replacements causing voltage changes.


E016

Instantaneous power failure error

Cause:


  • PS voltage decreased due to power failure.

  • Contact fault in circuit breaker.




Remedy:


  • Check power supply capacity.

  • Check magnetic contactor/breaker.


E019

Temperature detector error

Cause:


  • Temperature detector circuit disconnected or broken.




Remedy:


  • Repair is required (circuit broken).


E020

Cooling fan rotation speed reduction error

Cause:


  • Foreign object stuck in fan.

  • Fan end of life.




Remedy:


  • Remove foreign object.

  • Replace cooling fan.


E021

Temperature error

Cause:


  • High carrier frequency.

  • Clogged heatsink fins.

  • High ambient temperature or poor ventilation.

  • Improper installation.




Remedy:


  • Lower carrier frequency setting.

  • Clean the fins.

  • Improve cooling environment.

  • Install according to manual.


E024

Input open-phase error

Cause:


  • Input line/motor loose connection.

  • Single-phase input used on 3-phase setting.




Remedy:


  • Check input lines and breaker terminals. Tighten screws.

  • Use three-phase connection.


E030

IGBT error

Cause:


  • Ground fault, short circuit, or output element failure.

  • Motor rotation locked.




Remedy:


  • Disconnect motor and check wires/insulation.

  • Remove cause of motor lock.

  • If element broken, repair required.


E034

Output open-phase error

Cause:


  • Output line/motor loose connection or disconnected.

  • Motor insulation breakdown.




Remedy:


  • Check output wiring and motor condition.

  • Re-tighten screws.


E035

Thermistor error

Cause:


  • Motor overheated (cooling insufficient or heavy load).

  • Inadequate thermistor setting.

  • Thermistor broken or noise interference.




Remedy:


  • Improve cooling or reduce load.

  • Check thermistor settings and wiring.

  • Separate wiring to reduce noise.


E036

Brake error

Cause:


  • Disconnection of brake check signal line.

  • Brake function setting (timing/logic) incorrect.




Remedy:


  • Check signal wiring.

  • Re-examine brake check waiting time and logic.


E038

Low-speed range overload error

Cause:


  • Motor load is heavy at low frequency (0.2Hz or below).




Remedy:


  • Reduce load at low-speed range.

  • Select larger capacity inverter if frequent.


E039

Controller (inverter) overload error

Cause:


  • Operation under heavy load continued.

  • Insufficient acceleration torque.

  • Load inertia is large.




Remedy:


  • Check load condition.

  • Adjust boost function [Hb141] or control method.

  • Increase accel/decel time.


E040

Operator keypad communication error

Cause:


  • Loose connection/disconnection.

  • Noise interference.




Remedy:


  • Check wiring/connection.

  • Take noise countermeasures (wiring separation).


E041

RS485 communication error

Cause:


  • Loose connection/disconnection.

  • Noise interference.




Remedy:


  • Check wiring.

  • Take noise countermeasures.


E042

RTC error

Cause:


  • Keypad battery runs out.




Remedy:


  • Replace battery and set date.


E043

EzSQ illegal instruction error

Cause:


  • Program not entered or writing error due to noise.




Remedy:


  • Write program after initialization.

  • Avoid noise during writing.


E044

EzSQ nest count error

Cause:


  • Program structure too complicated (nesting > 8 times).




Remedy:


  • Improve program structure.


E045

EzSQ executive instruction error

Cause:


  • Program flow inadequate (invalid "for/next/goto").

  • Math overflow/underflow/div by zero.

  • Non-existing parameter accessed.




Remedy:


  • Check program logic and arithmetic operations.

  • Check parameter instructions.


E050 to E059

EzSQ user-assigned errors

Cause:


  • Program triggered a user-assigned error instruction.




Remedy:


  • Check content of trip instruction in EzSQ program.


E060 to E089

Option 1/2/3 errors

Cause:


  • Option not securely mounted.

  • Option used incorrectly.




Remedy:


  • Check option mounting.

  • Refer to specific option manual.


E090 to E096

STO path / FS option error

Cause:


  • Safety function system has problems.




Remedy:


  • Refer to "Functional Safety Guide".


E100

Encoder disconnection error

Cause:


  • Feedback option error.




Remedy:


  • Refer to P1-FB user's guide.


E104

Position control range error

Cause:


  • Position counter exceeded range.

  • Improper electronic gear or encoder setting.

  • Slipping due to mounting.




Remedy:


  • Recheck electronic gear/encoder settings.

  • Check encoder mounting.


E105

Speed deviation error

Cause:


  • Deviation between frequency command and feedback speed.

  • Improper encoder/gear setting.




Remedy:


  • Re-examine load conditions.

  • Check encoder/gear settings.


E106

Position deviation error

Cause:


  • Position feedback deviation exceeds limit.




Remedy:


  • Re-examine load conditions.

  • Check encoder/gear settings.


E107

Over-speed error

Cause:


  • Speed exceeded detection level.




Remedy:


  • Re-examine operation/load conditions.

  • Check encoder/gear settings.


E110

Contactor error

Cause:


  • Wiring defect in intelligent input.

  • Contactor response defect.




Remedy:


  • Check setting and wiring of intelligent input.

  • Check contactor operation and response time.


E112

Feedback option connection error

Cause:


  • Connection error related to feedback options.




Remedy:


  • Refer to P1-FB user's guide.


How to Clear & Reset Hitachi SJ-P1 Drive Faults

  1. Keypad Reset: Press the red STOP/RESET key on the standard color TFT LCD operator. For thermal overload (E005) or severe instantaneous overcurrent (E001–E004) trips, allow a 10 to 15-second cooling interval before resetting.
  2. Intelligent Input Terminal Reset (RS): Pulse the digital input terminal assigned to function 028 [RS] (Reset) for at least 12 ms, then open the terminal circuit.
  3. Run Command Interlock Check: Ensure that active forward [FW] or reverse [REV] run commands are turned OFF before initiating a reset; clearing an alarm while a run command is asserted will either initiate an instant start or trigger E013 (USP – Unattended Start Protection).
  4. ProDriveNext PC Tool / USB: Connect a PC via the micro-USB port on the front of the color operator, open Hitachi ProDriveNext software, and issue a digital fault clear command from the diagnostic monitor window.
  5. Fieldbus Network Reset: Write the reset command bit via embedded RS-485 Modbus RTU or optional communication slot cassettes (EtherCAT, Profinet, Ethernet/IP, Profibus-DP) from your PLC.
  6. Main Power Cycle: Switch off main 3-phase AC power, wait at least 5 to 10 minutes until the internal charge lamp completely extinguishes (confirming intermediate DC bus capacitors have discharged safely), and reapply line power.
⚠️ High-Voltage Electrical Safety Warning: Hazardous voltage remains stored in the intermediate DC bus capacitors even after switching off the AC power supply. Always wait a minimum of five (5) to ten (10) minutes after powering down, and verify with a calibrated DC voltmeter that voltage across terminals [+1] / [P/+] and [-] / [N/-] has dropped below 50VDC before removing protective covers, inspecting motor leads, or servicing output terminals U, V, and W.