Hitachi SJ200 Inverter Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Hitachi SJ200 sensorless vector drive series. Search or filter through the complete fault code directory below.
Power Range
0.2 – 7.5 kW (1/4 – 10 HP)
Supply Voltage
200–240V / 380–480V AC
Control Modes
Sensorless Vector & V/f Control
Operator Interface
Digital Keypad & Frequency Potentiometer
Complete Hitachi SJ200 Inverter Fault Code Directory
Use the search box in the table below to quickly find your error code (e.g., type E01, E07, E14, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| E01 Over-current event while at constant speed | Cause: The inverter output was short-circuited, or the motor shaft is locked or has a heavy load. These conditions cause excessive current for the inverter, so the inverter output is turned OFF. The dual-voltage motor is wired incorrectly. Remedy:
|
| E02 Over-current event during deceleration | Cause: The inverter output was short-circuited, or the motor shaft is locked or has a heavy load. The dual-voltage motor is wired incorrectly. Remedy:
|
| E03 Over-current event during acceleration | Cause: The inverter output was short-circuited, or the motor shaft is locked or has a heavy load. The dual-voltage motor is wired incorrectly. Remedy:
|
| E04 Over-current event during other conditions | Cause: The inverter output was short-circuited, or the motor shaft is locked or has a heavy load. The dual-voltage motor is wired incorrectly. Remedy:
|
| E05 Overload protection | Cause: When a motor overload is detected by the electronic thermal function, the inverter trips and turns OFF its output. Remedy:
|
| E06 Braking resistor overload | Cause: When the regenerative braking resistor exceeds the usage time allowance or usage ratio, the inverter trips and turns OFF its output to the motor. Remedy:
|
| E07 Over-voltage protection | Cause: When the DC bus voltage exceeds a threshold, due to regenerative energy from the motor. Remedy:
|
| E08 EEPROM error | Cause: When the built-in EEPROM memory has problems due to noise or excessive temperature, the inverter trips and turns OFF its output to the motor. Remedy:
|
| E09 Under-voltage error | Cause: A decrease of internal DC bus voltage below a threshold results in a control circuit fault. This condition can also generate excessive motor heat or cause low torque. Remedy:
|
| E11, E22 CPU error | Cause: A malfunction in the built-in CPU has occurred, so the inverter trips and turns OFF its output to the motor. Remedy:
|
| E12 External trip | Cause: A signal on an intelligent input terminal configured as EXT has occurred. The inverter trips and turns OFF the output to the motor. Remedy:
|
| E13 USP (Unattended Start Protection) | Cause: When the Unattended Start Protection (USP) is enabled, an error occurred when power is applied while a Run signal is present. Remedy:
|
| E14 Ground fault | Cause: The inverter is protected by the detection of ground faults between the inverter output and the motor during powerup tests. Remedy:
|
| E15 Input over-voltage | Cause: The inverter tests for input over-voltage after the inverter has been in Stop Mode for 100 seconds. If an over-voltage condition exists, the inverter enters a fault state. Remedy:
|
| E21 Inverter thermal trip | Cause: When the inverter internal temperature is above the threshold, the thermal sensor in the inverter module detects the excessive temperature of the power devices and trips. Remedy:
|
| E23 Gate array error | Cause: An internal inverter error has occurred in communications between the CPU and gate array IC. Remedy:
|
| E35 Thermistor | Cause: When a thermistor is connected to terminals [6] and [L] and the inverter has sensed the temperature is too high, the inverter trips and turns OFF the output. Remedy:
|
| E60 Communications error | Cause: The inverter’s watchdog timer for the communications network has timed out. Remedy:
|
| - - - Under-voltage (brown-out) with output shutoff | Cause: Due to low input voltage, the inverter turns its output OFF and tries to restart. If it fails to restart, then the alarm trips to record the under-voltage error event. Remedy:
|
How to Clear & Reset Hitachi SJ200 Inverter Faults
- Keypad Stop/Reset Key: Press the red STOP/RESET key on the front digital operator panel while the trip code (E01–E60) is displayed. Note: The Stop/Reset key acts as a reset command only during a drive trip condition.
- Intelligent Input Terminal Reset [RS]: Trigger the digital input terminal assigned to Reset function
18 (RS)(Terminal 5 is configured by default as RS in parameterC005 = 18). The inverter clears the fault when the RS terminal input transitions from ON to OFF. - Serial Network Reset (RS-485): Send an inverter trip reset command via the built-in Modbus RTU communication network over the serial link to remotely clear the alarm state.
- Power Cycle: Turn OFF the main AC supply power. Wait at least 10 minutes until the internal intermediate DC bus capacitors fully discharge and the front charge lamp completely turns off before reapplying mains power.
⚠️ High-Voltage Electrical Safety Warning:
Dangerous residual electrical energy remains stored in the intermediate DC bus capacitors after main supply power is disconnected. Wait at least 10 minutes after turning off the AC power and ensure the red “CHARGE” LED indicator is completely dark. Always verify with a calibrated digital multimeter that the DC bus voltage across terminals [+] and [-] (or P and N) measures strictly below 50VDC before inspecting motor leads, wiring terminal blocks, or touching inverter output terminals U/T1, V/T2, and W/T3.