Hitachi SJ700D Inverter Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Hitachi SJ700D high-performance industrial inverter series. Search or filter through the complete fault code directory below.

High Performance Vector Drive Power: 0.4 to 400 kW (0.5 to 550 HP) EzSQ Logic Programming & Modbus RTU
Power Range 0.4 – 400 kW (0.5 – 550 HP)
Supply Voltage 200–240V / 380–480V AC (3-Phase)
Control Modes Sensorless Vector, 0Hz SLV & Closed Loop
Operator Interface Detachable Digital Keypad / WOP Copy Unit

Complete Hitachi SJ700D Inverter Fault Code Directory

Use the search box in the table below to quickly find your error code (e.g., type E01, E09, E14, or Overcurrent).

Fault Code and MeaningCause and Remedy
E01 / E02 / E03 / E04

Overcurrent protection

Cause:
The motor was constrained or suddenly accelerated/decelerated, causing high current to flow. The inverter detected current higher than the specified level.

  • E01: During constant speed operation.

  • E02: During deceleration.

  • E03: During acceleration.

  • E04: Others.




Remedy:

  • Check for short circuits or ground faults.

  • Check if the motor load is too heavy or constrained.

  • Adjust acceleration/deceleration times.


E05

Overload protection

Cause:
The internal electronic thermal protection circuit has detected a motor overload based on the output current.



Remedy:

  • Check the motor load magnitude.

  • Check the electronic thermal protection settings.


E06

Braking resistor overload protection

Cause:
The BRD (Braking Resistor) operation rate exceeded the setting of "b090".



Remedy:

  • Check the braking usage ratio.

  • Increase deceleration time or check the "b090" setting.


E07

Overvoltage protection

Cause:
DC voltage across P and N terminals is too high. This can happen due to regenerative energy from the motor or high input voltage.

Trip levels: >400 VDC (200V class) or >800 VDC (400V class).



Remedy:

  • Check if input voltage is within specifications.

  • Check if deceleration is too fast (regenerative energy).


E08

EEPROM error

Cause:
Internal EEPROM error caused by external noise, abnormal temperature rise, or CPU error.



Remedy:

  • Turn off the inverter power and turn it back on.

  • If E08 persists, initialize the inverter and re-set parameters.

  • Check for external noise sources.


E09

Under voltage

Cause:
Input voltage dropped, causing the DC voltage across P and N terminals to fall below the specified level.

Trip levels: <175 VDC (200V class) or <345 VDC (400V class).



Remedy:

  • Check the input power supply voltage.

  • Check for power failures or loose connections.


E10

CT error

Cause:
Error in the internal current detector (CT). The CT outputs about 0.6 V or more at power-on.



Remedy:

  • Hardware failure likely; contact service/repair.


E11

CPU error

Cause:
Internal CPU malfunction or error. Can also be caused by reading abnormal data from EEPROM.



Remedy:

  • Turn power off and on again.

  • Check grounding and noise interference.


E12

External trip

Cause:
An error occurred in external equipment connected to the inverter, triggering the external trip signal.



Remedy:

  • Check the external device connected to the trip terminal.

  • Resolve the fault in the external system.


E13

USP error

Cause:
Power was turned on while an input operation signal was already active (remaining in the inverter).



Remedy:

  • Turn off the run command before powering on the inverter.

  • Check the USP function settings.


E14

Ground-fault protection

Cause:
A ground fault was detected between the inverter output circuit and the motor upon power-on.



Remedy:

  • Check motor and cables for insulation failure or ground faults.


E15

Input overvoltage protection

Cause:
Input voltage kept above specification level for 100 seconds while stopped.



Remedy:

  • Check the power source voltage.


E16

Instantaneous power failure protection

Cause:
Instantaneous power failure lasted 15 ms or more.



Remedy:

  • Check power supply stability.


E20

Temperature error (Fan)

Cause:
Cooling-fan speed lowering detected.



Remedy:

  • Check cooling fan for obstruction or failure.

  • Clean air vents.


E21

Temperature error (Main)

Cause:
Main circuit temperature rose due to high ambient temperature or other reasons.



Remedy:

  • Check ambient temperature.

  • Ensure proper ventilation around the inverter.


E23

Gate array communication error

Cause:
Communication error between the internal CPU and gate array.



Remedy:

  • Internal hardware issue. Turn power off/on.


E24

Phase loss input protection

Cause:
Input phase loss detected (when enabled via b006=01). Phase loss continued for about 1 second or more.



Remedy:

  • Check input power wiring (R, S, T) for loose connections or open phases.


E25

Main circuit error

Cause:
Gate array cannot confirm the on/off state of IGBT due to noise, short, or damage.



Remedy:

  • Check for excessive noise.

  • Inverter hardware may be damaged.


E30

IGBT error

Cause:
Instantaneous overcurrent, abnormal main circuit element temperature, or drive power drop. The inverter shuts off to protect the element.



Remedy:

  • Cannot retry operation immediately. Turn off power and check motor/output for shorts.


E34

Phase loss output protection

Cause:
Output phase loss detected (when enabled via b141=01) while output frequency is 5 Hz to 100 Hz.



Remedy:

  • Check output wiring (U, V, W) to the motor.


E35

Thermistor error

Cause:
The resistance of the thermistor connected to the TH terminal indicates the motor temperature has risen.



Remedy:

  • Check motor temperature.

  • Allow motor to cool down.


E37

Emergency stop

Cause:
EMR signal (on three terminals) turned on, or slide switch (SW1) set to ON. Malfunction due to noise if EMR not ON.



Remedy:

  • Check EMR terminal status.

  • Reset the inverter by turning on the RS terminal (Digital operator reset not accepted).


E38

Low-speed overload protection

Cause:
Overload occurred during motor operation at very low speed (0.2 Hz or less).



Remedy:

  • Check load at low speeds.


E41

Modbus communication error

Cause:
Timeout occurred due to line disconnection during Modbus-RTU communication.



Remedy:

  • Check communication cables and settings (C076).


E43

Invalid instruction

Cause:
Inverter detected error in "Easy Sequence".



Remedy:

  • Refer to SJ700D-3 instruction manual regarding Easy Sequence programming.


E44

Nesting count error

Cause:
Inverter detected error in "Easy Sequence".



Remedy:

  • Refer to SJ700D-3 instruction manual regarding Easy Sequence programming.


E45

Execution error

Cause:
Inverter detected error in "Easy Sequence".



Remedy:

  • Refer to SJ700D-3 instruction manual regarding Easy Sequence programming.


E50 to E59

User Trip

Cause:
The inverter detects errors in the easy sequence.



Remedy:

  • Refer to SJ700D-3 instruction manual.


E60 to E69

Option 1 error

Cause:
Error in the option board mounted in optional slot 1.



Remedy:

  • Refer to the instruction manual for the mounted option board.


E70 to E79

Option 2 error

Cause:
Error in the option board mounted in optional slot 2.



Remedy:

  • Refer to the instruction manual for the mounted option board.


How to Clear & Reset Hitachi SJ700D Inverter Faults

  1. Keypad Stop/Reset Key: Press the red STOP/RESET key on the front digital operator panel while a trip code (E01–E60) is displayed. The Stop/Reset key acts as a reset command only when the inverter is in an active trip state.
  2. Intelligent Input Terminal Reset [RS]: Energize and then release the control terminal mapped to the Reset function 18 (RS) (configurable across inputs 1 to 8). The inverter completes the fault reset when the assigned RS terminal transitions from ON to OFF.
  3. Network Communication Reset: Send a trip reset command via the standard Modbus RTU RS-485 interface or optional communication fieldbus cards (Profibus-DP, DeviceNet, or CANopen) by asserting the communication reset control bit.
  4. Power Cycle: Disconnect main three-phase AC power. Wait at least 10 minutes until the internal DC bus capacitors have fully discharged and the front “CHARGE” indicator LED is completely unlit before restoring power.
⚠️ High-Voltage Electrical Safety Warning: Lethal electrical voltages remain stored in the intermediate DC bus capacitors even after primary AC line power is turned off. Wait at least 10 to 15 minutes after power-down and verify that the red “CHARGE” LED has completely extinguished. Always verify with a calibrated digital multimeter that the DC bus voltage across terminals [+] and [-] (or P and N) measures strictly below 50VDC before removing terminal covers, checking connections, or touching terminals U/T1, V/T2, and W/T3.